Radionics D9210B Specification sheet

32206C 3/97 © 1997 Radionics
D9210B Access Control Interface Module
Operation and Installation Manual
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 2
Notices
About This Manual
This manual assumes that you have basic security system installation skills such
as measuring voltages, stripping wire, making proper wire connections, and
checking phone lines. It also assumes you are familiar with the proper
installation of Radionics Control/Communicator panels and the related
programming tasks.
The material and instructions in this manual have been carefully checked for
accuracy and are presumed to be reliable. However, Radionics, Inc. assumes no
responsibility for inaccuracies and reserves the right to modify and revise this
manual without notice.
It is our goal at Radionics to always supply accurate and reliable documentation.
If a discrepancy is found in this documentation, please mail a photocopy of the
corrected material to:
Radionics, Inc.
c/o Technical Writing Department
130 Perinton Parkway
Fairport, NY 14450
FCC Notice
This equipment generates, uses and can radiate radio frequency energy. If not
installed in accordance with the manufacturer’s instructions, it may cause
interference to radio communications. It has been tested and found to comply
with the specifications in Subpart J of Part 15 of FCC Rules for Class B
Computing Devices.
If this equipment causes interference to radio or television reception –– which
can be determined by turning the equipment on and off –– the installer is
encouraged to correct the interference by one or more of the following measures:
1) Reorient the antenna of the radio/television, 2) Connect the AC transformer to
a different outlet so the control panel and radio/television are on different branch
circuits, 3) Relocate the control panel with respect to the radio/television.
If necessary, the installer should consult an experienced radio/television
technician for additional suggestions, or send for the “Interference Handbook”
prepared by the Federal Communications Commission. This booklet is available
from the U.S. Government Printing Office, Washington DC 20402, stock no. 004-
000-00450-7.
Regulatory Listings
UL 294 UL 1076 UL 609 FCC 15B
UL 365 UL 1610 UL 864 CSFM
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 3
Table of Contents
Notices................................................................................................................................................................2
About This Manual ..........................................................................................................................................2
FCC Notice......................................................................................................................................................2
Regulatory Listings..........................................................................................................................................2
Table of Contents ..............................................................................................................................................3
Tables and Figures............................................................................................................................................ 4
Introduction........................................................................................................................................................5
The D9210B Access Control Interface............................................................................................................5
Materials Included ...........................................................................................................................................6
Ordered Separately.........................................................................................................................................6
Listings and Approval Information...................................................................................................................6
Installation..........................................................................................................................................................7
Before You Begin ............................................................................................................................................7
Step 1: Mounting the Enclosure and Installing the D9210B............................................................................7
Step 2: Pulling and Marking the Wires............................................................................................................8
Step 3: Mounting ...........................................................................................................................................10
Step 4: Door Contact (Onboard) Point, Terminals 9 and 10.........................................................................10
Step 5: Door Lock, Terminals 2, 3 and 4.......................................................................................................11
Step 6: Request to Enter (RTE), Terminals 11 and 12 .................................................................................12
Step 7: Request to Exit (REX), Terminals 13 and 12....................................................................................12
Step 8: Enclosure Tamper Switch, Terminals 8 and 9..................................................................................12
Step 9: Connecting the Card Reader, Terminals 12, 14, 15, 16, 17, and 18 ................................................13
Step 10: Setting the Dipswitch and Tagging the Unit....................................................................................14
Step 11 Connecting Power and SDI, Terminals 1, 5, 6, 7, and 9..................................................................15
Step 12: Programming and Activating the D9210B.......................................................................................16
Step 13: Testing the D9210B........................................................................................................................16
Troubleshooting ..............................................................................................................................................17
