PT Maxsis RXR User manual

www.powertecnique.com
25kW/42kW to 1MW 3 Phase In - 3 Phase Out
Modular Double Online Conversion Technology (VFI)
Maxsis
RXR
INSTALLATION MANUAL
IM-MRXR-01-0717

GLOSSARY OF ACRONYMS
ACRONYM ITEM Description
RXR300 Power Cabinet 294 KW
RXR130 Power Cabinet 125 kW
RXRC130 Combo Cabinet 126 kW
RXR500SC Switching Cabinet 500kW
RXRBC170 Battery Cabinet 170 kW
PM Power Module
RXR25PM Power Module
RXR42PM Power Module
BU Battery Unit
BUA Battery Unit Array
KUA Empty Battery Unit Array
BM Bypass Module
BM126 Bypass Module
BM252 Bypass Module
CP Connectivity Panel
MU Monitoring Unit
PSU Power Supply Unit
MCU Main Communication Unit
SLOT Slots
ASB Auxiliary Signal Board
- Relay Slot
CIB Cabinet Interface Board
SA Service Access Port
Power Cabinet with 7 slots to place 7xRXR25PM or 7xRXR42PM
Power Cabinet with 5 slots to place 5xRXR25PM
Combo Cabinet with 3 slots to place 3xRXR25PM or 3xRXR42PM + 20x BU
Switching Cabinet to merge 2x RXR300
Battery Cabinet with 9 shelves to place 36x BU
Power module unit (Acronym used to indicate either RXR25PM or RXR42PM )
25 kW power module unit (Description is applicable to RXR25PM, only)
42 kW power module unit (Description is applicable to RXR42PM , only)
Battery Backup intelligent unit
Battery Unit Array (4x BU)
Empty Battery Unit Array (4x BU without batteries)
Solid state transfer device module (Acronym used to indicate either BM126 or BM252)
Solid state transfer device module (Description is applicable to BM126, only)
Solid state transfer device module (Description is applicable to PM252, only)
User and service system interface panel
Intelligent microprocessor monitoring device
Internal circuits power supply unit
Display, Ethernet, and SA ports
Slot to accomodate Riello communication cards
Auxiliary switches status, temp. Sensor and EPO signal interface
Slot to accomodate PTCom 382 and 392
Communication interface card between cabinet
Port interface to connect service maintenance tools
SWBATT Switch Battery Battery / Combo (cabinet) battery breaker
SWMB Switch Manual Bypass Power / Combo (cabinet) manual bypass breaker
SWIN Switch Input External input breaker (on distribution cabinet)
SWBYP Switch Bypass line Input External bpass line input breaker (on distribution cabinet)
B+ - Positive battery voltage/current/temp.
B- - Negative battery voltage/current/temp.

