
4 5
3.1 LOCATION
This unit is designed for interior installa on
only and is NOT WEATHERPROOF. If the unit
is to be installed outside, it must be protect-
ed from the weather and from freezing.
3.2 OPENING THE UNIT
To remove the jacket from all models, re-
move the retaining screws on the sides and
pull the jacket forward.
3.3 MINIMUM CLEARANCES
All units require a minimum clearance of
50 mm on all sides, however, we recommend
you leave sucient clearance for servicing.
3.4 MOUNTING
The Boiling Water unit, when installed is sus-
pended from mounng screws located into
keyhole slots at the back of the unit (refer
to the dimension specicaon diagrams on
page 6 or the template on the carton). Be
sure that the mounng screws are securely
inserted into the keyhole slots. The screws
MUST be anchored in such a way, that they
will hold the weight of the unit when lled
with water (refer to the weight table on P. 8).
3.5 WATER SUPPLY CONNECTION
Mains cold water supply (refer to pressure
table on Page 8 for operang water
pressures) must be piped and connected to
the 1/2” BSP inlet ng located on the le
hand side underneath the unit. An accessible
isolang valve must be installed near the
unit.
This unit contains a strainer on the water
inlet connecon. To ensure connuing
sasfactory operaon, it is suggested that
the inlet strainer be serviced every six
months. Where poor water quality is present
it is recommended to install an addional
auxiliary lter.
For rear entry connecon, we recommend
that you use a braided exible hose with a
90° elbow for ease of connecon.
3.6 VENT/OVERFLOW CONNECTION
Connect a 15 mm (1/2”) pipe to the vent/
overow connecon (1/2” BSP). This pipe
must have a connuous fall, not exceeding
3 metres in length, or contain no more than
4 bends.
During the normal operaon of the Boiling
Water unit the vent/overow connecon
may discharge small quanes of steam
and condensate, so it is ESSENTIAL that the
drain pipe is aached to the vent/overow
connecon. This drain pipe must discharge
to waste at a point where no scald injury or
inconvenience is caused.
Ensure that the venUoverow line remains
open because the Boiling Water unit tank is
not designed to be pressurised. It is recom-
mended to install an air break in the vent/
overow drain line no more than 300 mm
from the Boiling Water unit.
3.7 DRAIN CONNECTION
There is a drain screw located on the under-
side of the unit to completely drain the tank
for servicing.
Before removing the drain screw, ensure
the appliance has been switched o and the
water is not hot enough to scald.
CAUTION
This unit is not suitable for installaon
in an area where a water jet could be used.
This unit must not be cleaned using
a water jet.
3.8 TAP OUTLET
To prevent damage during transportaon,
the tap is bubble-wrapped and placed inside
the carton.
The tap is ed to the threaded tap outlet
extension with an “o” ring seal ed and
xing screw to secure in the vercal posion.
PLEASE NOTE:
Installaon and maintenance of the Boiling
Water Unit should be carried out by
a qualied service person.
3.9 ELECTRICAL REQUIREMENTS
All models
230 Volts AC, 50HZ,
Single Phase
ELEMENT RATING
1800 Was - 2.5L
2000 Was - 5L to 10L
2400 Was - 15L
3000 Was - 25L
A exible cord complete with a plug is sup-
plied on all models. Do not loosen the cord
grip or pull excess cord into the Unit. If the
supply cord of this unit is damaged, it must
be replaced by a qualied service person.
CAUTION
THIS APPLIANCE MUST BE EARTHED
4. OPERATION
When the installaon is complete, rst turn
on the water supply and then switch on the
power, which will engage the solenoid valve
and the unit will automacally begin to ll
and the heang sequence will commence.
The water is heated in small quanes,
so boiling water is available at all mes.
The electronic control unit constantly
controls the water level and the water
temperature.
4.1 MODE 1 OPERATION
To follow through the sequence of events in
order, it is necessary that we consider the
unit is switched on for the rst me.
When the unit is switched on, the controller
scans the Level Probe condion, and having
established that, then executes a sequence
of events parcular to that mode.
1. The Controller scans the Level Probe to
establish the Level Probe condion. Both
Probes (low and high) will be found to be in
an OPEN condion i.e. no water pressent.
This then places the unit in MODE 1 condi-
on.
2. The Solenoid valve is then energised,
allowing water to enter the tank.
3. Water connues to enter the tank unl
such me as the Low Level Probe becomes
“CLOSED”, i.e. water present, up to the end
of the Low Level Probe.
4. The Solenoid Valve is then powered, stop-
ping the ow of water into the tank.
5. The Controller then steps into MODE 2
new line condion.