6. To prevent damage or a safety hazard, keep the UPS away from
open flame and any other devices that may cause sparks.
7. Do not open or damage individual battery cases as spillage of
caustic electrolyte may occur resulting in danger to life, safety, and
the environment.
8. The charging characteristics of UPS batteries vary by both brand
and type. For this reason, replacement batteries should be of the
same brand and type as those specified by the manufacturer.
Using batteries other than the brand and type specified by the
manufacturer may affect the performance of the UPS. Before
installing batteries of different brand or type, please consult with the
manufacturer.
9. The UPS has an internal EMI filter for purposes of enhancing
electromagnetic compatibility with the input mains supply. This
filter produces leakage current to earth on the input mains. When
selecting a circuit breaker for the branch circuit supplying power
to the UPS, ensure that the breaker selected is not an ELCB type
circuit breaker that detects earth leakage current.
10. Please contact the manufacturer or an authorized distributor for any
assistance with troubleshooting.
11. The UPS should only be serviced or maintained by a factory
authorized service technician.
12. This UPS meets FCC Class A electromagnetic compatibility
requirements.
13. Depleted batteries must be disposed of in a proper manner.
Contact your local recycling or hazardous waste center or the UPS
manufacturer for instructions concerning proper disposal.