OPERATING MANUAL
1. SAFETY SUMMARY
The symbols below are used on the equipment and throu hout this document to draw the user’s attention to
important operational and safety information.
CAUTION or WARNIN :
Read complete instructions prior to installation
and operation of the unit.
CAUTION or WARNIN :
Electrical Shock Hazard
All safety related instructions that appear in the manual must be observed to ensure personal safety and to
prevent dama e to either the instrument or the system. If the instrument is used in a manner not specified by
the manufacturer, the protection provided by the equipment may be impaired.
2. INSTALLATION
The controller should be installed in a panel cut out as specified in item 2. First remove the mountin clamp
and insert the controller into the panel cut out. Place the unit into the panel cut-out and slide the mountin
clamps from the rear to a firm rip at the panel.
The internal circuitry can be fully removed from the housin without disconnectin any wirin . Grab firmly the
front panel and pull out the circuitry from the housin .
2.1 ELECTRICAL CONNECTIONS
All electrical connections are made to the screw terminals at the rear of the controller. They accept wire sizes
from 0.5 to 1.5 mm2 (16 to 22 AWG). The terminals should be ti htened to a torque of 0.4 Nm (3.5 lb in).
The installation must include a power isolatin switch or circuit breaker that disconnects all current carryin
conductors. The device should be mounted close to the controller, within easy reach of the operator and
marked as the disconnectin device for the instrument.
Fi ure 1 shows the electrical terminals of the controller.
Fi ure 1 - Back panel terminals
3. SPECIFICATIONS
•Dimensions: 48 x 48 x 110 mm (1/16 DIN). Panel cut-out: 45,5 x 45,5 mm. Wei ht: 160 (max);
•Power: 100 to 240 Vac/dc (±10 %), 50/60 Hz or 24 Vdc/ac (±10 %); Max. Consumption: 9 VA;
•Pt100: α= 385. 3-wire connection. Excitation current: 0.170 mA;
•Accuracy: 0.2 % of full scale for Pt100 and 0.25 % of full scale ±1 °C for T/C
•Thermocouple input impedance: 10 MΩ
•A/D converter resolution: 15000 steps
•Samplin rate: 10 measurements per second
•Environmental conditions: 5 to 50 °C; Relative humidity (maximum): 80 % up to 30 ºC. For temperatures
above 30 ºC, decrease 3 % per ºC. Installation cate ory II. Pollution de ree 2. Altitude < 2000 m.
•Front Panel: Polycarbonate UL94 V-2; Back Panel: ABS + PC UL94 V-0
•EMC: EN 61326-1:1997 and EN 61326-1/A1:1998
•SAFETY: EN61010-1:1993 and EN61010-1/A2:1995
3.1 TEMPERATURE SENSOR INPUT
Thermocouples are connected to terminals 10 and 11 with positive in terminal 11. Pt100 sensors are
connected to terminals 10, 11 and 12, as indicated in fi ure 1. For full compensation of cable resistance only
cables with equal wire electrical resistance should be used. Table 1 shows the sensor types accepted and
their respective codes.
TIPO CÓDI O FAIXA
J 0
00
0
-50 to 760 °C (-58 to 1400 °F)
K 1
11
1
-90 to 1370 °C (-130 to 2498 °F)
S 2
22
2
0 to 1760 °C (32 to 3200 °F)
Pt100 (Resolution 0,1°C) 3
33
3
-199.9 to 530.0 °C (-199.9 to 986.0 °F)
Pt100 (Resolution 1°C) 4
44
4
-200 to 530 °C (-328 to 986 °F)
T 5
55
5
-100 to 400 °C (-148 to 752 °F)
E 6
66
6
-30 to 720 °C (-22 to 1328 °F)
N 7
77
7
-90 to 1300 °C (-130 to 2372 °F)
R 8
88
8
0 to 1760 °C (32 to 3200 °F)
Table 1 - Sensor types, codes and ran es
3.2 POWER
Mains power is connected to terminals 1 and 2. Check the upper side of the housin for proper power
indication.
