POWERPATH PS-8-LP User manual

POWERPATH
PS-8-LP (105540)
PS-8-B-LP (105554)
PS-8E-LP (105542)
PS-8E-B-LP (105555)
PS-6 (105530)
PS-6-B (100257)
PS-6E (100262)
PS-6E-B (105085)
NAC EXTENDER
POWER SUPPLIES
Installation Instructions
273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707
Copyright 2015 Cooper Wheelock Inc., dba Cooper Notification. All rights reserved.
Part Number: P84905-002A
firealarmresources.com

P84905-002 A Sheet 2 of 37
MODEL MATRIX
MODEL AMPS VOLTAGE ENCLOSURE
PS-8-LP 8A 120VAC RED
PS-8-B-LP 8A 120VAC BLACK
PS-8E-LP 8A 240VAC RED
PS-8E-B-LP 8A 240VAC BLACK
PS-6 6A 120VAC RED
PS-6-B 6A 120VAC BLACK
PS-6E 6A 240VAC RED
PS-6E-B 6A 240VAC BLACK
firealarmresources.com

P84905-002 A Sheet 3 of 37
Thank you for using our products.
Use this product according to this instruction manual.
Please keep this instruction manual for future reference.
TABLE OF CONTENTS
1.0-INTRODUCTIONANDSPECIFICATIONS 4
1.1-INTRODUCTION 4
1.2 - SPECIFICATIONS 5
1.3-TERMINOLOGY 6
2.0 - INSTALLATION INSTRUCTIONS 7
2.1-UNPACKING 7
2.2-MOUNTING 7
2.3-WIRING 9
3.0–SETTINGTHEDIPSWITCHES 15
3.1–CONTROLPCBOARD 15
4.0 – APPLYING POWER TO THE POWER SUPPLY PANEL 17
5.0-TROUBLESHOOTING 18
6.0 – OPERATION EXAMPLES 23
7.0 - BATTERY CALCULATION SHEETS 32
7.1-PS-8-LPCALCULATIONSHEET 32
7.2-PS-6CALCULATIONSHEET 33
8.0 - LIST OF COMPATIBLE AUXILIARY DEVICES 34
9.0 - WARRANTY STATEMENT 35
10.0 APPENDIX A – LIST OF COMPATIBLE NAC DEVICES 36
LIST OF FIGURES
FIGURE1: EnclosureLayout 6
FIGURE 2: Mounting Dimensions 8
FIGURE 3: AC and DC Input Wiring Paths 10
FIGURE 4: Power Supply/Battery Charger PC Board 11
FIGURE 5: NAC Extender Wiring 12
FIGURE6: ControlPCBoard 13
FIGURE7: ControlPCBoardDIPSwitches 15
FIGURE 8: AC Power Terminals on the Power Supply PC Board 17
FIGURE9: BatteriesConnectedinSeries 17
FIGURE 10: Power Supply/Battery Charger PC Board Trouble LED
Locations 19
FIGURE 11: Control PC Board Trouble LED Locations 20
LIST OF TABLES
TABLE 1: Power Supply/Battery Charger PC Board Terminal Identification 11
TABLE 2: Control PC Board Terminal Identification 13
TABLE 3: Control PC Board DIP Switch Settings 15
TABLE 4: Power Supply/Battery Charger PC Board LED Trouble
Indicators 19
TABLE 5: Control PC Board LED Trouble Indicators 20
TABLE 6: Control PC Board Trouble Priority Identification 21
TABLE 7: Control PC Board Coded Trouble Identification 21
firealarmresources.com

P84905-002 A Sheet 4 of 37
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All WARNINGS are printed in bold capital
letters.
READ THIS INSTRUCTION MANUAL CAREFULLY. FAILURE TO COMPLY WITH ANY OF
THE FOLLOWING INSTRUCTIONS, CAUTIONS, AND WARNINGS COULD RESULT IN
IMPROPER APPLICATION AND/OR OPERATION OF THESE PRODUCTS IN AN
EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.
1.0 INTRODUCTION AND SPECIFICATIONS:
1.1 INTRODUCTION
The POWERPATH NAC Extender Power Supply is available in four models: the PS-8-LP (120Vac), PS-8-LPE
(240Vac), PS-6 (120Vac), and the PS-6E (240Vac). Except where specifically noted in this manual, PS-8-LP
will denote both 8-amp models, and PS-6 will denote both 6-amp models. The PS-8-LP differs from the PS-6 in
the NAC output current. All other features, indicators and capacities are the same.
The PS-8-LP is an 8 Amp, 24VDC, filtered and regulated, supervised remote power supply/charger used for
supervision and expanded power driving capability for Fire Alarm Notification Appliance Circuits (NACs). NAC
output options include up to four (4) Class “B”, two (2) Class “A”, or two (2) Class “B” and one (1) Class “A”
Notification Appliance Circuits. Additionally, an auxiliary power output can provide constant power of up to 0.24
Amps for 24 hours and up to 0.02 Amps for 60 hours, or managed power up to 2.5 Amps in a non-alarm
condition and when AC power is applied to the panel. The PS-8-LP also contains a battery charger capable of
charging up to 33 Amp/Hour (Ahr) of battery backup. The PS-8-LP’s NAC outputs can also be used as UL-1481
Compliant power supply outputs. When configured this way, the maximum continuous current rating is 3 Amps
per power supply output and 4 Amps maximum total current for all continuous duty power supply outputs.
Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support
system accessories. The PS-8-LP may be connected to any 12VDC or 24VDC Fire Alarm Control Panel
(FACP) by using Notification Appliance Circuits (NAC) or a “Dry Contact(s)”.
The PS-6 is a 6 Amp, 24VDC, filtered and regulated, supervised remote power supply/charger used for
supervision and expanded power driving capability for Fire Alarm Notification Appliance Circuits (NACs). NAC
Output options include up to four (4) Class “B”, two (2) Class “A”, or two (2) Class “B” and one (1) Class “A”
Notification Appliance Circuits. Additionally, an auxiliary power output can provide constant power of up to
0.075 Amps for 24 hours, or managed power up to 2.5 Amps in a non-alarm condition and when AC power is
applied to the panel. The PS-6 also contains a battery charger capable of charging up to 33 Amp/Hour (Ahr) of
battery backup. The PS-6’s NAC outputs can also be used as a UL-1481 Compliant power supply outputs.
When configured this way, the maximum continuous current rating is 3 Amps per power supply output and 4
Amps maximum total current for all continuous duty power supply outputs. Primary applications include NAC
expansion (supports ADA requirements) and auxiliary power to support system accessories. The PS-6 may be
connected to any 12VDC or 24VDC Fire Alarm Control Panel (FACP) by using Notification Appliance Circuits
(NAC) or a “Dry Contact(s)”.
Each NAC Extender Power Supply allows two FACP NAC circuits or two “Dry” contact closures to activate it
when connected to the inputs. These inputs can then be directed to control supervision and power delivery to
any combination of the four (4) outputs.
Each NAC output is rated at 3.0 Amps (Class "B") or 3.0 Amps (Class "A") and can be programmed to
generate a steady or Code 3 Temporal Horn sound, and a strobe output under alarm condition. Total
load for the PS-8-LP NAC circuits shall not exceed 8.0 Amps. Total load for the PS-6 NAC circuits shall
not exceed 6.0 Amps.
Each NAC Extender Power Supply, under non-alarm condition provides independent loop supervision for Class
“A” and Class “B” FACP NAC circuits. In the event of a loop trouble, the FACP will be notified via the panel
steered input (IN1 or IN2). In addition there are common trouble output terminals (used to indicate a loop
trouble) and common trouble input terminals (used generically by any initiating circuit).
Wheelock horns/strobes, strobes and horns with synchronizing capability can be utilized with both the PS-8-LP
and the PS-6. Audibles can be silenced with only two wires outputs. Additionally, the POWERPATH can
provide a temporal coded signal for appliances that can utilize it.
firealarmresources.com