Detailed System Description .......................................................................................................................... 18
Operational Primer........................................................................................................................................18
Basic Features ..............................................................................................................................................21
Displays and Reports ....................................................................................................................................21
Door Release Application ...............................................................................................................................22
D9210B Terminal Quick Reference and Electrical Specifications ..............................................................23
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 4
Tables and Figures
TABLE 1. D9210B DIAGNOSTIC AND STATUS LEDS......................................................................................5
TABLE 2. TYPICAL WIRE PLANNING CHART FOR THE D9210B....................................................................8
TABLE 3. UL LISTED COMPATIBLE READERS FOR THE D9210B...............................................................13
TABLE 4. D9210B DIP SWITCH SETTINGS ....................................................................................................14
TABLE 5. LED TROUBLESHOOTING GUIDE..................................................................................................17
TABLE 6. TERMINAL QUICK REFERENCE GUIDE AND ELECTRICAL SPECIFICATIONS..........................23
FIGURE 1. D9210B ACCESS CONTROL INTERFACE MODULE .....................................................................5
FIGURE 2. WIRING DIAGRAM FOR TYPICAL D9210B INSTALLATION..........................................................9
FIGURE 3. RELAY INSTALLATION ..................................................................................................................11
FIGURE 4. D9210B DIPSWITCH WITH FACTORY DEFAULT SETTINGS.....................................................14
FIGURE 5. POWER SUPPLY AND SDI CONNECTIONS.................................................................................15
FIGURE 6. D9210B DOOR RELEASE APPLICATION CONNECTIONS..........................................................22
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 5
Introduction
The D9210B Access Control Interface
1
PWR+
7
SDIB
6
SDIA
5
COM
8
T+
10
ZN+
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
13
REX
12
COM
11
RTE
16
DATA1
17
BUZZER
18
LED
15
DATA0
14
+5.20V
D0
READER
OPER
MON
D1
READER
1
2
3
4
5
6
ON
D9210B
Terminal
Blocks
Diagnosticand
StatusLEDs
EPROM
DIPSwitch
Relay
Figure 1. D9210B Access Control Interface Module
Terminal Blocks. The D9210B comes with three banks of terminal blocks for
connecting the D9210B to its power source, the panel and associated readers
and relays.
Relay. A removable (model D136) relay provides a dry contact single pull, double
throw output.
Dipswitch. The D9210B dipswitch has six on-off switch settings. Setting these
switches allows each unique D9210B to be programmed for a specific address.
EPROM. The D9210B is controlled by a programmable read-only memory
microprocessor.
Diagnostic and Status LEDs. The D9210B has a series of light emitting diodes
(LEDs) for identifying operational and diagnostic states. These are listed below.
LED Action State
Operational Monitor (Green) LED blinks on and off System is operational
LED is on or off (solid) System is off or not operational
D0 Reader (Green) LED rapidly blinking Card data executing
LED is off No card data is being received
D1 Reader (Yellow) LED rapidly blinking Card data executing
LED is off No card data is being sent
Table 1. D9210B Diagnostic and Status LEDs
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 6
Materials Included
Radionics ships the D9210B Access Control Interface module pre-assembled
from the factory with a power supply, in its own can, or as a unit less can. You
will receive the following parts with your package depending upon what model is
ordered, (see Ordered separately).
• D136 removable relay mounted on the board.
• Battery Leads (for the D9210BLC).
• 1K Ω1/2 watt end of line resistor.
• Literature Pack containing: D9210B Operation and Installation Manual,
D9210 Program Entry Guide, ACCESS Program Record Sheet, and Power
Supply Installation Instructions.
• Hardware pack containing: three #6x3/8 self-tapping sheet metal screws to
secure the module on the mounting skirt or the enclosure. Two strain relief
cable ties.
Ordered Separately
The D9210B Door Controller can be used with the Radionics D7412 (supports 2
doors) or D9412 (supports 8 doors) Control/Communicator security panels and
associated control keypads and access control readers. Following are the
available options.
• D9210BLC: The D9210BLC (up to 4) can be installed in the same enclosure
as the control panel using the mounting screws and fasteners. Two additional
modules can be mounted using the D136 brackets. Radionics recommends
that you use a separate power supply for the D9210Bs to isolate them from
other SDI devices.
• D9210BC: The D9210BC is a complete unit mounted on a mounting skirt,
(D9201M) with a switchable 12/24 VDC (500-1500 mA) power supply, 24
VAC/40 VA fused transformer, and (1) D9210B. It can be installed with
another D9210BLC in a single D8103, D8109 or D8108A enclosure.
• D9210B: The D9210B is mounted in a 5(W)x8(L)x3(H) enclosure and can be
mounted as a standalone unit in the field.
• Compatible Readers: Readers are not shipped with the unit (see Table 3).
Listings and Approval Information
Underwriters Laboratories (UL). The D9210B, when used with the D7412 or
D9412 panels, is listed by UL for use as part of an Access Control System;
Local, Police-Connect, Central Station, or Proprietary Burglar Alarm System; and
a Commercial Fire Alarm System. In addition to the manual, refer to the
D7412/D9412 installation documentation regarding Burglar Alarm Grades and
Fire Alarm services supported. The D9210B is a Signaling Device Subassembly
also suitable as a Burglar Alarm Unit Accessory Subassembly and Access
Control Unit Subassembly.
