(Amperes), Power factor, kVar (Reactive
Power).
Parameter no. 42 –Power reporting in Watts
by time interval
Set value means time interval (0 –32535) in
seconds, when power report is send. Available
config. parameters (data type is 2 Byte DEC):
default value 0
0 = Reporting Disabled
1 –32535 = 1 second –32535 seconds.
Reporting enabled, Power report is send with
time interval set by entered value. When
reporting Watts, module will automatically
reports also V (Voltage), A (Amperes),
Power factor, kVar (Reactive Power).
Parameter no. 45 –Reset Power counters
Available configuration parameters (data type is 1
Byte DEC):
default value 0
0 = no function
1 = reset counter 1 –KWh
2 = reset counter 2 –kVARh
4 = reset counter 3 –kVAh
15 = reset ALL counters
Parameter no. 100 –Enable / Disable
endpoints IR external relay and External relay
Enabling IR external relay and External relay or
both of them, means that endpoint (IR external
relay) and endpoint (External relay) or both will be
present on UI. Disabling them will result in hiding
endpoints according to parameter set value. Note
that hiding endpoint has no impact on its
functionality. Available configuration parameters
(data type is 1 Byte DEC):
default value 0
0 = Endpoints IR external relay and External
relay disabled
1 = Endpoints IR external relay disabled,
External relay enabled
2 = Endpoints IR external relay enabled,
External relay disabled
3 = Endpoints IR external relay and External
relay enabled
NOTE: After parameter change module has to be
re-included.
Parameter no. 130 –Serial Number
Read only. Unsigned Value (32bit)
Parameter no. 131 –Meter Software reference
Read only. Unsigned Value (16bit). 2 decimal
places.
Parameter no. 132–Meter Hardware reference
Read only. Unsigned Value (16bit), 2 decimal
places.
Parameter no. 140–Voltage U1
Read only. Unit: V. Binary Unsigned Value (24bit),
1 decimal place.
Parameter no. 141–Current I1
Read only. Unit: A. Binary Unsigned Value (24bit),
3 decimal places.
Parameter no. 142–Active Power Total (Pt)
Read only. Unit: W. Binary Signed Value (24bit),
1 decimal place.
Parameter no. 143–Reactive Power Total (Qt)
Read only. Unit: kVAR. Binary Signed value
(24bit), 1 decimal place.
Parameter no. 144–Power Factor Total (PFt)
Read only. Unsigned Value (16bit), 4 decimal
places.
Parameter no. 145–Energy Counter 1 –Active
power accumulated
Read only. Unit: Kwh. Signed Long Value (32bit),
1 decimal place.
Parameter no. 146–Energy Counter 2 –
Reactive power accumulated
Read only. Unit: kVARh. Signed Long Value
(32bit), 1 decimal place.
Parameter no. 147–Energy Counter 3 –
Apparent power accumulated
Read only. Unit: KVAh. Signed Long Value (32bit),
1 decimal place.
Technical Specifications
Main terminals (LI, NI, Lo, No)
Contacts capacity: 1.5 ... 16 (25) mm2
Connection screws: M5
Max torque: 3.5 Nm (PZ2)
Optional terminals (1,2,4,5)
Contact capacity: 0.05 ... 1 (2.5) mm2
Screws: M3
Max torque: 0.6 Nm
Measuring input:
Type (connection): single phase (1b)
Reference current (Iref): 5 A
Maximum current (Imax): 65 A
Minimum current (Imin): 0.25 A
Starting current: 20 mA
Voltage (Un): 230 V (±20 %)
Power consumption at Un: < 2W
Nominal frequency (fn): 50 and 60 Hz
Accuracy:
Active energy and power:
Standard EN 62053-21: class 1
Standard EN 50470-3: class B
Reactive energy:
Standard EN 62053-23: class 2
Optical communication:
Type: IR - used to control
BICOM432-40-IR
Input (1):
Rated voltage: 230 V (± 20%)
Input resistance: 450 kOhm
Safety:
Indoor meter: yes
Degree of pollution: 2
Protection class: II
AC voltage test: 4 kV
Installation Category: 300 Vrms cat. III
Standard: EN 50470
Ambient conditions and EMC:
According standards for indoor active energy
meters.
