QEM HB 237.16 User manual

User Manual
Supplement to "Installation, maintenance and servicing manual"
POSITION CONTROLLER WITH POSITIVE AND NEGATIVE QUOTAS,
AND MANAGEMENT OF 8 OUTPUTS PROGRAMMABLE WITH UP TO 9
PROGRAMS
HB 237.16
(OHFWURQLF ,QVWUXPHQW
PRG
SET
b237H16

Quality in Electronic Manufacturing
Pag. 2 di 27
HB 237.16
LIST OF SUBJECTS DEALT WITH IN THIS MANUAL
CHAP. 1 - INTRODUCTION
- Supplementary nature of manual 1 - 1
- References 1 - 2
- Responsibility and validity 1 - 3
- Description of operation 1 - 4
CHAP. 2 - OPERATOR/MACHINE INTERFACE
- Description of keyboard 2 - 1
- Description of inputs 2 - 2
- Description of outputs 2 - 3
CHAP. 3 - SETTING UP FOR OPERATION
- Programming (set-up) 3 - 1
CHAP. 4 - USE
- Work programs and auxiliary functions 4 - 1
- Operation graphs and tables 4 - 2
CHAP. 5 - ASSISTANCE
- Inputs and outputs troubleshooting 5 - 1
- How to complete the technical assistance fax form 5 - 2
- Warranty 5 - 3

Quality in Electronic Manufacturing
Pag. 3 di 27
HB 237.16
CHAPTER 1
Supplementary nature of manual
References
Responsibility and validity
Description of operation
INTRODUCTION

Quality in Electronic Manufacturing
Pag. 4 di 27
HB 237.16
1 - 1 SUPPLEMENTARY NATURE OF MANUAL
This manual is to be considered as a supplement to the "Installation, maintenance and servicing manual" which
contains information on wiring, checking and eliminating faults, start-up and maintenance procedures. This manual
gives instructions on the use and correct programming of the instrument.
You are urged, therefore, to read the manual carefully and, if you have any queries, to contact QEM for further
explanations by sending the assistance fax contained in the manual.
1 - 2 REFERENCES
The documentation relative to the instruments designed and sold by QEM has been divided into different booklets for
effective and speedy consultation according to the type of information required.
User Manual
Explanation of software.
This manual gives all the necessary
information for the understanding and
use of the instrument described. The
manual deals with the instrument
software, it gives information on the
understanding, programming,
calibration and use of the instrument
described.
Once the instrument is installed
following the indications given in the
Installation, maintenance and
servicing manual, this user manual
gives all the necessary information
for the correct use and programming
of the instrument.
Installation, maintenance and
servicing manual
All the necessary information for
installation, maintenance and
assistance.
In-depth explanations of all essential
details for correct installation and
maintenance.
The aim is to provide you with valid
and accurate information for the
manufacture of products of
recognised quality and reliability. It is
also a valid support for whoever
needs technical assistance
concerning a machine that includes
a QEM instrument.
Hardware structure
Basic information on the standard
hardware in the series plus
customisation possibilities.
This booklet is enclosed with the
user manual and describes the
hardware configuration for the series
of instruments described.
It also gives the standard electrical,
technical and mechanical
specifications for the series, together
with the possibilities of hardware
customisation in relation to the
different software versions.

Quality in Electronic Manufacturing
Pag. 5 di 27
HB 237.16
Instrument
release
Manual
release
0 0 New manual 01 / 03 / 97
Modifications to manual Date of
modifications
1 - 3 RESPONSIBILITY AND VALIDITY
RESPONSIBILITY
QEM declines all responsibility for any injury to persons or damage to things resulting from the failure to observe the
instructions and rules in this manual and the "Installation, maintenance and servicing manual". It is furthermore
specified that the customer/purchaser is bound to use the instrument according to the instructions provided by QEM
and, if any doubts arise, to send a written query to QEM. Any authorisation for exceptions or substitutions, if contested,
will be deemed valid by QEM only if written consent has been given by QEM.
The reproduction or transfer of all or part of this manual to third parties is forbidden without QEM's written consent.
Any transgression will result in a claim for compensation for the damages sustained.
All rights deriving from patent or designs are reserved.
QEM reserves the right to make partial or complete modifications to the characteristics of the instrument described
and the corresponding documentation.
Objective
The objective of this manual is to give the general rules for the use of the instrument described.
Recommendation
Write down all the instrument setting and programming parameters, keeping them in a safe place to facilitate any future
replacement or servicing operations.
VALIDITY
This manual is applicable to all instruments designed, manufactured and tested by QEM with the same order code.
This document is valid in its entirety, save errors or omissions.