Other Listings and Approvals. FCC 15B, CSFM (highrise)
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 7
Installation
Before You Begin
Thank you for choosing our product. We have made an effort to identify the key
steps for installing the D9210B successfully. To ensure that your installation
goes smoothly, follow the installation steps in the order presented.
System Planning. Before proceeding, draw your system layout on a sheet of
graph paper. Also, review the architect and engineering drawings (if available).
This will help you set addresses, mark the units, and route/tag wires. The
drawing should include the Control Panel, the D9210B, the trip switches for
RTE/REX, doors, readers, control centers assigned to the same area as the
D9210Bs, and the wiring run.
Have the following documents handy as you read through this manual:
• D9210B Program Entry Guide (32207)
• ACCESS Program Record Sheet (32208)
• Control/Communicator Program Entry Guide and Program Record Sheet
• Security System Owner’s Manual (71-06633-000)
• Power Supply Installation Instructions
You should be familiar also with the operation of the D5200 programmer or the
Remote Account Manager (R.A.M.) remote programmer.
Step 1: Mounting the Enclosure and Installing the D9210B
Enclosure Placement. There is a 500’ maximum distance allowed between the
D9210B and Weigand card readers. There is a 5000’ maximum distance allowed
between the D9210B and the panel. Consider placing the enclosure where a
technician can gain easy access for troubleshooting the unit and where wiring
can be routed easily.
Preparing Knockouts. The D9210B requires six primary wire runs to be routed to
the enclosure (see Table 2). To identify the proper knockouts required,
determine from which direction the panel, reader, door contact, door strike and
the request to exit/enter wires will be coming. Run the necessary wiring
throughout the premises and pull the wires into the enclosure. Avoid splicing and
grouping wires together. Knock out the tabs for the wiring prior to mounting the
enclosure.
Mounting the Enclosure. When mounting the enclosure, place it against the wall
and use a “level tool” to ensure the unit is level. Align the enclosure mounting
holes with the vertical wood beams, usually 16” apart, to ensure a solid mount.
With a pen or pencil, make marks where the top mounting holes expose the
surface.
Set the enclosure down and insert the mounting screws where the marks exist
for the top left and right mounting holes. Leave a 1/4” gap between the wall and
screw head so the enclosure can be hung on the screws.
IMPORTANT! If vertical wood beams are not available, be sure to use the proper
screw anchors and hardware to mount the unit.
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 8
If any of the knockouts require that wire be run behind the wall, mark the holes
and punch/drill them out prior to permanently installing the enclosure. After the
holes have been knocked out and the enclosure is level, use all five mounting
holes (three on the top and two on the bottom) to install the enclosure.
Step 2: Pulling and Marking the Wires
Running wire. Use Table 2 to estimate the wire bundle size for your knockouts
and where to mount the D9210B. Tag your wire runs to prevent confusion during
installation and troubleshooting. Figure 2 shows the wiring for a typical D9210B
installation.
Purpose Suggested
Wire Tag Approximate
Diameter Recommended
Wire Type Recommended
Color Code
Power/SDI data Tag A 1/4 “ 4/22 awg quad
(2500 feet)
4/18 awg quad
(5000 feet)
SDI: A (Green)
B (Yellow)
Pwr: + (Red)
- (Black)
RTE power/input* Tag B 1/4” 4/22 awg quad Green/Black
REX power/input* Tag C 1/4” 4/22 awg quad Yellow/Black
Strike power* Tag D 3/8” 2/16-18 awg zip Red
Door contact* Tag E 1/8” 2/22 awg twist White
Reader* Tag F 3/8” 6/22 awg
conductor
(500 feet)
12 VDC: Red
5 VDC: Orange
COM: Black
D1: White
D0: Green
LED: Brown
Buzzer: Yellow
Buzzer* Tag G 1/8” 2/22 awg twist +(Red), - (Blk)
Emergency Exit* Tag I 1/8” 2/18 awg twist Blue
Power Supply
Transformer Tag J 1/4” 2/18 awg zip Brown
* Be sure to multiply the wires by the number of D9210Bs in the enclosure.
