QUBINO Smart meter User manual

Qubino
The INNOVATIVE and SMALLEST
Smart meter
ORDERING CODE
Z-WAVE FREQUENCY
ZMNHTD1
868,4 MHz
ZMNHTD2
921,4 MHz
ZMNHTD3
908,4 MHz
ZMNHTD4
869,0 MHz
ZMNHTD5
916,0 MHz
This Z-Wave module is used for energy
measurements in single-phase electrical power
network and can be used in residential, industrial
and utility applications. Meters measure energy
directly in 2-wire networks according to the
principle of fast sampling of voltage and current
signals. A built-in microprocessor calculates
energy, power and power factor from the
measured signals.
The module can be controlled through Z-wave
network and it acts as repeater in order to
improve range and stability of Z-wave network.
It is designed to be mounted on DIN rail.
Installation
Before the installation disconnect power
supply.
Connect the module according to electrical
diagram.
Locate the antenna far from metal elements
(as far as possible).
Do not shorten the antenna.
Danger of electrocution!
Module installation requires a great degree
of skill and may be performed only by a
qualified and licensed electrician.
Even when the module is turned off, voltage
may be present on its terminals. Any works
on configuration changes related to
connection mode or load must be always
performed by disconnected power supply
(disable the fuse).
Note!
Do not connect the module to loads exceeding
recommended values. Connect the module only
in accordance to the below diagrams. Improper
connections may be dangerous. It is
recommended to use 65 A fuses for the line
protection.
Package contents
Smart meter
Electrical diagram 230VAC
IR
IR
Notes for the diagram:
LI
Live input
NI
Neutral input
Lo
Live output
No
Neutral output
1
Input for IR external relay/Ext. relay
2
Neutral lead for input
4
Live lead for External relay output
5
Output for External relay (max. 3W)
S
Service button (used to add or
remove module from the Z-Wave
network).
LED1
Green - Power on (solid) / no ID
(blinking slow 1s) / Inc./Exc. mode
(blinking fast 0,5s)
LED2
Yellow on –output on (any) /
Yellow off –outputs off (both)
IR
Output for IR external relay
1imp/
Wh
Red - Pulse rate
Measurements
Voltage
V
Current
I
Power –Active
W
Power –Active total
kWh
Power –Reactive
var
Power –Reactive total
kvarh
Power –Apparent total
kVAh
Power Factor
PF
External relays
It is possible to connect two external relay to
Smart meter module. One controlled by built-in
optical (IR) communication port on the side,
second controlled by output on terminal 5.
Module Inclusion (Adding to Z-wave
network)
Connect module to power supply
enable add/remove mode on main controller
auto-inclusion (works for about 5 seconds
after connected to power supply) or
press service button Sfor more than 2
second
NOTE: For auto-inclusion procedure, first set
main controller into inclusion mode and then
connect module to power supply.
Module Exclusion/Reset (Removing
from Z-Wave network)
Connect module to power supply
bring module within maximum 1 meter (3 feet)
of the main controller,
enable add/remove mode on main controller
press service button Sfor more than 6
seconds.
By this function all parameters of the module are
set to default values and own ID is deleted.
If service button S is pressed more than 2 and
less than 6 seconds module is excluded, but
configuration parameters are not set to default
values.
Association
Association enables Smart meter module to
transfer commands inside Z-Wave network
directly to other Z-Wave modules.
Associated Groups:
Group 1: Lifeline group (reserved for
communication with the main controller), 1 node
allowed.
Configuration parameters
Parameter no. 7 –Input 1 switch function
selection
Available configuration parameters (data type is 1
Byte DEC):
default value 4
0 disabled
2 IR external relay control –mono stable
push button
3 IR external relay control - bi stable switch
4 External relay control –mono stable push
button
5 External relay control –bi stable switch
Parameter no. 10 - Activate / deactivate
functions ALL ON / ALL OFF
Available configuration parameters (data type is 2
Byte DEC):
default value 255
255 - ALL ON active, ALL OFF active.
0 - ALL ON is not active, ALL OFF is not
active
1 - ALL ON is not active, ALL OFF active
2 - ALL ON active, ALL OFF is not active
Smart meter module responds to commands ALL
ON/ ALL OFF that may be sent by the main
controller or by other controller belonging to the
system
Parameter no. 11 - Automatic turning off IR
external relay output after set time
When IR external relay is ON it goes
automatically OFF after time defined by this
parameter. Timer is reset to zero each time the
module receive ON command regardless from
where it comes (push button, associated module,
controller,..). Available configuration parameters
(data type is 2 Byte DEC):
default value 0
0 = Auto OFF disabled
1 –32535 = 1second –32535 seconds. Auto
OFF enabled with define time, step is 1s.
Parameter no. 12 - Automatic turning on IR
external relay output after set time
When IR external relay is OFF it goes
automatically ON after time defined by this
parameter. Timer is reset to zero each time the
module receive OFF command regardless from
where it comes (push button, associated module,
controller,..). Available configuration parameters
(data type is 2 Byte DEC):
default value 0
0 = Auto ON disabled
1 –32535 = 1second –32535 seconds. Auto
ON enabled with define time, step is 1s.
Parameter no. 13 - Automatic turning off
External relay output after set time
When External relay is ON it goes automatically
OFF after time defined by this parameter. Timer
is reset to zero each time the module receive ON
command regardless from where it comes (push
button, associated module, controller,..).
Available configuration parameters (data type is 2
Byte DEC):
default value 0
0 = Auto OFF disabled
1 –32535 = 1second –32535 seconds. Auto
OFF enabled with define time, step is 1s.
Parameter no. 14 - Automatic turning on
External relay after output set time
When External relay is OFF it goes automatically
ON after time defined by this parameter. Timer is
reset to zero each time the module receive OFF
command regardless from where it comes (push
button, associated module, controller,..).
Available configuration parameters (data type is 2
Byte DEC):
default value 0
0 = Auto ON disabled
1 –32535 = 1second –32535 seconds. Auto
ON enabled with define time, step is 1s.
Parameter no. 40 –Power reporting in Watts
on power change
Set value means percentage, set value from 0 –
100 = 0% - 100%. Available configuration
parameters (data type is 1 Byte DEC):
default value 10
0 = Reporting disabled
1 –100 = 1% - 100% Reporting enabled.
Power report is send (push) only when actual
power in Watts in real time changes for more
than set percentage comparing to previous
actual power in Watts, step is 1%.
NOTE: if power changed is less than 1W, the
report is not send (pushed), independent of
percentage set. When reporting Watts, module
will automatically reports also V (Voltage), A

