
18.Set thelow gas pressureswitchto tripat20%less thanthe sensed gas pressure with theburnerfiring
at the high fire rate.
19. Proceed to warmup the boiler following the recommended procedure as provided bythe boiler
manufacturer. Intheabsenceofthese boiler manufacturers instructions, warmup the boilerat low fire
onlyfollowing a cycle of5 minutes on and 5 minutes off for 5 cycles then continuous lowfire until the
boiler reaches the desired operating pressure or temperature.Note: It maybenecessaryto limit the
boiler load inordertoobtain operating pressureortemperature atthe low firerate. Onlyafter reaching
the boiler operating pressure or temperature should the boiler be fired at full firing rate.
20. All HAC burners aredesignedfor modulation. The modulating motoris connected bylinkageto the air
inlet dampers and fuel metering devices. Each control point has its ownmulti-position armso that
proper air to fuel ratio can be obtained throughout the modulating range. After preliminarysafety
checks and start-up procedures have been accomplished, then proceed to the modulating operation
adjustments. See Figure 14, page 33 for linkage operation.
NOTE:Ifthe burner has been supplied with the Varicam® characterized fuel metering system,refer to
Figure15,page 34ofthis manualandbulletin No. VA1588“Varicam®Adjustment Instructions”
included in the information supplied with the burner.
A.Inorderforyoutodeterminethatthebutterflygas valveisinthelowfire position,observe
the slot in the end ofthe butterflyvalve shaft. The slot position is parallel to the valve
butterflyand thus indicates butterflyposition.
B. Settings must be noted and marked on the linkage prior to proceeding with your final
adjustment.
C. Mark thelinkagesetting previouslyarrivedatforlowfire warmupprior toproceedingwith
modulation linkage adjustments at higher firing rates.
D. Using the manual potentiometer manuallyincrease the firing rate to the midwaypoint by
small increments, watching linkage to assure free movement at each position. When
midpointis reached takefluegasreadingsandadjustthefuel/air ratio. 9.5to10.5% CO2
with CO less than 0.04$ CO should be obtainable from50% to 100% full firing rate. The
metering device settingsand airdamperopening should be noted and marked on linkages
before proceeding to full firing rate.
E.Againbysmall increments, use the manual potentiometer tomanuallymove the firing rate
to the high fire position. The high fire rate is set approximatelyto the manifold gas
pressuregiven ontheburnerspecificationsheet.Readthe gasmetertodetermineexact
firingrate.Check withthelocalgasutilitytodeterminemetercorrectionfactor applicable.
Repeatthetestsandadjustfuel/airratiothesameasdonefor themidpointadjustment.If
desired high fire input rate cannot be achieved with the butterflyvalve wide open (do not
go beyond fullopen) increase the gaspressure at the burnermain gaspressure regulator,
asrequired. The metering device setting and airdamper openingsused to obtainyour high
fire reference points should be marked and noted.
F. Move the modulating lever armon the modulating motor through the three previously
determined reference points. Check todetermine that the same fuel/airratios(%CO2)are
obtained. Minorsetting modificationsmaybe requiredtoensurethat your referencepoints
are acquired. Reset fuel/air linkage at lowfire to obtain the highest possible CO2
recommendations) with less than 0.04% CO.
G.Adjustthe high gaspressure switchto trip at 20%above thesensed gaspressure present
at full burner firing rate.
H. Tighten all linkages and permanentlymarksettings.
21. The “Owner” Operating Instructions,” page 48 ofthis manual, should be posted in aclearlyvisible
location close to the burner.
22. The gas burner start-up procedure is nowcomplete.
-15-