Quality in Electronic Manufacturing
Pag. 6 di 27
HB 237.16
1 - 4 DESCRIPTION OF OPERATION
The instrument HB 237.16 controls the position of one axis and governs the activation and de-activation of 8 totally
programmable outputs. The quotas for each single output can be set in a maximum of 9 programs that can be called
only from the keyboard.

Quality in Electronic Manufacturing
Pag. 7 di 27
HB 237.16
CHAPTER 2
Description of keyboard
Description of inputs
Description of outputs
OPERATOR/MACHINE
INTERFACE

Quality in Electronic Manufacturing
Pag. 8 di 27
HB 237.16
2 - 1 DESCRIPTION OF KEYBOARD
Key Function
Normal operation: Pressed for one second, gives access to choice of program to be
executed.
Data input: confirms the displayed data.
Normal operation: not used.
Data input: resets displayed data to zero.
Normal operation: pressed for two seconds, displays input/output diagnostics.
Data input: increases impulsively or continuously the figure selected on the display (the one
that flashes).
Normal operation: not used.
Data input: moves to the left the selection of the figure displayed.
Lighted when programming set-up parameters.
Lighted when introducing work programs.
Not used.
Not used.
When lighted, indicates possibility of introducing the sign "-".
For adding a value to the count.
Gives access to password-protected functions.
+
+
For introducing work programs.
+
PRG
SET

Quality in Electronic Manufacturing
Pag. 9 di 27
HB 237.16
2 - 2 DESCRIPTION OF INPUTS
Characteristics of inputs
Refer to the chapter entitled "Electrical characteristics" in the "Hardware stgructure" booklet enclosed with this manual.
Name
I1 ON X P1 Programmable input 1. Its function depends on the type of programming made in the "FI" set-up
parameter.
I2 ON X P1 Programmable input 2. Its function depends on the type of programming made in the "F2"set-up parameter.
By holding down together the keys (-) and (ENTER) + password 732, it is possible to set the input acquisition
time.
Polarizer
Operating logic Activation mode
Description
Key
X = See description.
Name
+ Positive transducer supply. Positive voltage supplied by the instrument to feed instrument inputs and transducers.
- Negative transducer supply. Negative voltage supplied by the instrument to feed inputs and transducers.
GND Ground connection. A Ø 4 mm. conductor is recommended.
Vac Instrument supply voltage. Alternating voltage as per code in your order.
Vac Instrument supply voltage. Alternating voltage as per code in your order.
Description

Quality in Electronic Manufacturing
Pag. 10 di 27
HB 237.16
COUNT INPUTS
Name
F1 N / P P1 "Phase 1" input incremental transducer.
F1 N / P P1 "Phase 2" input incremental transducer.
For details of the count inputs, refer to the chapter entitled "Electrical characteristic" in the "Hardware
structure" booklet enclosed with this manual.
PolarizerOperating logic
Description
Key
N = Transducer with NPN logic.
P = Transducer with PNP logic.
2 - 3 OUTPUTS
Output Characteristics
Refer to the chapter entitled "Electrical Characteristics" in the "Hardware structure" booklet enclosed with this manual.
Name
U1 P C1 C Quota 1. With set-up parameter "LI" set on "0", the output is activated when the count reaches the value of
the quota set as parameter "I" in the work program. When the set-up parameter "LI" is set on "1", the output
is de-activated when the count reaches the value of the quota set as parameter "I" in the work program.
U2 P C1 C Quota 2. §With set-up parameter "L2" is set on "0", the output is activated when the count reaches the value
of the quota set as parameter "2" in the work program. When the set-up parameter "L2" is set on "1", the output
is de-activated when the count reaches the value of the quota set as parameter "2" in the work program.
Operating logic Polarizer Activation mode
Description
Key
C = Continuous signal.
P = Programmable in set-up.