P84905-002 A Sheet 5 of 37
1.2 SPECIFICATIONS
Approvals:
UL Listed 1481 Standard for Power Supplies for Fire-Protective Signaling Systems.
UL Listed 864 9th Edition Control Units and Accessories for Fire Alarm Systems
California State Fire Marshall (CSFM)
NFPA 72 compliant
Environmental: Approved for indoor dry locations.
Inputs:
240VAC, 50/60Hz, 3.22 Amps (PS-8-LPE), 2.42 Amps (PS-6E) Operating Power in Alarm.
120VAC, 50/60Hz, 5.32 Amps (PS-8-LP), 4.25 Amps (PS-6) Operating Power in Alarm.
24VDC Sealed Lead Acid Battery Backup Connection.
Two (2), 12VDC or 24VDC NAC Initiating Circuits (8-33VDC at 5mA).
Two (2) “Dry” Contact initiating Circuits.
Accepts two Class “A” or two Class “B” circuit inputs.
Built in battery charger for sealed lead acid or gel type batteries. Maximum charging current: 0.75 Amps.
Outputs:
24VDC power limited synchronized outputs. Up to 50 NAC devices per output, maximum line impedance
1.46 Ohms per NAC.
8 Amp in alarm supply current for the PS-8-LP.
6 Amp in alarm supply current for the PS-6.
Capable of four (4), Class "B" regulated outputs (Maximum of 3 Amps on an output.)
Capable of two (2) Class “A” regulated outputs (Maximum of 3 Amps on an output.)
Capable of one (1) Class “A” regulated outputs and two (2) Class “B” regulated outputs (Maximum of 3 Amps
on an output.)
Temporal (Code 3) or constant voltage output generation.
Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits.
Input and output can be synchronized with “IN FOLLOWER” mode.
Continuous duty NON-RESETTABLE output configuration 4 Amps of maximum continuous duty current.
(Maximum of 3 Amps on an output for specific applications.) Continuous power outputs are not battery
backed up.
Audible silence capability.
Filtered and electronically regulated output.
PS-8-LP - 0.02 Amp continuous auxiliary power for 60 hours, which is power limited and battery backed up.
PS-8-LP - 0.240 Amp continuous auxiliary power for 24 hours, which is power limited battery backed up.
PS-6 - 0.075 Amp continuous auxiliary power for 24 hours, which is power limited battery backed up.
2.5 Amps managed auxiliary power that turns off during alarm or battery backup, and automatically restores.
Multiple POWERPATHs can be synchronized through the SBUS terminals, see Chapter 6.0 on sheet 22 for
example drawings.
Supervision:
Compatible with 12VDC or 24VDC FACP.
Signaling appliance loops are supervised and steered to either IN1 or IN2.
10K Ohm, 1/2 Watt End of Line Resistor (EOLR) for supervision of all outputs.
Common input and output trouble circuits.
Automatic switchover to standby battery when AC fails.
Short circuit protection with auto reset.
Input and output status LED indicators.
AC fail supervision (Form “C” contact, 1 Amp 24VDC).
Battery presence and low battery supervision (Form “C” contact, 1 Amp 24VDC).
Ground Fault Detection, with the ability to detect ground faults on individual circuits.
Minimum Impedance = 0 Ohms.
Parameter Description
Operating Temperature 0 to 49 °C (32 to 120 °F)
Storage Temperature -20 to 70 °C (-4 to 158 °F)
Humidity, Non-condensing 85 ± 5% at 30 ± 2 °C (86 ± 4 °F)
firealarmresources.com