- 1-
Maxsis RXR130
READ "SAFETY MANUAL" BEFORE STARTING
THE MODULAR UPS POWER CABINET INSTALLATION
INSTALLATION ENVIRONMENTS
The Modular UPS Power Cabinet is manufactured for an internal environment.
Essential Requirements:
- avoid dusty environments;
- the relative humidity must comply with the data in the table within this page;
- the operating ambient room temperature must comply with the data in the table within this page;
- avoid environments exposed directly to sunlight and hot air.
To regulate the ambient temperature within the UPS location at the appropriate range, waste heat disposal
systems must be used. Methods which can be used include:
- natural ventilation;
- forced ventilation, recommended if the external temperature is lower (e.g. 20°C) than the temperature at
which you want to operate the UPS;
- air conditioning system, recommended if the external temperature is higher (e.g. 30°C) than the
temperature at which you want to operate the UPS.
MAIN INFORMATION TABLE
Power [kVA / kW] 125 / 125
V Input [V] 380 – 400 – 415 (3PH + N)
Frequency Input [Hz] 50 - 60
V Output [V] 380 – 400 – 415 (3PH + N)
Frequency Output [Hz] 50 / 60
Operating temperature [°C] 0 ÷ 40
Max relative humidity in operation [%] 90% (without condensation)
Max installation height 1000 mt at nominal power
(-1% power for every 100 m above 1000 m) – max 4000 m
Power loss @ 100% load (1) 5.9 kW - 5073 kcal/h – 20130 BTU/h
Power loss @ 50% load (1) 2.7 kW - 2322 kcal/h – 9220 BTU/h
Max Leakage Current [mA] (2) 550
Cabinet Dimension (WxDxH) [mm] 595x1046x2002
Shipping Dimension (WxDxH) [mm] 700x1166x2174
Shipping Weight Power Cabinet [kg] 260
Net Weight without power modules / Bypass module
Included [kg] 240
TOTAL Net Weight with 5 power modules / Bypass module
Included [kg] 420
Air Flow [m3/h] 2710
Degree of protection IP20
(1) 3.97 BTU / h = 1 kcal / h
(2) The load leakage current is added to the one of the UPS on the ground protection conductor
PRELIMINARY INFORMATION FOR INSTALLATION
ALL OPERATIONS DESCRIBED IN THIS SECTION MUST BE PERFORMED BY QUALIFIED AND TRAINED
PERSONNEL ONLY.
Our Company assumes no liability for damages caused by incorrect connections or operations not
contained in this manual.
The following operations have to be performed with the UPS disconnected from the power mains, off
and with all equipment switches open.
Before making the connection, open all cabinet switches and verify that the UPS is completely
isolated from power sources: battery and AC power line. In particular, check that:
- the UPS input line is completely disconnected
- the UPS bypass line is completely disconnected
- the external UPS battery line switch/fuses are open
- all UPS switches are in the open position
- check with a multimeter that there are no dangerous voltages
The first connection to be made is the protective conductor (earth wire), this must be connected to
the bar marked as PE.
The UPS must operate while connected to the earthing system.
The input Neutral must always be connected.
ATTENTION: a three-phase four-wire distribution system is required.
The standard UPS version must be connected to a 3 Phase + Neutral + PE (ground protection) power
line.
Comply with clockwise phase rotation.
Read the battery box manual before connecting the batteries.
Check that the total battery voltage meets the requirements of the UPS (refer to the Battery Box
nameplate).
ATTENTION: the maximum length of the connection cables to the Battery Box is 10 meters.
ATTENTION: After the installation operation is complete, refit the cabinet protection panels using the
appropriate screws.
ELECTROMAGNETIC COMPATIBILITY
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
BATTERY ROOM VENTILATION
The room where the battery box is located must have enough ventilation to ensure the concentration
of hydrogen produced is within safe limits.
The room should preferably be ventilated naturally; if it cannot be, forced ventilation may be
employed.
Standard EN 50272-2 regarding air exchange provides that the minimum aperture must satisfy the
following equation:
A = 28 x Q = 28 x 0.05 x n x Igas x C10 (1/10³) [cm²] where:
A = area of opening [cm²]
Q = airflow required [m³/h]
n = number of battery cells;
C10 = battery capacity in 10 hours [Ah]
Igas = gas producing current [mA/Ah]
according to the standard:
Igas = 1 in backup charging for VRLA type batteries
Igas = 8 in fast charging for VRLA type batteries
NOTE: read the User Manual before using the Maxsis RXR.
NOTE: some images contained in this document are for information purposes only and may not faithfully
demonstrate the parts of the product they represent.

- 2-
POSITIONING INFORMATION
MAXSIS RXR POSITIONING
Warning! The cabinet cannot be moved and/or delivered on site with Power Modules inserted.
When positioning, take into account that:
- the cabinet must be positioned without the Power Modules inserted, the Power Modules can only be inserted once the cabinet
feet have been lowered.
- the wheels are to be used for final positioning only. Specialist moving equipment must be used to transport the UPS near to
the final position.
- plastic parts and the door are not able to act as pushing points or handles.
- you will need to ensure at least enough free space in front of the power cabinet for user operation and maintenance (≈1.5 m).
- no objects should rest on the upper part of the UPS Power Cabinet.
Warning!
The cabinet must be positioned on a level floor.
Ensure that the floor can support the total weight of the system.
The weight of the Power Cabinet full of Power Modules is 420 kg.
A
fter positioning, lower the four feet at the floor, using an appropriate spanner.
Ensure that the total weight of the cabinet is distributed on feet only (the revolving wheels must be lifted from floor).
Ensure that the Power Cabinet is level.
It is possible to reuse the brackets for pallet fastening (slides) to anchor the Power Cabinet to the floor.