Quality in Electronic Manufacturing
Pag. 11 di 27
HB 237.16
Charatteristics of output expansions (option L6 or U6)
Refer to the chapter entitled "Electrical characteristics" in the Hardware structure" booklet enclosed with this manual.
Name
U3 P C2 C Quota 3. With set-up parameter "L3" set on "0", the output is activated when the count reaches the value of
the quota set as parameter "3" in the work program. When the set-up parameter "L3" is set on "1", the output
is de-activated when the count reaches the value of the quota set as parameter "3" in the work program.
U4 P C2 C Quota 4. With set-up parameter "L4" set on "0", the output is activated when the count reaches the value set
as parameter "4" in the work program. When the set-up parameter "L4" is set on "1", the output is de-activated
when the count reaches the vaue of the quota set as parameter "4" in the work program.
U5 P C2 C Quota 5. With set-up parameter "L5" set on "0", the output is activated when the count reaches the value of
the quota set as parameter "5" in the work program. When the set-up parameter "L5" is set on "1", the output
is de-activated when the count reaches the value of the quota set as parameter "5" in the work program.
U6 P C2 C Quota 6. With set-up parameter "L6" set on "0", the output is activated when the count reaches the value of
the quota set as parameter "6" in the work program. When the set-up parameter "L6" is set on "1", the output
is de-activated when the count reaches the value of the quota set as parameter "6" in the work program.
U7 P C2 C Quota 7. With set-up parameter "L7" set on "0", the output is activated when the count reaches the value of
the quota set as parameter "7" in the work program. When the set-up parameter "L7"is set on "1", the output
is de-activated when the count reaches the value of the quota set as parameter "7" in the work program.
U8 P C2 C Quota 8. With set-up parameter "L8"set on "0", the output is activated when the count reaches the value of
the quota set as parameter "8" in the work program. When the set-up parameter "L8"is set on "1", the output
is de-activated when the count reaches the value of the quota set as parameter "8" in the work program.
Operating logic Polarizer Minimum activation
time [ms]
Descrizione
Key
C = Continuous signal.
P = Programmable in set-up.

Quality in Electronic Manufacturing
Pag. 12 di 27
HB 237.16
CHAPTER 3
SETTING UP FOR OPERATION
Programming (set-up)

Quality in Electronic Manufacturing
Pag. 13 di 27
HB 237.16
3 - 1 SET-UP
As these parameters set the operating mode of the instrument, access is restricted to the installer only; a password
must be entered for access to programming as follows:
Description
Access the set-up programming.
Enter the access code "237" and confirm with ENTER.
Keyboard Display
H000
+
=ON
FUNCTION DISPLAY DESCRIPTION
0=The instrument is not provided with Input/Output expansion.
1=Input/Output expansion is installed on the instrument.
Expansion
enabling
AE0
0=Normal display.
1=Display with HDR 1 system (High definition reading).
2=Display with HDR 2 system (High definition reading).
N.B. Refer to the "Installation, maintenance and servicing"
manual.
Hd0
Display method
Specifies the number of figures after the decimal point, with which
to display the count (axis position).
N.B. Introduction of decimal figures influences the DISPLAY of
the count; precision in positioning depends on the number
of impulses supplied by the transducer.
Cd0
Decimal figures
Max. 3
This parameter indicates by how much the encoder revolution
impulses must be multiplied to display the lengths in the required
unit of measurement. Values can be introduced from 0.00200 to
4.00000 bearing in mind that the frequency of the F1 phases must
not exceed the instruments maximum count frequency.
N.B. Refer to the "Installation, maintenance and servicing
manual".
Encoder resolution
E400000
0=Not enabled.
1=Resets count to zero.
2=Loads the count in impulse mode with the preset quota.
CL0
Functions of the
CLEAR key
× 1 sec.
PRG