P84905-002 A Sheet 6 of 37
1/2” and 3/4" Knockouts (13)
1.3 TERMINOLOGY
CLASS “A” = STYLE Z
CLASS “B” = STYLE Y
FACP = Fire Alarm Control Panel
EOLR = End of Line Resistor
NAC = Notification Appliance Circuit
SM = Wheelock Sync Module with single output
DSM = Wheelock Dual Sync Module with two outputs
C = Common
NC = Normally Closed
NO = Normally Open
Ahrs = Ampere/Hours
Enclosures
Figure 1 shows the location of the PC boards and knockouts on the PS-8-LP and PS-6 panels.
IN1 IN2CC1 CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1 RET2
COM NO
NC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
TB1 TB2
TB2
TB1 J2
SW1
D2
D9
D37
D3D4
D5D6
D7D8
D36 D35 D34
D21
D24
SW5
SW2
SW1
SW3
SW4
SW6
IN1 FOLLOWER
IN2 FOLLOWER
TROUBLELATCH
SBUS IN1/IN2
GF DETECT
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2CLASS B/A
NAC3-NAC4 CLASSB/A
AUX POWERCP/MP
SBUS MASTER/ REMOTE
NAC1 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC3 SYNC/TEMPORAL
NAC4 SYNC/TEMPORAL
NAC1 IN1/IN2
NAC2 IN1/IN2
NAC3 IN1/IN2
NAC4 IN1/IN2
Figure 1: Enclosure Layout
Power Supply/Battery
Charger PC Board
Control PC Board
Battery Compartment for
two – 12V 7Ahrs
Rechargeable Batteries
firealarmresources.com

P84905-002 A Sheet 7 of 37
2.0 INSTALLATION INSTRUCTIONS:
NOTE: The POWERPATH NAC Extender Power Supply shall be installed in accordance with the National Fire
Protection Association (NFPA), National Electrical Code (NEC) and all applicable state and local regulations.
2.1 UNPACKING
The POWERPATH was carefully checked before leaving the factory. Inspect shipping container and unit
carefully for indications of improper handling. If damage is detected, make an immediate claim to the carrier.
Remove the POWERPATH from the shipping container and check that the door lock keys, door lock, and
battery connection wires are inside. Make sure the printed circuit boards are within their proper packaging of
the enclosure.
2.2 MOUNTING
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT
TO RAIN OR MOISTURE.
This product is not intended for use in hazardous locations as defined by the National
Electrical Code (NEC) and by the National Fire Protection Association (NFPA).
A Mount the POWERPATH in the desired location using the mounting dimensions in Figure 2.
B. Mount the panel in an indoor and dry area that does not exceed a temperature range of 32F to 120F (0
C to 49C) and a humidity equal to 10% to 85% at 86F (30C) non-condensing.
NOTE: When mounting on interior walls, use proper screw anchors in plaster. When mounting to concrete,
especially when moisture is expected, first attach a piece of ¾ inch plywood to the concrete surface.
Attach the POWERPATH to the plywood.
C. Remove desired knockouts and mount conduit and conduit fittings to the enclosure.
firealarmresources.com

P84905-002 A Sheet 8 of 37
NOTE: All dimensions shown are measured in inches.
10.3"
12.8"
16.7"
3.0"
DIMENSIONS (H x W x D) – 16.7” x 12.8” x 3”
Figure 2: Mounting Dimensions
firealarmresources.com

P84905-002 A Sheet 9 of 37
2.3 WIRING
Review the Operation Section (4.0) in order to select the proper hook-up and use of the POWERPATH.
Set switches and wire the POWERPATH as follows: Terminal locations for the Power Supply/Battery Charger
PC board are shown in Figure 4. Terminal locations for the Control PC board are shown in Figure 6.
NOTE:The maximum current on a Class “A” or “B” output is 3 Amps with the rest of the NAC Extender
output current divided among the remaining circuits.
DO NOT CONNECT WIRING TO THE AC INPUT SOURCE OR TO THE BATTERIES UNTIL ALL WIRING
AND ALL SWITCH SETTINGS HAVE BEEN MADE
POWER LIMITED AND NON-POWER LIMITED WIRING SHALL BE SEPERATED AND SHALL NOT BE
WITHIN 1/4" OF EACH OTHER. NON POWER LIMITED WIRE SHALL BE SEPERATED FROM PC BOARDS
BY 1/4".
Power Supply/Battery Charger PC Board
NOTE: Sealed Lead Acid Batteries shall be used for backup batteries.
firealarmresources.com

P84905-002 A Sheet 10 of 37
POWER
D9
12VDC
BATTERY
12VDC
BATTERY
TB3
TB1 J2
L
N
NO
COM
NC BATTERY
IN1 IN2
CC1 CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1 RET2
COM NO
NC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1 TB2
SW2
SW1
SW3
SW4
SW6
IN2 FOLLOWER
IN1 FOLLOWER
TROUBLE LATCH OFF/ON
SBUS IN1/IN2
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL
NAC4 IN1/I N2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
TB6 TB3 TB4
D1
IN1 TROUBLE
CONNECT THE BATTERIES IN SERIES
BY CONNECTING THE OTHER + AND -
TERMINALS TOGETHER
BLACK
GREEN
WHITE
120VAC 50-60Hz NON-POWER LIMITED (PS-6, PS-8)
240VAC 50-60Hz NON-POWER LIMITED (PS-6E, PS-8E)
24VDC BATTERY BACKUP
NON-POWER LIMITED
TB2
GND
GF DETECT ONN/OFF
D31
D36
INPUT1
INPUT2
D38
SILENCE
D2
GENERAL TROUBLE
D30
IN2 TROUBLE
D37
ACTIVE
SW5
D40
D3: GROUND FAULT TROUBLE
D4-D8: SEE
TAB LE 9
< D8-D4 >
SYNC BUS
GROUND FAULT
LOCATOR
D21
AC LOSS TRB
D24
BATTERY
POWER
D36
D35
D34
D38
AC POWER
BATTERY TROUBLE
BATTERY CHARGER TROUBLE
MICROPROCESSOR TROUBLE
F1
10 AMP
250 VAC
F2
10 AMP
250 VAC
Figure 3: AC and DC Input Wiring Paths
A. Install the battery wires to the battery terminals (TB3) and dress them down to the back of the enclosure,
observing ¼” separation from power limited wiring.
B. Wire the AC LOSS terminals as applicable.
C. Install the battery insulation cover plate over the battery terminals, folding side facing the door. Ensure that
the battery wires maintain ¼” separation from power limited wiring.
firealarmresources.com