- 3-
REMOVING PANELS AND AUXILIARY DEVICES
REMOVING FRONT DOOR REMOVING REAR DOOR PANEL REMOVING COVER ACCESSORY
RELAY BOARD
REMOVING ASB
WARNING! BEFORE REMOVING,
REFER p. 6
REMOVING FRONT COVER
CONNECTIVITY PANEL
REMOVING REAR TERMINAL
CONNECTION PROTECTION COVER
BEFORE REMOVING IT, THE SYSTEM MUST BE
COMPLETELY ISOLATED FROM ALL POWER
SOURCES

- 4-
CABINET PARTS AND MODULES
Warning!
The cabinet cannot be moved and/or delivered
on site with Power Modules inserted.
ATTENTION!
RXR130 is compatible only with
RXR25PM

- 5-
FRONT SIGNALS CONNECTION AND COMMUNICATION DETAILS

-
6
-
R
EAR
/
TOP SIGNALS
C
ONNECTION AND
C
OMMUNICATION
D
ETAILS
AUXILIARY SIGNALS BOARD
WARNING! WHEN ASB IS REMOVED THE SYSTEM SHUTS DOWN.
BEFORE REMOVING ASB MAKE SURE THAT
SWITCH MANUAL BYPASS IS CLOSED.
Auxiliary optoisolated input details:
ATTENTION:
DO NOT APPLY ANY VOLTAGE AT AUXILIARY INPUTS. APPLY ONLY A CLOSED CIRCUIT
OR LEAVE THE CIRCUIT OPEN. INPUTS CIRCUITS HAVE COMMON POLE (SEE IMAGE FOR
DETAILS).
SWIN auxiliary input switch (N.C.)
When the remote input switch is opened, it must close the relative auxiliary contact.
SWMB Auxiliary external manual bypass switch (N.C.)
Before connection remove the pre-mounted jumper.
When the remote maintenance bypass switch is closed, it must open the relative auxiliary
contact.
Note: if it's not used, the jumper must be mounted
SWBYP Auxiliary external bypass switch (N.C.)
When the remote bypass input switch is opened, it must close the relative auxiliary contact.
SWBATT Auxiliary external battery switch (N.O.)
When the external battery switch is opened, it must open the relative auxiliary contact.
Note: if it's not used, the jumper must be mounted
SWOUT Auxiliary external output switch (N.C.)
When the external output switch is opened, it must close the relative auxiliary contact.
TEMP External temperature
Connect the optional temperature probe to read the external temperature.
To install and enable it read “MPW External Battery Temperature Sensor” and “MPW
Advanced Configuration Manual”
OPENING RELEASE SWBATT
Not applicable with this cabinet type
R.E.P.O. Remote emergency power off command (N.C.)
Before connection remove the pre-mounted bridge.
When the remote EPO contact opens, the UPS turns off.
Note: if it's not used, the jumper must be mounted
Connection wires: 1.5 mm
2
double insulated
Attention: in parallel systems each UPS cabinet must have an individual isolated auxiliary
signal board connection. Failure to complywith this requirementwill cause internal damage
to the UPS.