3.3 CONTROL AND ALARM OUTPUTS
Up to 4 outputs can be confi ured for control or alarm. The available outputs are identified on the rear panel
as OUTA, OUTB, OUTC or OUTD. Electrical characteristics of each output are:
OUTA: SPST Relay, 1,5 A / 250 Vac (3 A / 30 Vdc); Resistive load; 100 k cycles;
OUTB: Volta e Pulse, 5 Vdc / 20 mA;
OUTC: SPST Relay, 1,5 A / 250 Vac (3 A / 30 Vdc); Resistive load; 100 k cycles;
OUTD: SPDT Relay, 3 A / 250 Vac (3 A / 30 Vdc); Resistive load; 6 k cycles;
or 4-20 mA output. With 80 count resolution, precision: 0,25 mA, maximum load: 500 Ohms.
The output function is defined on controller confi uration, parameters IO A
IO AIO A
IO A, IO B
IO BIO B
IO B, IO (
IO (IO (
IO ( and IO d.
IO d.IO d.
IO d.
Control Output is used to control the process variable usin PID al orithm. More than one output can be
selected as control output. When OUTD is confi ured as Analog Control Output, all other outputs selected
as Control Output will not operate.
Control Outputs are turned off when a sensor error is detected (display “Erro
ErroErro
Erro”).
Alarm Outputs are used to si nal abnormal PV values, sensor error or end of pro ram. The alarm function
must be selected for each alarm output. (Refer to chapter 9).
4. CONFI URATION AND OPERATION
Prior to first operation the controller should be fully confi ured. The user must set basic parameters as
temperature type (“TYPE
TYPETYPE
TYPE”), the desired control set point (“ SP
SPSP
SP “), the alarms set points (“SPA1
SPA1SPA1
SPA1” and
“SPA2
SPA2SPA2
SPA2”), etc.
4.1 PARAMETERS FLOW CHART
The pro rammin parameters are or anized in 4 different sets or levels
Operation level / Alarms and tuning level / Configuration level / Calibration level
At power up the controller displays a prompt at the Operation Level and remains in this level while under
normal operation.
The other levels are only accessed when a chan e of parameters is necessary (except for Set Point
chan e). To reach these other parameters the user must keep the PRO Key (
Fi ure 2 – Protection Disabled Fi ure 3 – Protection Enabled
4.3 OPERATION LEVEL
TEMPERATURE
INDICATION
END
SP
TEMPERATURE measured by the sensor. At power up, the upper display shows the
process temperature value. It also shows the messa es described in chapter 5 of this
manual. The lower displays shows the set point value which is the temperature value
desired for the process.
rAte
TEMPERATURE RATE OF RISE: The user defines the rate of temperature rise from the
startin temperature to the value set in “ SP
SPSP
SP ”. Rate is defined in °C / minute.
T Sp TIME FOR SOAK: Time in minutes which the temperature will remain at the selected “
SP
SPSP
SP “. Refer to item 4.
Rvn
run
RUN: At this prompt the user sets the control output and alarms to active or to inactive.
0
00
0 - inactive outputs; 1
11
1 - active outputs;
4.4 TUNING AND ALARMS LEVEL
Atvn AUTO-TUNE: Activates the auto-tunin of PID parameters.
0
00
0 - Auto-tune is off; 1
11
1 - Auto-tune is on;
Pb
Proportional band
PROPORTIONAL BAND: percenta e of maximum input span.
When set to zero (0), control action is ON/OFF.
Ir
inte ral rate
INTE RAL RATE: Inte ral time constant in repetitions per minute (Reset). This
constant is not used when controller is set to ON/OFF action (Pb=0).
t
derivative time
DERIVATIVE TIME: Derivative time constant in seconds. This constant is not used
when controller is set to ON/OFF action (Pb=0).
(t
Cycle time
CYCLE TIME: Pulse Width Modulation (PWM) period in seconds. This term is not
used when controller is set to ON/OFF action (Pb=0).
KySt
HYSteresis
CONTROL HYSTERESIS: Is the hysteresis for ON/OFF control (set in temperature
units). This parameter is only used when the controller is in ON/OFF mode (Pb=0).
A1SP
A2SP
SP Alarm
SETPOINT for Alarm 1/2: Tripin point for alarm 1/2.