(Amperes), Power factor, kVar (Reactive
Power).
Parameter no. 42 –Power reporting in Watts
by time interval
Set value means time interval (0 –32535) in
seconds, when power report is send. Available
config. parameters (data type is 2 Byte DEC):
default value 0
0 = Reporting Disabled
1 –32535 = 1 second –32535 seconds.
Reporting enabled, Power report is send with
time interval set by entered value. When
reporting Watts, module will automatically
reports also V (Voltage), A (Amperes),
Power factor, kVar (Reactive Power).
Parameter no. 45 –Reset Power counters
Available configuration parameters (data type is 1
Byte DEC):
default value 0
0 = no function
1 = reset counter 1 –KWh
2 = reset counter 2 –kVARh
4 = reset counter 3 –kVAh
15 = reset ALL counters
Parameter no. 100 –Enable / Disable
endpoints IR external relay and External relay
Enabling IR external relay and External relay or
both of them, means that endpoint (IR external
relay) and endpoint (External relay) or both will be
present on UI. Disabling them will result in hiding
endpoints according to parameter set value. Note
that hiding endpoint has no impact on its
functionality. Available configuration parameters
(data type is 1 Byte DEC):
default value 0
0 = Endpoints IR external relay and External
relay disabled
1 = Endpoints IR external relay disabled,
External relay enabled
2 = Endpoints IR external relay enabled,
External relay disabled
3 = Endpoints IR external relay and External
relay enabled
NOTE: After parameter change module has to be
re-included.
Parameter no. 130 –Serial Number
Read only. Unsigned Value (32bit)
Parameter no. 131 –Meter Software reference
Read only. Unsigned Value (16bit). 2 decimal
places.
Parameter no. 132–Meter Hardware reference
Read only. Unsigned Value (16bit), 2 decimal
places.
Parameter no. 140–Voltage U1
Read only. Unit: V. Binary Unsigned Value (24bit),
1 decimal place.
Parameter no. 141–Current I1
Read only. Unit: A. Binary Unsigned Value (24bit),
3 decimal places.
Parameter no. 142–Active Power Total (Pt)
Read only. Unit: W. Binary Signed Value (24bit),
1 decimal place.
Parameter no. 143–Reactive Power Total (Qt)
Read only. Unit: kVAR. Binary Signed value
(24bit), 1 decimal place.
Parameter no. 144–Power Factor Total (PFt)
Read only. Unsigned Value (16bit), 4 decimal
places.
Parameter no. 145–Energy Counter 1 –Active
power accumulated
Read only. Unit: Kwh. Signed Long Value (32bit),
1 decimal place.
Parameter no. 146–Energy Counter 2 –
Reactive power accumulated
Read only. Unit: kVARh. Signed Long Value
(32bit), 1 decimal place.
Parameter no. 147–Energy Counter 3 –
Apparent power accumulated
Read only. Unit: KVAh. Signed Long Value (32bit),
1 decimal place.
Technical Specifications
Main terminals (LI, NI, Lo, No)
Contacts capacity: 1.5 ... 16 (25) mm2
Connection screws: M5
Max torque: 3.5 Nm (PZ2)
Optional terminals (1,2,4,5)
Contact capacity: 0.05 ... 1 (2.5) mm2
Screws: M3
Max torque: 0.6 Nm
Measuring input:
Type (connection): single phase (1b)
Reference current (Iref): 5 A
Maximum current (Imax): 65 A
Minimum current (Imin): 0.25 A
Starting current: 20 mA
Voltage (Un): 230 V (±20 %)
Power consumption at Un: < 2W
Nominal frequency (fn): 50 and 60 Hz
Accuracy:
Active energy and power:
Standard EN 62053-21: class 1
Standard EN 50470-3: class B
Reactive energy:
Standard EN 62053-23: class 2
Optical communication:
Type: IR - used to control
BICOM432-40-IR
Input (1):
Rated voltage: 230 V (± 20%)
Input resistance: 450 kOhm
Safety:
Indoor meter: yes
Degree of pollution: 2
Protection class: II
AC voltage test: 4 kV
Installation Category: 300 Vrms cat. III
Standard: EN 50470
Ambient conditions and EMC:
According standards for indoor active energy
meters.
Temperature and climatic condition according to
EN 62052-11
Ambient conditions and Safety:
According standards for indoor active energy
meters.
Temperature and climatic condition according to
EN 62052-11
Dust/water protection: IP20
Operating temperature: -10 ... 40°C
Storage temperature: -40 ... 70°C
Enclosure material: self extinguish
complying UL94 V