Quality in Electronic Manufacturing
Pag. 14 di 27
HB 237.16
FUNCTION DISPLAY DESCRIPTION
0= No function.
1= Continuous loading of the preset quota.
2= Impulse loading of the preset quota on the count when input
I1 is activated.
3= Impulse loading of the preset quota on the count when input
I1 is de-activated.
4= Impulse loading of the preset quota on the count when input
I1 is activated only when input I2 is activated and parameter
"F2" is set on "1" (fast input is interrupted).
5= Impulse loading of the preset quota on the count when input
I1 is de-activated only when input I2 is activated and parameter
"F2" is set on "1" (fast input is interrupted).
6= Continuous zero reset of outputs.
7= Program increase.
8= Restart program (its activation utilises program number 1).
FI0
0= No function.
1= Enables preset loading.
2= Continuous zero reset of outputs.
3=Program increase.
4= Restart program (its activation utilises program number 1).
5= Blocks the count.
N.B. In order to obtain the required acquisition speed for input I2
the minimum acquisition times must be calibrated.
F20
Choice of functions
for input I2
Choice of functions
for input I1

Quality in Electronic Manufacturing
Pag. 15 di 27
HB 237.16
FUNCTION DISPLAY DESCRIPTION
This is the value loaded on the count when input I1 is activated or
the CLEAR key is pressed when the parameter "FC" is set on "2".
QI1234
Determines the number of programs to be used.
nP0
0= Introduction of work programs without the access code.
1= Introduction of work programs with the access code (password
532).
Introduction of
work programs
EP0
0= Output disabled.
1= The output is activated when the count is equal to or greater
than the value introduced in the work program (quota 1).
The count increases (UP).
2= The output is activated when the count is equal to or greater
than the value introduced in the work program (quota 1) and
remains enabled for the time set in the work program (timer 1).
The count increases (UP).
3= The output is activated when the count is equal to or greater
than the value introduced in the work program (quota 1) and
remains enabled for the delta set in the work program (delta
1).
The count increases (UP).
4=The output is activated when the count is equal to or less than
the value introduced in the work program (quota 1).
The count decreases (DOWN).
5= The output is activated when the count is equal to or less than
the value introduced in the work program (quota 1) and
remains enabled for the time set in the work program (timer 1).
The count decreases (DOWN).
6=The output is activated when the count is equal to or less than
the value introduced in the work program (quota 1) and
remains enabled for the delta set in the work program (delta
1).
The count decreases (DOWN).
FUI 0
Choice of functions
for output U1
Preset Quota
Min. -99999
Max. 99999
Number of
programs
Max. 9

Quality in Electronic Manufacturing
Pag. 16 di 27
HB 237.16
FUNCTION DISPLAY DESCRIPTION
0= Output disabled.
1= The output is activated when the count is equal to or greater
than the value introduced in the work program (quota 2).
The count increases (UP).
2=The output is activated when the count is equal to or greater
than the value introduced in the work program (quota 2) and
remains enabled for the time set in the work program (timer 2).
The count increases (UP).
3=The output is activated when the count is equal to or greater
than the value introduced in the work program (quota 2) and
remains enbled for the delta set in the work program (delta 2).
The count increases (UP).
4= The output is activated when the count is equal to or less than
the value introduced in the work program (quota 2).
The count decreases (DOWN).
5= The output is activated when the count is equal to or less than
the value introduced in the work program (quota 2) and
remains enabled for the time set in the work program (timer 2).
The count decreases (DOWN).
6= The output is activated when the count is equal to or less than
the value introduced in the work program (quota 2) and
remains enabled for the delta set in the work program (delta
2).
The count decreases (DOWN).
FU2 0
Choice of functions
for output U2