P84905-002 A Sheet 11 of 37
TB3
TB1 J2
NO
COM
NC
BATTERY
TB2
GND
L
N
D36
D35
D34
D21 D38
POWER
BATTERY TROUBLE
BATTERY CHARGER TROUBLE
MICROPROCESSOR TROUBLE
AC LOSS TRB
D24
BATTERY
POWER
JP1
AC LOSS DELAY
JP1 IN = 0 MIN
JP1 OUT = 170 MIN
Figure 4: Power Supply/Battery Charger PC Board
Table 1: Power Supply/Battery Charger PC Board Terminal Identification
Terminal Block
Identification
Numbers (Figure 4)
Terminal
Identification Function/Description
TB1 - 1,2,3 AC Trouble Form “C” contacts rated 24VDC at 1 Amp used for external trouble alerts.
TB2 - 1,2,3 AC Input Input power terminals for 120VAC, 50 to 60 Hz. Non-Power Limited (PS-6, PS-8-LP)
TB2 - 1,2,3 AC Input Input power terminals for 240VAC, 50 to 60 Hz. Non-Power Limited (PS-6E, PS-8E-
LP)
TB3 - 1,2 Battery
Backup battery terminals: 24VDC, 7 to 33 Ahrs, Sealed Lead Acid Non-Power Limited.
All Models – Two 12VDC 7 Ahrs batteries fit inside the enclosure. Batteries larger
than 7 Ahrs require an external enclosure such as the Wheelock Product BATC.
JP1 - 1,2 JP1 Jumper Sets Delay for Remote AC LOSS Annunciation.
JP1 IN = 0 Min Delay JP1 OUT = 170 Min Delay
AC Input
120VAC
50 – 60 Hz
(PS-6, PS-8-LP)
AC LOSS Form “C”
Relay Terminals
AC Input
240VAC
50 – 60 Hz
(PS-6E, PS-8-LPE)
Battery Terminals
24VDC, 7 to 33 Ahrs
firealarmresources.com

P84905-002 A Sheet 12 of 37
AC LOSS
TROUBLE
TERMINALS
AC INPUT
TERMINALS
BLACK
WHITE
GREEN
IN1 IN2
CC1 CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1 RET2
COM NC
NO
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1 TB2
D37
SW5
TB6
TB3
TB2
TB1
J2
D35
D34
D21
L
N
NO
COM
NC
AC LOSS TRB
D38
AC POWER
BATTERY
SW6
D2
D9
D1
D30
D38 D31
D36
D40
D3: GROUND FAULT TROUBLE
GROUND FAULT
LOCATOR
ACTIVE
GENERAL TROUBLE
SILENCE INPUT 2
INPUT 1
SYNC BUS
IN1 TROUBLE
IN2 TROUBLE
POWER
D4-D8: SEE
SW2
SW1
SW4
SW3
TABLE 1
D8-D4
<>
D36
GND
X
F1
10AMP
250VAC
F2
10AMP
250VAC
24VDC 1 AMP
MAXIMUM RESISTIVE LOAD
(NON SUPERVISED)
PS-EXP
EXPANSIONBOARD
SW2
SW1
SW3
SW4
D1
NAC 5
OUT
NAC 6
OUT
NAC 7
OUT
NAC 8
OUT
D12
ALARM LED
TROUBLE LEDS GENERAL TROUBLE LED
POWER LED
D6
D5
D4
D3
D2
J1
D7
Figure 5: NAC Extender Wiring
Control PC Board
firealarmresources.com