Table 2. Typical Wire Planning Chart for the D9210B
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 9
1
PWR+
7
SDIB
6
SDIA
5
COM
8
T+
10
ZN+
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
13
REX
12
COM
11
RTE
16
DATA1
17
BUZZER
18
LED
15
DATA0
14
+5.20V
D0
READER
OPER
MON
D1
READER
1
2
3
4
5
6
ON
D9210
DOOR
DOORCONTACT
(NORMALE.O.L.
INCIRCUIT)
1K
E.O.L.
RTE/REX
(NORMAL
OPEN)
(white)
(green)
(orange)
(brown)
12 VDC
BUZZER
12 VDCREADER
(+)
(-)
(yellow)
TAMPERSWITCH
(NORMALOPEN)
(black)
12 VDC
DOOR
STRIKE
Somejurisdictionswill not
allowthe useofEmergencyEgress as
yoursolemeansofescape.Ifthis
featureisused,itstill maybe necessary
toprovide listed panichardware.
Consultyourlocalauthorityhaving
jurisdiction (AHJ)priortoinstallation.
CAUTION
DONOTpowerthe
D9210 Module
with24 VDC.
CAUTION
Strike and
D9210
NOTE:A24VDC powersupplymaybe used forthe door
strikeifneccessary.
Figure 2. Wiring Diagram for Typical D9210B Installation
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 10
Step 3: Mounting
CAUTION Do not install or replace a D9210B while it is connected to live power
circuits. The D9210B should be powered down until it is ready to be tested.
D9210BLC
1. Mount the D8103, D8109 or D8108A enclosure on a flat service.
2. Install another D9210LC to the mounting skirt (optional) prior to step 3.
3. Hang the mounting skirt in the enclosure by aligning the rectangular tabs of
the enclosure with the rectangular knockouts on the mounting skirt.
4. Insert the #6x3/8” screw on the bottom tab of the mounting skirt and tighten
1/4 turn to seat it. This completes the mounting of the skirt in the enclosure.
D9210B
1. Remove the cover of the D9210B by loosening the two cover screws.
2. Remove the required knockouts prior to replacing the cover.
3. Mark the holes provided for mounting the bottom half of the unit to a wall or
ceiling.
4. Screw the provided screws in to the marked service and allow a 1/4” gap
between the surface and bottom of the screw.
5. Hang the unit and secure the screws. Replace the cover and cover screws.
D9210BLC
1. The unit can be installed in a D8103, D8109 or D8108A enclosure by
matching the three plastic mounting anchors to the three hole foot prints
provided around the sides of the enclosure (4).
2. The unit can be added to a D9210BC by matching the three plastic mount
anchors to the available three hole foot prints below the factory installed
D9210B.
3. To secure the unit, use the three #8-3/4” screws provided.
Step 4: Door Contact (Onboard) Point, Terminals 9 and 10
Description. The D9210B monitors the sensor loop between the input terminal
10 and the common terminal 9 for normal, shorted, or open conditions. This loop
is provided for a door contact. The door contact can be programmed as a
perimeter, interior, or 24 hour burglar alarm point.
See the D9210B Program Entry Guide (32207) for assigning a point to the door
controller and the panel Program Entry Guide for the point types.
Point Sensor Loop. Install a 1k Ωresistor at the door contact, not at the
terminal of the input. This will provide supervision against grounds on the loop.
You can connect only one contact, that being the door, to this input.
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 11
Point Tolerances. The following voltages determine the condition of the on-
board point. Use the point common as your (-) reference when measuring the
point (+). Set your meter for 10 to 24 VDC range.
Open Loop =Greater than 8.7 VDC, but less than 13.8 VDC. (open
wire, e.o.l. resistor not in circuit)
Normal Loop =Greater than 3.9 VDC, but less than 5.8 VDC. (e.o.l
resistor in circuit)
Shorted Loop =Greater than 3.0 VDC, but less than 2.0 VDC. (wire to
wire short, e.o.l. resistor not in circuit)
Step 5: Door Lock, Terminals 2, 3 and 4
Description. A removable relay (model D136) provides a dry contact single pull
double throw output. Some strikes require a closed circuit to unlock the door
while others require an open circuit to unlock the door. The relay will support 12
VDC @ 2A or 24 VDC @ 2.5 A or 12/24VAC @ 40 VA.
Common Input (3) =This terminal will be used for the input to power
the strike. Use the (+) side of the power to the
strike via this input. Connect the (-) side directly
to the strike.