Quality in Electronic Manufacturing
Pag. 17 di 27
HB 237.16
FUNCTION DISPLAY DESCRIPTION
FU3 0
Choice of functions
for outputs U3, U4
U5, U6, U7, U8
0= Output disabled.
1= The output is activated when the count is equal to or greateer
than the value introduced in the work program (quotas 3÷8).
The count increases (UP).
2=The output is activated when the count is equal to or greater
than the value introduced in the work program (quotas 3÷8)
and remains enabled for the time set in the work program
(timer 3÷8).
The ocunt increases (UP).
3= The output is activated when the count is equal to or greater
than the value introduced in the work program (quotas 3÷8)
and remains enabled for the delta set in the work program
(delta 3÷8).
The count increases (UP).
4= The output is activated when the count is equal to or less than
the value introduced in the work program (quotas 3÷8).
The count decreases (DOWN).
5= The output is activated when the count is equal to or less than
the value introduced in the work program (quotas 3÷8) and
remains enabled for the time set in the work program (timer
3÷8).
The count decreases (DOWN).
6= Theoutput is activated when the count is equal to or less than
the value introduced in the work program (quotas 3÷8) and
remains enabled for the delta set in the work program (delta
3÷8).
The count decreases (DOWN).
○○○○○○
FU8 0
These displays appear if the parameter "Expansion enabling" is set on 1
Output U1
logic status
LI0
0=Output U1 is normally de-activated.
1=Output U1 is normally activated.
Output U2
logic status
L20
0= Output U2 is normally de-activated.
1= Output U2 is normally activated.

Quality in Electronic Manufacturing
Pag. 18 di 27
HB 237.16
FUNCTION DISPLAY DESCRIPTION
These displays appear if the parameter "Expansion enabling" is set on 1
Output U3
logic status
L30
0= Output U3 is normally de-activated.
1=Output U3 is normally activated.
Output U4
logic status
L40
0= Output U4 is normally de-activated.
1= Output U4 is normally activated.
Output U5
logic status
L50
0=Output U5 is normally de-activated.
1= Output U5 is normally activated.
Output U6
logic status
L60
0= Output U6 is normally de-activated.
1= Output U6 is normally activated.
Output U7
logic status
L70
0= Output U7 is normally de-activated.
1=Output U7 is normally activated.
Output U8
logic status
L80
0=Output U8 is normally de-activated.
1= Output U8 is normally activated.
After programming the last function return to the display in use before entering set-up (PRG led = OFF).
N.B. To obtain the required acquisition speed for input I2 the minimum acquisition times must be calibrated.

Quality in Electronic Manufacturing
Pag. 19 di 27
HB 237.16
CHAPTER 4
USE
Work programs and auxiliary functions
Operation graphs and tables

Quality in Electronic Manufacturing
Pag. 20 di 27
HB 237.16
4 - 1 WORK PROGRAMS AND AUXILIARY FUNCTIONS
INTRODUCING A SINGLE WORK PROGRAM (SET-UP "nP" SET ON "1")
Access introduction of work program.
Example with set-up parameter "FU1" set on "1".
The current quota 1 (flashing) is displayed.
The operator can introduce the quota relative to the first output
enabled in set-up (min. -9999 - max. 9999) and confirm it with the
ENTER key.
Example with set-up parameter "FU2" set on "2".
The current quota 2 (flashing) is displayed.
The operator can introduce the quota relative to the second output
enabled in set-up (min. -9999 - max. 9999) and confirm it with the
ENTER key.
A request is made to introduce the time for activating the second
output enabled in set-up (max. 60.00 seconds).
The operator can introduce its value and confirm with ENTER.
Example with set-up parameter "FU3" set on "3" when parameter
"Ab" is set on "1".
The current quota 3 (flashing) is displayed.
The operator can introduce the quota relative to the third output
enabled in set-up (min. -9999 - max. 9999) and confirm it with
ENTER.
A request is made to introduce the delta for activating the third
output enabled in set-up (min. 0 - max. 9999).
The operator can introduce its value and confirm with ENTER.
When confirmed with ENTER the programming of the other enabled
outputs will appear.
After programming, the display will return to the display in use.
Description Keyboard Display
+ × 2 sec.
23456
2t1000
12345
= ON
34567
3d67
SET
= OFF
SET
Table of contents