- 7-
POWER CONNECTION INFORMATION
(*) Input voltage at 346 V and battery charger suppling 7 A (each module)
BYPASS AC Line Connection 3PH + N + PE (Dual Mains)
Max
Power
[kW-kVA]
Max
nominal
current
[A]
Max admitted
neutral current
[A]
Size of protection
device (plant)
[A]
Terminal
BYP1, BYP2, BYP3, N, PE Wire BYP1, BYP2, BYP3, N, PE
Type Width
[mm] Bolt Type Cross sectional area
[N x mm2]
126 187 310 200 Al BAR 25
2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
1 x 95
or
1 x AWG 3/0
Output AC Line Connection 3PH + N + PE
N
module
Max
Power
[kW-kVA]
Max
nominal
current
In [A]
Max
admitted
neutral
current
[A]
Terminal
OUT1, OUT2, OUT3, N, PE Wire
OUT1, OUT2, OUT3, N, PE Output Protection
(recommended values for selectivity)
Type Width
[mm] Bolt Type
Cross
sectional
area
[N x mm2]
Normal Fuses
(gL - gG)
Thermal
magnetic
switches
(C curve)
1 25 37 62
Al BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
1 x 95
or
1 x AWG 3/0
In / 4 In / 4
2 50 74 123
3 75 111 185
4 100 148 246
5 125 185 269
WARNING
THE INPUT, OUTPUT AND PROTECTIVE EARTHING CONDUCTORS MUST BE SIZED FOLLOWING
THE RATED VOLTAGE AND CURRENT, AS SHOWN IN THE TABLES AND ALSO COMPLY WITH
LOCAL AND NATIONAL REGULATION FOR MAXIMUM POWER RATING
THE PROTECTIVE EARTHING CONDUCTOR (PE) MUST BE CONNECTED PRIOR TO
CONNECTING ANY INPUT / OUTPUT CABLES
SHORTCIRCUIT PROTECTION
UPS in BYPASS OPERATION: the load is instantly switched to the bypass line (l2t=145000A2s): the input line is
connected to the output without any internal protection.
UPS in INVERTER OPERATION: the UPS protects itself supplying 2.5 times nominal current to the output for the
first 0.2 s, which is then reduced to 1.5 times nominal for 0.3 s. After this time (0.5 s) it switches off.
BACKFEED PROTECTION
Cabinet is equipped with an internal protection system which, if a backfeed is detected, cuts the bypass line (through a
metal contactor). If backfeed is detected, the load is powered by the inverter, also during the battery operation.
DIFFERENTIAL SWITCH
In the absence of an input separating transformer, the neutral from the mains power supply is connected to the neutral of
the UPS output. This way the neutral regime of the equipment is not modified.
The input neutral is connected to the output neutral. The distribution system that powers the UPS is not modified by the
cabinet.
CAUTION: make sure that the equipment is connected correctly to the input neutral, otherwise
damage to the UPS may be caused.
DUAL INPUT
The neutral for the input line and bypass line are shared inside the device.
A single differential switch must be fitted upstream of the point at which the line divides to supply the standard inputs and
bypass inputs for the cabinet.
When operating from mains power, a differential switch located at the input can trip as the output circuit protection is not
isolated from the input circuit.
In addition, other differential switches can be inserted on the output, possibly coordinated with the switches at the input.
The differential switch located upstream must have the following features:
- DIFFERENTIAL CURRENT ADJUSTED TO THE SUM OF THE UPS CABINET + LOAD. WE STRONGLY
RECOMMEND MAINTAINING AN ADEGUATE MARGIN TO AVOID DELAYED ACTUATION (1A MINIMUM
CURRENT)
- TYPE B
- DELAY GREATER THAN OR EQUAL TO 0,1s
Input AC Line Connection 3PH + N + PE (Single / Dual Mains)
N
module
Max
Power
[kW-kVA]
Max
current (*)
[A]
Max admitted
neutral current
[A]
Size of
protection
device (plant)
[A]
Terminal IN1, IN2, IN3, N, PE Wire IN1, IN2, IN3, N, PE
Type Width
[mm] Bolt Type Cross sectional
area
[N x mm2]
1 25 50 62 50
Al BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
1 x 95
or
1 x AWG 3/0
2 50 100 123 100
3 75 150 185 160
4 100 200 246 200
5 125 250 269 250
Input Battery DC Line Connection BATT+, BATT-, BATT N, PE (Nominal voltage +240V, -240V)
N
module
Max
Power
[kW-kVA]
Rated Current [A] Absolute
max sized
battery
protection
device [A]
Terminal
BATT +, BATT -, BATT N Earthing terminal PE Wire
BATT +, BATT -, BATT N, PE
@nominal
battery
voltage
@end of
discharge
voltage Type Width
[mm] Bolt Type Width
[mm] Bolt Type Cross sectional
area [N x mm2]
1 25 55 66 80
Al BAR 30 2 x M8
16 Nm Al BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
1 x 120
or
1 x AWG 4/0
2 50 109 131 160
3 75 163 196 200
4 100 217 261 315
5 125 272 326 350