Temperature and climatic condition according to
EN 62052-11
Ambient conditions and Safety:
According standards for indoor active energy
meters.
Temperature and climatic condition according to
EN 62052-11
Dust/water protection: IP20
Operating temperature: -10 ... 40°C
Storage temperature: -40 ... 70°C
Enclosure material: self extinguish
complying UL94 V
Indoor meter: yes
Degree of pollution: 2
AC voltage test: 4 kV
Standard: EN 50470
Distance: up to 30 m indoors
(depending on
building materials)
Weight (with packaging): 150g (170g)
Frequency range: 868.4 MHz, Z-Wave
Installation Din rail 35mm
Dimensions (W x H x D): 36 x 90 x 64mm
Package dimensions
(W x H x D): 40 x 95 x 80mm
Colour RAL 7035
EC Directives conformity:
EC Directive on Meas. Instruments 2004/22/EC
EC Directive on EMC 2004/108/EC
EC Directive on Low Voltage 2006/95/EC
EC Directive WEEE 2002/96/EC
Dimensional drawings:
Z-Wave Device Class:
ZWAVEPLUS_INFO_REPORT_ROLE_TYPE_SLAVE_ALWAYS_0N
GENERIC_TYPE_METER
SPECIFIC_TYPE_WHOLE_HOME_METER_SIMPLE
Z-Wave Supported Command Classes:
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_ALL
COMMAND_CLASS_SWITCH_BINARY_V2
COMMAND_CLASS_METER_V4
COMMAND_CLASS_MULTI_CHANNEL_V4
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3
COMMAND_CLASS_CONFIGURATION
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V2
COMMAND_CLASS_DEVICE_RESET_LOCALLY
COMMAND_CLASS_POWERLEVEL
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V2
COMMAND_CLASS_DEVICE_RESET_LOCALLY
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY_V2
Endpoint 1 (IR external relay):
Device Class:
GENERIC_TYPE_SWITCH_BINARY
SPECIFIC_TYPE_POWER_SWITCH_BINARY
Command Classes:
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY_V2
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V2
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
Endpoint 2 (External relay):
Device Class:
GENERIC_TYPE_SWITCH_BINARY
SPECIFIC_TYPE_POWER_SWITCH_BINARY
Command Classes:
COMMAND_CLASS_ZWAVEPLUS_INFO_V2
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_BINARY_V2
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V2
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3
COMMAND_CLASS_MARK
COMMAND_CLASS_BASIC
NOTE:
- Endpoints are shown/hidden by Parameter No.
100
- BASIC SET/GET on root device is mapped to
basic set/get of both endpoints.
This product can be included and operated in any
Z-Wave network with other Z-Wave certified
devices from any other manufacturers. All
constantly powered nodes in the same network
will act as repeaters regardless of the vendor in
order to increase reliability of the network.
Important disclaimer
Z-Wave wireless communication is inherently not
always 100% reliable, and as such, this product
should not be used in situations in which life
and/or valuables are solely dependent on its
function.
Warning!
Do not dispose of electrical appliances as
unsorted municipal waste, use separate collection
facilities.
Contact your local government for information
regarding the collection systems available. If
electrical appliances are disposed of in landfills or
dumps, hazardous substances can leak into the
groundwater and get into the food chain,
damaging your health and well-being. When
replacing old appliances with new once, the
retailer is legally obligated to take back your old
appliance for disposal at least for free of charge.
This user manual is subject to change and
improvement without notice.
NOTE: User manual is valid for module with SW
version S1 (SW version is part of P/N)!
Example: P/N: ZMNHTDx H1S1P1
Qubino
Goap d.o.o. Nova Gorica
Ulica Klementa Juga 007
5250 Solkan Slovenia
E-mail: info@qubino.com
Tel: +386 5 335 95 00
Web: www.qubino.com
Date: 12.11.2015
Document: Qubino_Smart
meter user manual_V1.0_eng