P84905-002 A Sheet 13 of 37
Refer to Figure 6 for the locations of the terminals described in Table 2.
IN1 IN2
CC1 CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1 RET2
COM NO
NC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1 TB2
SW2
SW1
SW3
SW4
IN2 FOLLOWER OFF/ ON
TROUBLE LATCH OFF/ON
SBUS IN1/IN2
GF DETECT ON/OFF
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC4 IN1/IN2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
IN1 FOLLOWER OFF/ ON
SW6
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL
D30
IN2 TROUBLE
D31
D36
INPUT1
INPUT2
D38
SILENCE
D2
GENERAL TROUBLE
D37
ACTIVE
SW5
D40
D3: GROUND FAULT TROUBLE
D4-D8: SEE
TABLE 9
< D8-D4 >
SYNC BUS
GROUND FAULT
LOCATOR
D9
POWER
D1
IN1 TROUBLE
X
* PS-EXP
EXPANSIONBOARD
NAC4
NAC3
NAC2
NAC1
NAC OUTPUTS
EOLR 10K OHM
CLASS B
(POWER LIMITED,
SUPERVISED)
SW2
SW1
SW3
SW4
D1
TROUBLE LATCH OFF/ON
SYNC BUS SYNC/TEMPORAL
IN2 FOLLOWER OFF/ON
IN1 FOLLOWER OFF/ON
NAC8 SYNC / TEMPORAL
NAC7 SYNC / TEMPORAL
NAC6 SYNC / TEMPORAL
NAC5 SY NC / TEMPORAL
NAC8 IN1 / IN2
NAC7 IN1 / IN2
NAC5-NAC6 CLASS A/B
NAC7-NAC8 CLASS A/B
NAC 5
OUT
NAC 6
OUT
NAC 7
OUT
NAC 8
OUT
SYNC PROTOCOL
SYNC PROTOCOL
NAC6 IN1 / IN2
NAC5 IN1 / IN2
D12
ALARM LED
CODED
TROUBLE LEDS GENERAL TROUBLE LED
POWER LED
D6
D5
D4
D3
D2
D7
J1
Figure 6: Control PC Board
* Shown with optional PS-EXP Add on PC Board
Table 2: Control PC Board Terminal Identification
Terminal Block
Identification
Numbers
Terminal
Identification Function/Description
TB1-1, 2 IN1+, IN1-
These terminals connect to the input voltage source (i.e. 12VDC or 24VDC
FACP). The FACP will supply a voltage from 8-33VDC at 5mA. During the alarm
condition these inputs will cause the designated outputs to drive the notification
appliances (designated outputs are set by output DIP switch banks). During
Stand-by on a FACP, a trouble condition on the designated loop will cause these
inputs to open, providing a trouble condition on the FACP. Alarm condition always
overrides trouble to drive output indicating appliances.
TB1-3, 4, RET1+, RET1- EOLR is connected on these terminals corresponding to IN1+ and IN1-, or the
loop may be continued to other power supplies or appliances before terminating.
TB1-5, 6 CC1+, CC1-
Dry contacts are used to actuate the designated outputs. Contacts are normally
closed and actuate the power supply on contact OPEN. Designated outputs
correspond to IN1+, IN1-. NOTE: FACP NAC circuit cannot energize the power
supply by these contacts. When these terminals are not in use, a jumper must be
connected across them.
TB1-7, 8 IN2+, IN2- Same as IN1+, IN1- for corresponding terminals.
TB1-9, 10 RET2+, RET2- Same as RET1+, RET1- for corresponding terminals.
TB1-11, 12 CC2+, CC2- Operates the same as C “Dry2” NC for corresponding terminals. When these
terminals are not in use, a jumper must be connected across them.
TB1-13, 14 S BUS IN+, IN-
Synchronizing Bus IN: Links from previous POWERPATH “S BUS RET” to
synchronize both together. Controlled as Master or Remote by switch SW3
Position 4. Current Draw is 0.006 Amps per POWERPATH.
TB1-15, 16 S BUS RET+, RET-
Synchronizing Bus RET: Sync control output from the master POWERPATH to
additional POWERPATH panel “S BUS IN” terminals. Always place 10K Ohm
EOLR on the last panel. Controlled as Master or Remote by switch SW3 Position
4. Up to 40 power supplies can be connected to the PS-8-LP or 12 to the PS-6.
TB2-1,2 SIL+, SIL- Audible Silence: NAC input to the master POWERPATH from FACP. The Audible
signal is transmitted to all POWERPATH panels within the loop. Power Limited.
TB2-3,4,5 “NO” “C” “NC”
(COMMON TROUBLE
OUTPUT)
Typically used to trigger remote alerts or other reporting appliances. Form “C”
contacts rated 24VDC at 1 Amp. NOTE: These terminals must be monitored by
the FACP for Class “A” mode.
TB2-6, 7 + AUX OUT -
This output has two modes of operation. The CP Mode is capable of 0.02 Amps
for 60 hours (PS-8-LP only) or 0.24 Amps (PS-8-LP)/0.075 Amps (PS-6) for 24
hours on battery back up for desired auxiliary equipment. The MP Mode provides
up to 2.5 Amps in non-alarm condition or when the input AC is present. Special
Applications, Power Limited.
TB2-8, 9
TB2-10, 11
TB2-12, 13
TB2-14, 15
+OUT1-
+OUT2-
+OUT3-
+OUT4-
NAC appliances are connected to these outputs. Each output can supply a
maximum load of 3.0 Amps, Class "B" or 3.0 Amps Class "A" and can be
individually programmed for Wheelock Strobe Sync Mode, Temporal Mode or
Input follower Mode. The outputs can be configured as four Class "B" circuits,
two Class "A" circuits, or two Class "B" and one Class "A" circuits. Outputs are
controlled by a designated input (INPUT 1 or 2) as selected by the DIP switch for
that output. Power Limited.
TB2-16 Not Used
firealarmresources.com

P84905-002 A Sheet 14 of 37
NOTE: The maximum number of NAC appliances is dependent upon the field wire gauge used and the
total current draw of the Appliances on the NAC circuit.
C. Connect notification appliances to desired outputs OUT1 – OUT4. See Figure 6.
The POWERPATH has in-out wiring terminals that accept two #18 to #12 American Wire Gauge
(AWG) wires at each screw terminal. Strip leads 3/8 inch and connect to screw terminals.
Separate all in-out wire runs on supervised circuits to insure integrity of circuit supervision. The polarity
shown in the wiring diagrams and on the circuit boards is for operation of the appliances. The polarity
is reversed by the POWERPATH during supervision.
Total load for the PS-8-LP NAC circuits shall not exceed 8.0 Amps. Total load for the PS-6 NAC circuits
shall not exceed 6.0 Amps.
Total load of any Class “B” output circuit shall not exceed 3.0 Amps.
Total load of any Class “A” output circuit shall not exceed 3.0 Amps.
D. Terminate unused Class “B” outputs and the last appliance on an output with a 10K Ohm EOLR. Do not
terminate Class “A” outputs with an EOLR, use jumper wires, see Chapter 6.0 on sheet 22 for example
drawings.
E. Connect the indicating circuit(s) from the FACP to the desired input(s), IN1 and IN2. Connect FACP
compatible EOLR’s to RET1 and RET2.
F. In order to use the audible silence feature, connect a 24V or NAC output to the PS-8-LP (PS-6) SIL input
terminal.
G. If all NAC appliances must activate at the same time, connect “OUT4” from the first PS-8-LP (PS-6) to the
“IN1” of the second PS-8-LP (PS-6). Next connect the “IN1 RET” of the second PS-8-LP (PS-6) to the next
PS-8-LP (PS-6) “IN1. Connect a 10K EOLR to the “IN1 RET” terminal on the last PS-8-LP (PS-6).
If NAC appliances must be activated sequentially (not all at the same time) connect the SYNC BUS/SYNC
BUS RET between PS-8-LP (PS-6).
H. Connect desired auxiliary equipment to the auxiliary output terminals +AUX-. See Sheet 33, Section 8.0,
for the List of Compatible AUX Devices.
Total load of the AUX output shall not exceed 0.02 Amps during 60 hour battery backup in the Constant
Power (CP) mode, if using standard 12 Ahr batteries.
Total load of the AUX output shall not exceed 0.24 Amps during 24 hour battery backup in the Constant
Power (CP) mode, if using standard 12 Ahr batteries.
Total load of the AUX output shall not exceed 0.075 Amps during 24 hour battery backup in the
Constant Power (CP) mode for the PS-6, if using standard 7 Ahr batteries.
Total load of the AUX output shall not exceed 2.5 Amps in the Managed Power (MP) mode.
I. Connect system trouble relay terminals as desired.
firealarmresources.com