Lock N/C (2) =Provides Input power to device with relay de-
energized.
Lock N/O (4) =Provides Input power to device with relay
energized.
Relay Installation. The D136 Relay is installed into the relay socket of the
D9210B. Follow these steps for installing the relay:
1. Locate the relay socket on the D9210B board (shown in Figure 3).
2. Place the relay into the socket. The plug-in relay has two legs on the bottom
and three legs on the top. When inserting the relay, ensure that it is oriented
as shown in Figure 3.
Figure 3. Relay Installation
1
PWR+
7
SDIB
6
SDIA
5
COM
8
T+
10
ZN+
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
1
1
O
N
D9210B
MANUFACTURER
NAME
MANUFACTURER
NAME
D9210B
TOP
L
E
F
T
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 12
Step 6: Request to Enter (RTE), Terminals 11 and 12
Description. When terminal 11 is momentarily shorted to terminal 12, the strike
is activated and the door point is shunted.
Shunt Only: An option is provided that only shunts the point when this input is
momentarily shorted. To activate the shunt, but not the strike, program RTE
Shunt Only? as YES.
Step 7: Request to Exit (REX), Terminals 13 and 12
Description. When terminal 13 is momentarily shorted to terminal 12, the strike
is activated and the door point is shunted.
Shunt Only: An option is provided that only shunts the point when this input is
momentarily shorted. To activate the shunt, but not the strike, program REX
Shunt Only? as YES.
IMPORTANT: REX must not be used for emergency exit applications. NFPA 101
requires that a UL listed panic device be used to provide direct power from the
standby power source. (see Figure 2 for wiring an emergency exit device).
Check with your local Authority Having Jurisdiction (AHJ) prior to installing your
system.
Step 8: Enclosure Tamper Switch, Terminals 8 and 9
Description. A short to this loop will generate a Missing Trouble Point ### for
the point number assigned to the D9210B. With this tamper point faulted, the
D9210B will still function.
Connect a N/O tamper switch to terminals 8 and 9. Upon opening the enclosure,
the tamper switch will short the inputs and generate the Missing Trouble Point
message.
TROUBLESHOOTING TIP: SDI FAILURE ### and MISSING PT ### are
reported to the central station when the SDI bus has failed or the D9210B is
missing.
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 13
Step 9: Connecting the Card Reader, Terminals 12, 14, 15, 16, 17, and 18
Description. These terminals provide connection for a standard 26-bit
Wiegand™ reader.
Compatible Readers: Table 3 specifies the UL listed Wiegand™ readers and
associated tokens that are compatible with the D9210B. Radionics guarantees
only these readers will function properly and only the readers noted below can
be used in UL certified systems.
Model Voltage Description Tokens Cards Format
D8201/
D8201W+12 @35 mA Proximity, Low Profile,
Black or White (W) D8238 proximity D8239 proximity 26-bit
D8203/
D8203W+12 @35 mA Mullion Proximity, Black
or White (W) D8238 proximity D8239 proximity 26-bit
D8227 +5 @35 mA Insert, Magnetic Stripe N/A D8230/D8240 magnetic stripe 26-bit
D8221 +5 @25 mA Swipe N/A D8231 sealed magnetic 26-bit
D8223* +12 @175 mA Proximity, Gray N/A D8236 proximity cards 26-bit
D8224 +5 @80 mA Proximity, slim, Gray N/A D8236 proximity cards 26-bit
D8229 +5 @120 mA Keypad reader N/A N/A 26-bit
* 12 V power from D9210B source
Table 3. UL Listed Compatible Readers for the D9210B
Readers can be mounted up to 500’ from the D9210B module. A typical reader
connection is shown in Figure 2.
Terminal 1, +12 VDC. The red wire is used to provide 12 VDC readers with
power. Current is limited only by the source providing the power.
Terminal 12, Common. The black wire provides the common for the reader.
(Use this terminal when comparing other reader voltages.)
Terminal 14, +5.25V. The orange wire is used to provide 5 VDC readers with
power.
Terminal 15, Data 0. The green wire is the carrier of binary one (1) pulses from
the reader.
Terminal 16, Data 1. The white wire is the carrier of binary zero (0) pulses from
the reader.
Terminal 17, Buzzer. The yellow wire is the common for the reader buzzer or
external buzzer.