Indoor meter: yes
Degree of pollution: 2
AC voltage test: 4 kV
Standard: EN 50470
Distance: up to 30 m indoors
(depending on
building materials)
Weight (with packaging): 150g (170g)
Frequency range: 868.4 MHz, Z-Wave
Installation Din rail 35mm
Dimensions (W x H x D): 36 x 90 x 64mm
Package dimensions
(W x H x D): 40 x 95 x 80mm
Colour RAL 7035
EC Directives conformity:
EC Directive on Meas. Instruments 2004/22/EC
EC Directive on EMC 2004/108/EC
EC Directive on Low Voltage 2006/95/EC
EC Directive WEEE 2002/96/EC
Dimensional drawings:
Z-Wave Device Class:
ZWAVEPLUS_INFO_REPORT_ROLE_TYPE_SLAVE_ALWAYS_0N
GENERIC_TYPE_METER
SPECIFIC_TYPE_WHOLE_HOME_METER_SIMPLE
Z-Wave Supported Command Classes:
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_ALL
COMMAND_CLASS_SWITCH_BINARY_V2
COMMAND_CLASS_METER_V4
COMMAND_CLASS_MULTI_CHANNEL_V4
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3
COMMAND_CLASS_CONFIGURATION
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V2
COMMAND_CLASS_DEVICE_RESET_LOCALLY
COMMAND_CLASS_POWERLEVEL
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V2
COMMAND_CLASS_DEVICE_RESET_LOCALLY
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY_V2
Endpoint 1 (IR external relay):
Device Class:
GENERIC_TYPE_SWITCH_BINARY
SPECIFIC_TYPE_POWER_SWITCH_BINARY
Command Classes:
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY_V2
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V2
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
Endpoint 2 (External relay):
Device Class:
GENERIC_TYPE_SWITCH_BINARY
SPECIFIC_TYPE_POWER_SWITCH_BINARY
Command Classes:
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY_V2
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V2
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
NOTE:
- Endpoints are shown/hidden by Parameter No.
100
- BASIC SET/GET on root device is mapped to
basic set/get of both endpoints.
This product can be included and operated in any
Z-Wave network with other Z-Wave certified
devices from any other manufacturers. All
constantly powered nodes in the same network
will act as repeaters regardless of the vendor in
order to increase reliability of the network.
Important disclaimer
Z-Wave wireless communication is inherently not
always 100% reliable, and as such, this product
should not be used in situations in which life
and/or valuables are solely dependent on its
function.
Warning!
Do not dispose of electrical appliances as
unsorted municipal waste, use separate collection
facilities.
Contact your local government for information
regarding the collection systems available. If
electrical appliances are disposed of in landfills or
dumps, hazardous substances can leak into the
groundwater and get into the food chain,
damaging your health and well-being. When
replacing old appliances with new once, the
retailer is legally obligated to take back your old
appliance for disposal at least for free of charge.
This user manual is subject to change and
improvement without notice.
NOTE: User manual is valid for module with SW
version S1 (SW version is part of P/N)!
Example: P/N: ZMNHTDx H1S1P1
Qubino
Goap d.o.o. Nova Gorica
Ulica Klementa Juga 007
5250 Solkan Slovenia
E-mail: info@qubino.com
Tel: +386 5 335 95 00
Web: www.qubino.com
Date: 12.11.2015
Document: Qubino_Smart
meter user manual_V1.0_eng
Other QUBINO Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Cirrus Research
Cirrus Research revo CV31A user manual

LAUREL
LAUREL LAUREATE 2 Series owner's manual

Keysight
Keysight x series Measurement guide

Agilent Technologies
Agilent Technologies U3051C Security features and volatility documentation

Leica Geosystems
Leica Geosystems DISTO E7100i manual

NanoSense
NanoSense EP5000M installation manual

Ametek
Ametek Level Mate II INSTRUCTIONS FOR INSTALLATION, OPERATION, MAINTENANCE, SERVICE AND PARTS

Unitronics electric
Unitronics electric UM2B user manual

NK
NK EmPower Oarlock user manual

SKC
SKC Leland Legacy operating instructions

Fungilab
Fungilab V-Pad instruction manual

SAT-Kabel
SAT-Kabel IRM?20 operating instructions