P84905-002 A Sheet 15 of 37
3.0 SETTING THE DIP SWITCHES
3.1 CONTROL PC BOARD
Refer to Figure 6 for the location and setting of the DIP switches on the Control PC board.
1. Set NAC output DIP Switch(s) on SW1 to follow corresponding input (IN1, IN2).
2. See Figure 7 for DIP switch locations and Table 3 for DIP Switch Selection and DIP Switch Settings
SW5
SW2
SW1
SW3
SW4
IN2 FOLLOWER OFF/ON
TROUBLE LATCH OFF/ON
SBUS IN1/IN2
GF DETECT ON/OFF
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC4 IN1/IN2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
IN1 FOLLOWER OFF/ON
SW6
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL GROUND FAULT TEST
LOCATOR SWITCH
Figure 7: Control PC Board DIP Switches
Table 3: Control PC Board DIP Switch Settings
DIP
Switch Function
Description Dip Switch Setting:
“LEFT” Dip Switch Setting:
“RIGHT” Dip Switch Setting:
“LEFT” Dip Switch Setting:
“RIGHT”
SW6
Position 1
TROUBLE
LATCH
OFF / ON
Any trouble conditions will
clear automatically as the
trouble condition is
repaired.
Trouble indicators latch ON
until this switch is switched
to the disable (LEFT)
position or all power is
removed from the panel.
Same Functionality as
Master Mode.
Same Functionality as
Master Mode.
Position 2 SBUS
IN1 / IN2
If IN1 Follower = ON, SBUS
will repeat the signals on
IN1 / CC1 input.
If IN2 Follower = ON,
SBUS will repeat the
signals on IN2 / CC2 input.
If IN1 Follower = ON, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on the SBUS when
IN1 / CC1 “Activates.”
If IN1 Follower = ON, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on IN1 / CC1 input,
ignoring the NAC Output’s
SYNC / TEMPORAL
dipswitch settings.
If IN1 Follower = OFF,
SBUS will generate signals
according to its SW2 -
SYNC / TEMPORAL switch
setting.
If IN2 Follower = OFF,
SBUS will generate signals
according to its SW2 - SYNC
/ TEMPORAL switch setting.
If IN1 Follower = OFF, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on the SBUS when
IN1 / CC1 “Activates.”
If IN1 Follower = OFF, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on the SBUS when
IN1 / CC1 “Activates.”
Position 3
IN2
FOLLOWER
OFF / ON
NAC Output(s) or SBUS set
to trigger on IN2 / CC2 will
generate signals according
to its SYNC / TEMPORAL
switch setting.
NAC Output(s) or SBUS set
to trigger on IN2 / CC2 turn
on when IN2 / CC2 is
“Active” and will apply NAC
reverse supervision voltage
when IN2 / CC2 is “Not
Active.”
See SW6 Position 2’s
description for this setting. See SW6 Position 2’s
description for this setting.
Position 4 IN1 NAC Output(s) or SBUS set NAC Output(s) or SBUS set See SW6 Position 2’s See SW6 Position 2’s
firealarmresources.com