Terminal 18, LED. The brown wire is the common for the reader LED. (Note:
The reader buzzer or common for the external buzzer can be used here as in
option).
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 14
Step 10: Setting the Dipswitch and Tagging the Unit
The D9412 panel supports up to eight door controllers using all eight address
settings. The D7412 supports up to two door controllers using the first two
address settings. Each D9210B uses one of eight addresses. Addresses can
not be duplicated. Because the D9210B is always supervised, two D9210B
modules having the same address will not function and SDI failures will occur.
Fill out the Program Record Sheet. Be sure the program record sheet for this
door controller contains the area assignment, address assignment and control
center assignment.
TECH TIP: Whenever possible, be consistent when numbering doors, control
centers, and areas. This will help when programming a system with more than
one door. (Example: Assign Door 1 to Area 1 and Control Center 1.)
The D9210B dipswitch with factory default
settings (all ON) is shown in Figure 4. Table 4
shows the serial device reporting address
settings for each door controller. Table 4 also
shows dipswitch settings for Test and Fail
modes.
Door Controller Address Fail
Mode Test
Mode Memory
Dump
1 2 3 4 5* 6*
Serial Device
Control Center
Display Central Station
Modem IIIa2
D9210 #1 SDI #33 ON ON ON --- --- ---
D9210 #2 SDI #34 OFF ON ON --- --- ---
D9210 #3 SDI #35 ON OFF ON --- --- ---
D9210 #4 SDI #36 OFF OFF ON --- --- ---
D9210 #5 SDI #37 ON ON OFF --- --- ---
D9210 #6 SDI #38 OFF ON OFF --- --- ---
D9210 #7 SDI #39 ON OFF OFF --- --- ---
D9210 #8 SDI #40 OFF OFF OFF --- --- ---
SDI Fail Mode
SDI Fail – Door Unlocked --- --- --- ON --- ---
SDI Fail – Door Locked --- --- --- OFF --- ---
* Switches 5 and 6 must stay in the “ON” position.
Table 4. D9210B Dipswitch Settings
Figure 4. D9210B DIP Switch
(Factory Settings)
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 15
Step 11 Connecting Power and SDI, Terminals 1, 5, 6, 7, and 9
CAUTION: Do not connect 24 VDC or non-isolated [from the strike] 12/24 VAC
of the D9210B.
Reference Figure 5 for the following connections.
Terminal 1, Pwr +12 VDC IN. The red wire provides power to the D9210B, 12
VDC readers and buzzers.
Terminal 5, Common. The black conductor provides electrical common
between the D9210B and the power source.
Technical Tip: IMPORTANT! Always ensure a common exist from the D9210B to
the panel so the power supply and panel have the same ground reference. Use
any common terminal on the D9210B, 5, 9 and 12 for connections.
Terminal 6, SDI A PANEL DATA (INPUT). The yellow conductor from the panel
connected to this terminal. This is where data from the panel is received by the
D9210B.
Terminal 7, SDI B PANEL DATA IN (RETURN). The green conductor from the
panel is connected to this terminal. This is where the data from the D9210B is
returned back to the panel.
Terminal 3, LCKCOM. For 24VDC strikes provide the input power here from the
power supply. For 12 VDC strikes, provide the input power here from the power
supply.
1
PWR+
7
SDIB
6
SDIA
5
COM
8
T+
10
ZN+
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
TECHNICAL TIP: It is very important to include your strike current. Radionics recommends you use an
auxiliary power supply to isolate door controls and ensure the integrity of the system.
Figure 5. Power Supply and SDI Connections
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 16
Step 12: Programming and Activating the D9210B
Description. The D9210B needs to be assigned with an area before it will
communicate properly with the panel. In addition, the dipswitch settings and the
power need to be connected.
The dipswitch settings in Table 4 determine the address of the D9210B. At the
top of the ACCESS program record sheet, the address number (noted next to
the dipswitch setting in Figure 4) will determine which parameters for the door
controller are sent.
To activate the D9210B, follow the instructions in the D9210B Program Entry
Guide (32207). Use the ACCESS Program Record Sheet (32208) to match the
door to the proper address and to ensure that the door is assigned to the proper
area.
Step 13: Testing the D9210B
Description. The D9210B comes shipped with a default program that will let you
run a quick test upon installing the unit. Go through the following items to verify
the D9210B is functioning properly. If you have problems, see the trouble
shooting section.