- 8-
POWER CONNECTION DETAIL

- 9-

- 10 -

- 11 -
MAXSIS RXR300
READ "SAFETY MANUAL" BEFORE STARTING
THE MODULAR UPS POWER CABINET INSTALLATION
INSTALLATION ENVIRONMENTS
The Maxsis RXR is manufactured for an internal environment.
Essential Requirements:
- avoid dusty environments;
- the relative humidity must comply with the data in the table within this page;
- the operating ambient room temperature must comply with the data in the table within this page;
- avoid environments exposed directly to sunlight and hot air.
To regulate the ambient temperature within the UPS location at the appropriate range, waste heat disposal
systems must be used. Methods which can be used include:
- natural ventilation;
- forced ventilation, recommended if the external temperature is lower (e.g. 20°C) than the temperature at
which you want to operate the UPS;
- air conditioning system, recommended if the external temperature is higher (e.g. 30°C) than the
temperature at which you want to operate the UPS.
MAIN INFORMATION TABLE
Power [kVA / kW] 294 / 294
V Input [V] 380 – 400 – 415 (3PH + N)
Frequency Input [Hz] 50 - 60
V Output [V] 380 – 400 – 415 (3PH + N)
Frequency Output [Hz] 50 / 60
Operating temperature [°C] 0 ÷ 40
Max relative humidity in operation [%] 90% (without condensation)
Max installation height 1000 mt at nominal power
(-1% power for every 100 m above 1000 m) – max 4000 m
Power loss @ 100% load (1) 13.8 kW - 11866 kcal/h – 47100 BTU/h
Power loss @ 50% load (1) 6.4 kW - 5503 kcal/h – 21840 BTU/h
Max Leakage Current [mA] (2) 550
Cabinet Dimension (WxDxH) [mm] 595x1046x2002
Shipping Dimension (WxDxH) [mm] 700x1166x2174
Shipping Weight Power Cabinet [kg] 320
Net Weight without power modules / Bypass module
Included [kg] 300
TOTAL Net Weight with 7 power modules / Bypass module
Included [kg] 552 with PM25 / 580 with PM42
Air Flow [m3/h] 3800
Degree of protection IP20
(1) 3.97 BTU / h = 1 kcal / h
(2) The load leakage current is added to the one of the UPS on the ground protection conductor
PRELIMINARY INFORMATION FOR INSTALLATION
ALL OPERATIONS DESCRIBED IN THIS SECTION MUST BE PERFORMED BY QUALIFIED AND TRAINED
PERSONNEL ONLY.
Our Company assumes no liability for damages caused by incorrect connections or operations not
contained in this manual.
The following operations have to be performed with the UPS disconnected from the power mains, off
and with all equipment switches open.
Before making the connection, open all cabinet switches and verify that the UPS is completely
isolated from power sources: battery and AC power line. In particular, check that:
- the UPS input line is completely disconnected
- the UPS bypass line is completely disconnected
- the external UPS battery line switch/fuses are open
- all UPS switches are in the open position
- check with a multimeter that there are no dangerous voltages
The first connection to be made is the protective conductor (earth wire), this must be connected to
the bar marked as PE.
The UPS must operate while connected to the earthing system.
The input Neutral must always be connected.
ATTENTION: a three-phase four-wire distribution system is required.
The standard UPS version must be connected to a 3 Phase + Neutral + PE (ground protection) power
line.
Comply with clockwise phase rotation.
Read the battery box manual before connecting the batteries.
Check that the total battery voltage meets the requirements of the UPS (refer to the Battery Box
nameplate).
ATTENTION: the maximum length of the connection cables to the Battery Box is 10 meters.
ATTENTION: After the installation operation is complete, refit the cabinet protection panels using the
appropriate screws.
ELECTROMAGNETIC COMPATIBILITY
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
BATTERY ROOM VENTILATION
The room where the battery box is located must have enough ventilation to ensure the concentration
of hydrogen produced is within safe limits.
The room should preferably be ventilated naturally; if it cannot be, forced ventilation may be
employed.
Standard EN 50272-2 regarding air exchange provides that the minimum aperture must satisfy the
following equation:
A = 28 x Q = 28 x 0.05 x n x Igas x C10 (1/10³) [cm²] where:
A = area of opening [cm²]
Q = airflow required [m³/h]
n = number of battery cells;
C10 = battery capacity in 10 hours [Ah]
Igas = gas producing current [mA/Ah]
according to the standard:
Igas = 1 in backup charging for VRLA type batteries
Igas = 8 in fast charging for VRLA type batteries
NOTE: read the User Manual before using the Maxsis RXR.
NOTE: some images contained in this document are for information purposes only and may not faithfully
demonstrate the parts of the product they represent.

