READER CONNECTION
The Protégé Reader Expander allows the connection of 4
Wiegand reading devices and the ability to control 2
doors (Entry or Exit Only) or 1 door (Entry and Exit). The
following diagrams show the connection of standard
Wiegand Reader (Entry Unit) and a Multiplexed reader
(Exit Reader).
When operating the reader expander in multiple reader
mode the Protégé Reader Expander allows the
connection of 4 wiegand reading devices controlling two
doors each with Entry/Exit readers.
DOOR CONTACT CONNECTION
The Protégé Reader Expander allows the connection of
up to 4 contacts for monitoring and controlling access
control doors. Each zone on
the reader expander can be
used for the door function
that is automatically
assigned and as a normal
zone input on the system.
The following example
shows the connection of a
normally closed door
position monitoring contact
to monitor the open, closed,
forced and alarm conditions
of the door.
DOOR LOCK CONNECTION
The Protégé Reader expander provides a connection for 2
electric strike locks with full monitoring of the lock circuit
for tamper and over current/fuse blown conditions. The
door lock monitoring can be disabled if it is not required.
SPECIFICATION
Power Supply
AC Input Voltage 16VAC 50/60Hz @ 40VA (Max)
Operating Current 280mA (Typical)
DC Output (Auxiliary) 1.2A (Max)
Battery Charging 350mA/700mA
Communication
RS-485 Isolated Module Network
Outputs
Lock Outputs 2 Outputs
400mA (Max), 500mA Shutdown
PGM Outputs 6 (50mA Max) Open Collector
Inputs
Zone 8 (500ms to 40sec Input Speed)
Tamper 1 (Normally Closed)
Trouble Zone 16
Dimensions
PCB Dimensions 183mm X 234mm
7.2" X 9.2"
*Specifications are subject to change without notice, please
visit www.integratedcontroltechnology.com for the updated
information.
Unit C, 6 Ascension Place, Mairangi Bay, P.O. Box 302-340
North Harbour, Auckland, New Zealand.
Phone: +64 (9) 476 7124 yFax: +64 (9) 476 7128
www.integratedcontroltechnology.com
2 Reader Expander
Quick Start Guide
PRT-RDI2 / RDS2
INTRODUCTION
The Protégé Reader Expander extends the number of card
reader inputs on the system by 2, number of zone inputs
by 8 (4 zones used for door monitoring and control and
up to eight can be used for extended functionality) and
the number of PGM outputs by 8 (includes 2 monitored
lock control outputs).
•4 Wiegand Reader Mode for 2 Entry/Exit Doors Per
Reader Expander
•Secure Encrypted RS-485 Module Communications
•8 Zone Inputs
•2 Monitored Lock Control PGM Outputs
•6 Open Collector PGM Outputs (Reader Control
Outputs)
•Intelligent Battery Charge and Monitoring
•Smart Reader Missing/Tamper Monitoring
•Online and Remote upgradeable firmware
For a full installation manual or more information on the
Protégé Reader Expander and other Integrated Control
Technology products please login to our website