D9210B: Verify that the Operational Monitor LED is pulsing approximately once
every second. This indicates the microprocessor is running. Go to the [UNLOCK
DOOR] function. A number from 1 to 8 should appear for the door controller. If
an “F” appears, the unit has failed.
Zone: Using the Control Center, verify the point is normal when the door is
closed, the point goes off normal when the door is opened and a shunt is not
applied, and that the point stays normal upon opening the door on a valid access
granted.
Strike: Read a valid token to activate the strike. If tokens have not been added,
use the [DOOR CONTROL], [DOOR UNLOCK] mode to cycle the strike. In
addition, you will cycle the strike when you test the RTE/REX inputs (if shunt only
is not yes).
RTE/REX: Fault these inputs to activate the strike. The default for the strike time
is 10 seconds. Test each separately.
Buzzer: The buzzer should have sounded on each strike activation. Also hold
the door open past the normal shunt time and ensure the “Extend Buzz”
functions.
Reader: The reader LED will be red upon powering up the D9210B. During the
above tests, it will turn green anytime the strike is activated.
To verify the reader, check and see that the D1 and D0 LED’s blink rapidly while
a card is passed through the reader or a token is held up to the proximity reader.
For other LED functionality, see Table 5, “LED Troubleshooting” .
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 17
Troubleshooting
LED TROUBLESHOOTING. Use the following reader and D9210B LED patterns
to troubleshoot the D9210B. It is important to use the [DOOR CONTROL]
function to validate actual door states when troubleshooting.
Reader Action If Reader LED is then Door State is so LED will toggle
Idle reader LED Red Locked
Red Secured
Green Held Open
Continuous Red/Green Locked on Fail
(Dipswitch optional)
Unlocked on Fail
(Dipswitch optional)
SDI disconnected,
D9210B is not
programmed with an
area, D9210B faulty.
Access Granted Red: Valid token to
activate strike. Locked Red to Green for
duration of strike time.
Green: Valid token will
not activate strike
because strike is latched
to allow access.
Held Open Green to Red to Green
Access Denied Red: Valid token format
not added. Locked Red to Green to Red
(pattern repeats twice)
Red: Valid token but
level is turned off. Locked Red to Green to Red
(pattern repeats twice)
Red: No access allowed
regardless of level
because door is secured.
Secured Red to Green to Red
(pattern repeats three
times)
Custom Function Red: Valid token will run. Locked/Secured Red to 1 second Green
to Red
Green: Valid token will
run. Held Open Green to 1 second Red
to Green
Adding IDs Red: Adding new token Learn Mode while door
is secured or locked. Red to 2 second Green
back to Red
Red: Adding token that
exists. Learn Mode while door
is secured or locked. Red to Green to Red to
Green to Red
Green: Adding token that
exists. Learn Mode while door
is held open. Green to 1 second Red
to Green
Green: Adding new
token Learn Mode while door
is held open. Green to 2 second Red
to Green
Table 5. LED Troubleshooting Guide
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 18
Detailed System Description
Operational Primer
The D9210B is a fully supervised, addressable SDI bus device that allows
access control integration for the D9412 (8 doors) and D7412 (2 doors) panels.
Each D9210B can store up to 986 user tokens (300 tokens for D7412), each with
a different access level for each door. Authority for access is controlled by the
level of the user, the time of day, the state of the door and the armed state of the
area that the D9210B is assigned to. Each of the authority restrictions can be
controlled through automatic and manual functions.
Users can be added to the system either by local programming using the D5200,
remote programming using the Remote Account Manager (R.A.M.), or by adding
tokens using the Add User function through the control center(s).
The D9210B is not programmed using a local or remote programmer. The
D9210B must be connected to the SDI bus to function properly and receive
operational programming parameters and user data.
Outputs.
Dry contact SPDT relay for 12/24 volt strikes. The D136 removable relay
provides a Normally Closed (NC), Common (Input voltage) and Normally Open
(NO) output. When the relay is energized, the outputs switch to an opposite
state.
Buzzer Output. The buzzer output activates when the door sequence begins or if
the door is left open for an extended period of time. It provides common to the
negative side of the buzzer.
+5 VDC reader output. The +5 volt DC output is for ID readers that require a
lower voltage than the +12 VDC readers. It provides a maximum of 150 mA.
Inputs.
SDI input and output. SDI A (yellow) receives data from the SDI A of the panel.