-0MNMPWK25N1ENIA-
- 12 -
POSITIONING INFORMATION
MAXSIS RXR POSITIONING
Warning! The cabinet cannot be moved and/or delivered on site with Power Modules inserted.
When positioning, take into account that:
- the cabinet must be positioned without the Power Modules inserted, the Power Modules can only be inserted once the cabinet
feet have been lowered.
- the wheels are to be used for final positioning only. Specialist moving equipment must be used to transport the UPS near to
the final position.
- plastic parts and the door are not able to act as pushing points or handles.
- you will need to ensure at least enough free space in front of the power cabinet for user operation and maintenance (≈1.5 m).
- no objects should rest on the upper part of the UPS Power Cabinet.
Warning!
The cabinet must be positioned on a level floor.
Ensure that the floor can support the total weight of the system.
The weight of the RXR300 full of Power Modules is 552 kg with
RXR25PM or 580 kg with RXR42PM.
A
fter positioning, lower the four feet at the floor, using an appropriate spanner.
Ensure that the total weight of the cabinet is distributed on feet only (the revolving wheels must be lifted from floor).
Ensure that the Power Cabinet is level.
It is possible to reuse the brackets for pallet fastening (slides) to anchor the Power Cabinet to the floor.

- 13 -
REMOVING PANELS AND AUXILIARY DEVICES
REMOVING FRONT DOOR REMOVING REAR DOOR PANEL REMOVING COVER ACCESSORY
RELAY BOARD
REMOVING ASB
WARNING! BEFORE REMOVING,
REFER p. 16
REMOVING FRONT COVER
CONNECTIVITY PANEL
REMOVING REAR TERMINAL
CONNECTION PROTECTION COVER
BEFORE REMOVING IT, THE SYSTEM MUST BE
COMPLETELY ISOLATED FROM ALL POWER
SOURCES

- 14 -
CABINET PARTS AND MODULES
Warning!
The cabinet cannot be moved and/or delivered
on site with Power Modules inserted.
ATTENTION!
PWC 300 is compatible with both PM25 or PM42
but not with combination of the two models