P84905-002 A Sheet 16 of 37
FOLLOWER
OFF / ON
to trigger on IN1 / CC1 will
generate signals according
to its SYNC / TEMPORAL
switch setting.
to trigger on IN1 / CC1 turn
on when IN1 / CC1 is
“Active” and will apply NAC
reverse supervision voltage
when IN1 / CC1 is “Not
Active.”
description for this setting. description for this setting.
SW2
Position 1 NAC4 SYNC /
TEMPORAL Sets Sync pattern on NAC4 Sets CODE 3 Temporal
Pattern on NAC4.
See SW6 Position 2’s
description for this setting. See SW6 Position 2’s
description for this setting.
Position 2 NAC3 SYNC /
TEMPORAL Sets Sync pattern on NAC3 Sets CODE 3 Temporal
Pattern on NAC3.
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.
Position 3 NAC2 SYNC /
TEMPORAL Sets Sync pattern on NAC2 Sets CODE 3 Temporal
Pattern on NAC2.
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.
Position 4 NAC1 SYNC /
TEMPORAL Sets Sync pattern on NAC1 Sets CODE 3 Temporal
Pattern on NAC1.
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.
SW1
Position 1 NAC4
IN1 / IN2
Input 1 (IN1or CC1) triggers
NAC4. Any trouble
condition on NAC4 will
cause an open condition on
IN1_RET & IN2_RET.
Input 2 (IN2 or CC2) triggers
NAC4. Any trouble condition
on NAC4 will cause an open
condition on IN1_RET &
IN2_RET.
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.
Position 2 NAC3
IN1 / IN2
Input 1 (IN1or CC1) triggers
NAC3. Any trouble
condition on NAC3 will
cause an open condition on
IN1_RET & IN2_RET.
Input 2 (IN2 or CC2) triggers
NAC3. Any trouble condition
on NAC3 will cause an open
condition on IN2_RET.
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.
Position 3 NAC2
IN1 / IN2
Input 1 (IN1or CC1) triggers
NAC2. Any trouble
condition on NAC1 will
cause an open condition on
IN1_RET.
Input 2 (IN2 or CC2) triggers
NAC2. Any trouble condition
on NAC2 will cause an open
condition on IN1_RET &
IN2_RET.
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.
Position 4 NAC1
IN1 / IN2
Input 1 (IN1or CC1) triggers
NAC1. Any trouble
condition on NAC1 will
cause an open condition on
IN1_RET & IN2_RET.
Input 2 (IN2 or CC2) triggers
NAC1. Any trouble condition
on NAC1 will cause an open
condition on IN1_RET &
IN2_RET.
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.
SW4
Position 1 SYNC
PROTOCOL
Wheelock Sync Only –
Leave in this position. For Future Use Same Functionality as
Master Mode.
Same Functionality as
Master Mode.
Position 2 SYNC
PROTOCOL
Wheelock Sync Only –
Leave in this position. For Future Use Same Functionality as
Master Mode.
Same Functionality as
Master Mode.
Position 3 SBUS SYNC /
TEMPORAL
SBUS Output Terminals will
self generate SYNC.
SBUS Output Terminals will
self generate TEMPORAL.
In REMOTE Mode Set this
switch to same setting as
MASTER PS-8-LP (PS-6).
In REMOTE Mode Set this
switch to same setting as
MASTER PS-8-LP (PS-6).
Position 4
SBUS
MASTER /
REMOTE
Sets the NAC Extender to
“MASTER MODE”
Sets the NAC Extender to
“REMOTE MODE”
Sets the NAC Extender to
“MASTER MODE”
Sets the NAC Extender to
“REMOTE MODE”
SW3
Position 1 GF DETECT
ON / OFF Ground Fault Detect – ON
Ground Fault Detect – OFF
Clear Ground Fault test
results. NOTE: LEAVING
THE SWITCH IN THIS
POSITION IS NOT
COMPATIBLE WITH UL-864
Same Functionality as
Master Mode.
Same Functionality as
Master Mode. NOTE:
LEAVING THE SWITCH IN
THIS POSITION IS NOT
COMPATIBLE WITH UL-
864
Position 2 AUX POWER
CP / MP
Constant Power (CP) –
Provides Auxiliary power in
alarm and on battery
backup.
Managed Power (MP) –
Power is off in alarm and
when there is a loss of AC.
Same Functionality as
Master Mode.
Same Functionality as
Master Mode.
Position 3 NAC3-NAC4
CLASS A / B
Set NAC3-NAC4 for CLASS
A Mode.
Set NAC3-NAC4 CLASS B
for CLASS B Mode.
Same Functionality as
Master Mode.
Same Functionality as
Master Mode.
Position 4 NAC1-NAC2
CLASS A / B
Set NAC1-NAC2 for CLASS
A Mode.
Set NAC1-NAC2 CLASS B
for CLASS B Mode.
Same Functionality as
Master Mode.
Same Functionality as
Master Mode.
EXAMPLE – Basic Settings on the Control PC Board
For a 4 NAC, Class B circuit output controlled by
Input 1 (IN1), Wheelock Sync, Auxiliary power in the
Constant Power mode(CP), and Ground Fault
detection, set the switches as follows:
SW2 Positions 1 - 4 Left
SW1 Positions 1 - 4 Left
SW3 Positions 1 - 2
Positions 3 - 4
Left
Right
SW4 Positions 1 - 4 Left
SW6 Positions 1 - 4 Left
firealarmresources.com

P84905-002 A Sheet 17 of 37
4.0 Applying Power to the Power Supply Panel
Now that all the Wiring is complete and the switch settings have been made, it’s time to apply power to the Power Supply
panel.
ALWAYS APPLY AC POWER BEFORE APPLYING BATTERY POWER. ALWAYS
REMOVE BATTERY POWER BEFORE REMOVING AC POWER. FAILURE TO DO SO
CAN CAUSE DAMAGE TO THE POWER SUPPLY COMPONENTS.
1. Connect AC source. The AC source shall be connected to a dedicated, non-switch power source. The AC must
first be wired into the buildings main electrical power. The conduit entry can be either from the top or left side
using the knock-outs. See Figure 8. Connect Earth Ground First.
TB2
L
N
GND
Figure 8:
AC Power Terminals on the Power Supply PC Board
2. Connect backup batteries. Batteries shall be Sealed Lead Acid type. Observe correct polarity and voltage. Use
two of the same size batteries connected in series as shown in Figure 9. Use up to 33 Ahr batteries depending
on circuit loading, BATTERY CALCULATION SHEET is provided on pages 20 and 21.
NOTE: The POWERPATH enclosure can accommodate two 12VDC batteries up to 7 Ahr in size. Batteries larger than
7 Ahr must be stored in a separate battery enclosure such as the Wheelock BATC Battery Enclosure.
Figure 9: Batteries Connected in Series
BATTERY MAINTENANCE
TWO DIFFERENT SOURCES OF POWER MAY BE CONNECTED TO THIS PANEL.
DISCONNECT BOTH SOURCES OF POWER BEFORE SERVICING. FAILURE TO
DISCONNECT BOTH SOURCES OF POWER BEFORE SERVICING COULD RESULT
IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
firealarmresources.com

P84905-002 A Sheet 18 of 37
Battery Replacement: Replace with new batteries every four (4) years or as needed if battery will no longer accept full
charge. Two 12V batteries are required for 24VDC.
The Power supply is now operational. Table 4 is a list of the LED indicators on the Power Supply/Battery Charger PC
board. Table 4 is a list of the LED indicators on the Control PC board. Amber LED indicators always indicate a trouble
condition. If amber LED indicator(s) light turn to the troubleshooting section for resolution.
5.0 TROUBLESHOOTING:
THE POWERPATH CONTAINS VOLTAGES THAT CAN CAUSE DEATH OR SERIOUS
INJURY. ALWAYS OBSERVE PROPER ELECTRICAL SAFETY PRECAUTIONS AND
WARNINGS.
Always follow good troubleshooting procedures:
When trouble occurs, observe all visual indications and note them. Refer to the interior door label.
If the problem is obvious or it can be located on the Troubleshooting Table, note it. Refer to the interior door label.
Always de-energize the POWERPATH completely (Remove both AC and DC power) before repairs.
While the POWERPATH is de-energized, perform a visual and hands on check of all terminals and wires to ensure
proper termination.
If intermittent troubles occur, use the trouble latch (SW2 Position 4) to find it.
Troubleshooting Using the LED Indicators
firealarmresources.com