- 15 -
FRONT SIGNALS CONNECTION AND COMMUNICATION DETAILS

-
16
-
R
EAR
/
TOP SIGNALS
C
ONNECTION AND
C
OMMUNICATION
D
ETAILS
AUXILIARY SIGNALS BOARD
WARNING! WHEN ASB IS REMOVED THE SYSTEM SHUTS DOWN.
BEFORE REMOVING ASB MAKE SURE THAT
SWITCH MANUAL BYPASS IS CLOSED.
Auxiliary optoisolated input details:
ATTENTION:
DO NOT APPLY ANY VOLTAGE AT AUXILIARY INPUTS. APPLY ONLY A CLOSED CIRCUIT
OR LEAVE THE CIRCUIT OPEN. INPUTS CIRCUITS HAVE COMMON POLE (SEE IMAGE FOR
DETAILS).
SWIN auxiliary input switch (N.C.)
When the remote input switch is opened, it must close the relative auxiliary contact.
SWMB Auxiliary external manual bypass switch (N.C.)
Before connection remove the pre-mounted jumper.
When the remote maintenance bypass switch is closed, it must open the relative auxiliary
contact.
Note: if it's not used, the jumper must be mounted
SWBYP Auxiliary external bypass switch (N.C.)
When the remote bypass input switch is opened, it must close the relative auxiliary contact.
SWBATT Auxiliary external battery switch (N.O.)
When the external battery switch is opened, it must open the relative auxiliary contact.
Note: if it's not used, the jumper must be mounted
SWOUT Auxiliary external output switch (N.C.)
When the external output switch is opened, it must close the relative auxiliary contact.
TEMP External temperature
Connect the optional temperature probe to read the external temperature.
To install and enable it read “MPW External Battery Temperature Sensor” and “MPW Advanced
Configuration Manual”.
OPENING RELEASE SWBATT
Not applicable with this cabinet type
R.E.P.O. Remote emergency power off command (N.C.)
Before connection remove the pre-mounted bridge.
When the remote EPO contact opens, the UPS turns off.
Note: if it's not used, the jumper must be mounted
Connection wires: 1.5 mm
2
double insulated
Attention: in parallel systems each UPS cabinet must have an individual isolated auxiliary
signal board connection. Failure to complywith this requirementwill cause internal damage
to the UPS.

- 17 -
POWER CONNECTION INFORMATION
(*) Input voltage at 346 V and battery charger suppling 7 A (each module)
BYPASS AC Line Connection 3PH + N + PE (Dual Mains)
Max
Power
[kW-kVA]
Max
Nominal
current
[A]
Max admitted
neutral current
[A]
Size of protection
device (plant)
[A]
Terminal
BYP1, BYP2, BYP3, N, PE Wire BYP1, BYP2, BYP3, N, PE
Type Width
[mm] Bolt Type Cross sectional area
[N x mm2]
252 373 560 400 Cu BAR 25
2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
2 x 95
or
2 x AWG 3/0
Output AC Line Connection 3PH + N + PE
PM
type N
module
Max
Power
[kW-kVA]
Max
Nominal
Current
In[A]
Max
admitted
neutral
current [A]
Terminal
OUT1, OUT2, OUT3, N, PE Wire
OUT1, OUT2, OUT3, N, PE Output Protection
(recommended values for selectivity)
Type Width
[mm] Bolt Type
Cross
sectional
area
[N x mm2]
Normal Fuses
(gL - gG)
Thermal
magnetic
switches
(C curve)
PM25
1 25 37 62
Cu BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
2 x 50
or
2 x AWG 2/0
In / 4 In / 4
2 50 74 123
3 75 111 185
4 100 148 246
5 125 185 308
6 150 222 350
7 175 259 350
PM42
1 42 62 103
Cu BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
2 x 95
or
2 x AWG 3/0
In / 4 In / 4
2 84 124 207
3 126 187 310
4 168 249 414
5 210 311 517
6 252 373 560
7 294 436 560
WARNING
THE INPUT, OUTPUT AND PROTECTIVE EARTHING CONDUCTORS MUST BE SIZED FOLLOWING
THE RATED VOLTAGE AND CURRENT, AS SHOWN IN THE TABLES AND ALSO COMPLY WITH
LOCAL AND NATIONAL REGULATION FOR MAXIMUM POWER RATING
THE PROTECTIVE EARTHING CONDUCTOR (PE) MUST BE CONNECTED PRIOR TO
CONNECTING ANY INPUT / OUTPUT CABLES
SHORTCIRCUIT PROTECTION
UPS in BYPASS OPERATION: the load is instantly switched to the bypass line (l2t=1620000A2s): the input line is
connected to the output without any internal protection.
UPS in INVERTER OPERATION: the UPS protects itself supplying 2.5 times nominal current to the output for the
first 0.2 s, which is then reduced to 1.5 times nominal for 0.3 s. After this time (0.5 s) it switches off.
BACKFEED PROTECTION
Cabinet is equipped with an internal protection system which, if a backfeed is detected, cuts the bypass line (through a
metal contactor). If backfeed is detected, the load is powered by the inverter, also during the battery operation.
DIFFERENTIAL SWITCH
In the absence of an input separating transformer, the neutral from the mains power supply is connected to the neutral of
the UPS output. This way the neutral regime of the equipment is not modified.
The input neutral is connected to the output neutral. The distribution system that powers the UPS is not modified by the
cabinet.
CAUTION: make sure that the equipment is connected correctly to the input neutral, otherwise
damage to the UPS may be caused.
DUAL INPUT
The neutral for the input line and bypass line are shared inside the device.
A single differential switch must be fitted upstream of the point at which the line divides to supply the standard inputs and
bypass inputs for the cabinet.
When operating from mains power, a differential switch located at the input can trip as the output circuit protection is not
isolated from the input circuit.
In addition, other differential switches can be inserted on the output, possibly coordinated with the switches at the input.
The differential switch located upstream must have the following features:
- DIFFERENTIAL CURRENT ADJUSTED TO THE SUM OF THE UPS CABINET + LOAD. WE STRONGLY
RECOMMEND MAINTAINING AN ADEGUATE MARGIN TO AVOID DELAYED ACTUATION (1A MINIMUM
CURRENT)
- TYPE B
- DELAY GREATER THAN OR EQUAL TO 0,1s
Input AC Line Connection 3PH + N + PE (Single / Dual Mains)
PM type N
module
Max
Power
[kW-kVA]
Max
current (*)
[A]
Max admitted
neutral
current
[A]
Size of
protection
device (plant)
[A]
Terminal IN1, IN2, IN3, N, PE Wire IN1, IN2, IN3, N, PE
Type Width
[mm] Bolt Type Cross sectional
area
[N x mm2]
RXR25PM
1 25 50 62 50
Cu BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
2 x 50
or
2 x AWG 2/0
2 50 100 123 100
3 75 150 185 160
4 100 200 246 200
5 125 250 308 250
6 150 300 350 300
7 175 350 350 350
RXR42PM
1 42 80 103 100
Cu BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
2 x 95
or
2 x AWG 3/0
2 84 160 207 180
3 126 239 310 250
4 168 319 414 350
5 210 399 517 400
6 252 478 560 500
7 294 558 560 600
Input Battery DC Line Connection BATT+, BATT-, BATT N, PE (Nominal voltage +240V, -240V)
PM
type N
module
Max
Power
[kW-kVA]
Rated Current [A] Absolute
max sized
battery
protection
device [A]
Terminal
BATT +, BATT -, BATT N Earthing terminal PE Wire
BATT +, BATT -, BATT N, PE
@nominal
battery
voltage
@end of
discharge
voltage Type Width
[mm] Bolt Type Width
[mm] Bolt Type Cross sectional
area [N x mm2]
PM25
1 25 55 66 80
Cu BAR 30 2 x M8
16 Nm Cu BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
2 x 70
or
2 x AWG 3/0
2 50 109 131 160
3 75 163 196 200
4 100 217 261 315
5 125 272 326 350
6 150 327 392 400
7 175 382 458 425
PM42
1 42 92 110 125
Cu BAR 30 2 x M8
16 Nm Cu BAR 25 2 x M8
16 Nm
FG7R (90°C)
or
AWG Style 1015
(105°C)
2 x 120
or
2 x AWG 4/0
2 84 183 220 250
3 126 275 330 350
4 168 366 440 500
5 210 458 550 600
6 252 550 660 700
7 294 641 770 800

- 18 -
POWER CONNECTION DETAIL
Table of contents