P84905-002 A Sheet 19 of 37
Power Supply/Battery Charger PC Board.
TB3
J2
BATTERY
TB1
TB2
N
L
GND
NC
COM
NO
D36
D35
D34
BATTERY TROUBLE
BATTERY CHARGER TROUBLE
MICROPROCESSOR TROUBLE
D21
D38
AC POWER
AC LOSS TRB
D24
BATTERY
POWER
JP1
Figure 10: Power Supply/Battery Charger PC Board Trouble LED Locations
Table 4: Power Supply/Battery Charger PC Board LED Trouble Indicators
LED
Designator Identification LED
Color Description Action
D38 AC Power Green
Indicates when AC power is applied to the
PC board. No Action Required
D24 Battery Power Green
Indicates when battery power is applied to
the PC board. No Action Required
D34 Battery Trouble Amber
Indicates that a trouble condition exists on
the battery circuit.
Check the battery wiring and terminal
connections. Replace the batteries.
D35 Battery Charger
Trouble Amber Indicates that the battery charger section is
not working.
Remove the batteries from the
terminals. Using a DC voltmeter
check the voltage across the
terminals. The voltage should be
26.5VDC or higher. If the voltage is
not present, the battery charger
section has failed. Replace the PC
Board. If the voltage is present,
replace the batteries.
D36 Processor
Trouble Amber Indicates that a trouble condition exists on
the processor circuit.
Disconnect DC and AC voltages
from the power supply PC board.
Wait 10 seconds and reconnect. If
the problem does not clear, replace
the PC board.
D21 AC Loss Amber
Indicates a brown out or total loss of AC
power.
Check AC Mains is properly
connected. Check branch circuit
breaker powering the PS6/8. Check
the AC Mains Fuse, F1.
NOTE: Power Supply PCB trouble conditions will change the state of the Logic PCB General Trouble Relay after 33
seconds.
firealarmresources.com

P84905-002 A Sheet 20 of 37
Control PC Board
IN1 IN2
CC1 CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1 RET2
COM NO
NC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1 TB2
TB6 TB3 TB4
SW2
SW1
SW3
SW4
IN2 FOLLOWER OFF/ON
TROUBLE LATCH OFF/ON
SBUS IN1/IN2
GF DETECT OFF/ON
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC4 IN1/IN2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
IN1 FOLLOWER OFF/ON
SW6
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL
D9
POWER
D37
ACTIVE
SW5
D40
D3: GROUND FAULT TROUBLE
D4-D8: SEE
TABLE 9
< D8-D4 >
SYNC BUS
GROUND FAULT
LOCATOR
SWITCH
D1
IN1 TROUBLE
D31
D36
INPUT1
INPUT2
D38
SILENCE
D2
GENERAL TROUBLE
D30
IN2 TROUBLE
Figure 11: Control PC Board Trouble LED Locations
Table 5: Control PC Board LED Trouble Indicators
LED
Designator Identification LED
Color Description Action
D9 Power Green
Indicates when power is applied to the Control
board. No Action Required
D37 Active Red
Indicates when the power supply is activated
and supplying power to the NAC output
circuits.
No Action Required
D2 System Trouble Amber
Indicates that a general trouble condition exists
on the Control board.
Check the Coded Trouble LED
Indicators and the Ground Fault LED.
Repair any problems indicated. If no
indication is observed, replace the
Control PC Board. See Table 7
D8, D7, D6,
D5, D4
Coded Trouble
LED Indicators Amber
These five LEDs light in a coded pattern
indicating the location and type of trouble
condition. If multiple troubles are present the
LEDs will indicate the highest priority trouble.
When repaired the LEDs will indicate the next
priority trouble.
See Table 7
D3 General Ground
Fault Amber
Indicates that a ground fault condition exists.
Pressing switch SW5 will cause the code
pattern on the coded Trouble LEDs to locate
the location.
See Table 7
D1, D30 IN1 RET, IN2
RET Trouble Amber
Indicates that a general trouble condition
exists, and the IN1 RET and IN2 RET relays
are open.
See Table 7
D40 SYNC BUS
Power Active Green This LED lights when 24V is present on the
SYNC BUS. See Table 7
D31 IN1/CC1 Active Red
This LED lights when IN1 or CC1 has been
activated.
See Table 7
D36 IN2/CC2 Active Red
This LED lights when IN2 or CC2 has been
activated.
See Table 7
D38 Silence Active Red
This LED turns on when the “SILENCE” feature
has been activated. See Table 7
Coded Trouble LEDs
D8, D7, D6, D5, D4
firealarmresources.com
This manual suits for next models
15
Table of contents
Other POWERPATH Power Supply manuals
Popular Power Supply manuals by other brands

Vertiv
Vertiv NetSure-48 VDC Power System 502NGFB Installation and user manual

Agilent Technologies
Agilent Technologies 66311A user guide

Matsusada Precision
Matsusada Precision VOL Series instruction manual

APS
APS 42L Series Operation manual

PEHA
PEHA 942 SPV Installation & operating instructions

Aiphone
Aiphone PS-18YC/A specification

PERFECT FRY COMPANY
PERFECT FRY COMPANY PFC570-HB Installation & operation manual

Juniper
Juniper SRX 3400 installation instructions

Gallagher
Gallagher 083114 quick start guide

Agilent Technologies
Agilent Technologies 6023A operating manual

Kontron
Kontron 986LCD-M/mITX Information

Altronix
Altronix AL201UL quick start guide