SDI B (green) returns data to the SDI B of the panel.
12 VDC input. This input is used to power the D9210B and provides a
connection for the 12 VDC reader and 12 VDC buzzer.
Supervised zone input for the door contact. The zone input on the D9210B is
used for the door contact that is physically mounted on the door to which the
strike is connected.
The input can be configured for shorts/opens on faults but is normal only when
the 1000k ohm resistor is in the circuit.
Unsupervised tamper input. The unsupervised tamper input is normal when
open. Upon a short, the point number assigned to the supervised zone is
reported as a MISSING PT### report.
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 19
Unsupervised Request to Enter (RTE) and Request to Exit (REX) inputs. The
RTE input and REX input are normally open inputs sharing the same common
terminal. When momentarily shorted (500 ms) by a dry contact input will initiate
the door sequence. Typical applications include a N/O momentary push button
or a N/O momentary relay activation from a Door motion detector device.
The REX input generates the Door Request to Exit and is used to exit the area
assigned to the D9210B without having to use an ID. The RTE generates the
Door Request to Enter and is used to enter the area assigned to the D9210B.
Programming REX Shunt Only and RTE Shunt Only allows you to initiate only
the shunt and buzz when the RTE or REX inputs are shorted. This eliminates the
need for a strike and would be used in applications where a push bar is used to
open the door.
It is advisable to assign a point number to the device used to activate the RTE
and REX inputs (such as an infrared with addressable ZONEX). This ensures
that the device is supervised.
Unsupervised reader. The Weigand Reader input is a five wire input that
supplies +5 VDC (use the +12 VDC terminal for 12volt readers), negative,
ground activation for the reader LED, (D1) and (D0) inputs for the card data.
Two LEDs are provided to indicate that data is reaching the inputs from the
reader when an ID is read. The IDs do not have to be valid to illuminate these
LEDs, but the IDs do need to have a format that the reader can decipher.
Normal Door Sequence. The Normal Door Sequence of the D9210B is initiated
by a valid access granted (User ID) or door request (RTE/REX). This initiates the
strike, shunt and buzz time to activate the strike, shunt the point and create an
event reporting the door sequence has begun.
When the door is held open past the normal door sequence time, an extended
door sequence time is initiated. This extended time extends the shunt and re-
activates the buzzer. If programmed, [ CLOSE DOOR # ] will display at the
control center assigned to the door.
The normal door sequence will not activate if the interlock point is in an off
normal (open or short) condition.
The INTERLOCK POINT can be assigned to multiple door controllers. This is
useful for applications that require doors to not activate when a point is faulted
until the interlock point is normal.
Door States. There are four door states for the D9210B. These door states can
be controlled through the control center, the Remote Account Manager (R.A.M.),
scheduled events (Skeds) and automatic programmable functions in the D9210B
parameters.
Locked Door. This state is considered a normal door state in that the strike is
holding the door closed.
Unlock Door. This state allows the door to be opened for free access.
Secure Door. This state will not allow access unless a Fire Unlock occurs.
www.PDF-Zoo.com
firealarmresources.com

32206C 3/97 D9210B Operation & Installation Manual © 1997 Radionics
Page 20
Fire Unlock. This state allows free access no matter what the previous door state
or armed state is. This is a programmable option that can be used to allow free
access into the building upon a fire alarm.
Automatic Functions and Door State. The D9210B has two automatic
functions that control door state based on the armed state of the area:
Auto Door. With this function as Yes, the door will be locked when the area is
armed and unlocked when the area is disarmed. Perimeter armed is considered
an armed state for this function.
Disarm on Open. With this function as Yes, a user with valid access rights will
activate the strike and disarm the system after the door is opened. With this
function as no, the area will disarm upon the strike activation.
Access Levels
Armed State rights Users can be prevented from access depending upon the
armed state of the area that the D9210B is assigned to. M-indicates the user has
access no matter what the armed state, P- indicates the user has access as long
as the Area is perimeter armed or disarmed and D-indicates the user only has
access when the area is completely disarmed.
Disarm Access Level. Users are allowed to disarm the area with an access id.
Care should be taken to ensure that the user first has the authority to activate the
strike based on the Armed State. P-indicates the user will disarm the area from
Master to Perimeter Instant. D- indicates the user will disarm the area from
Master or Perimeter to the disarmed state.
Skeds
Unlock Door . Provides an automatic free access at a specific time period.
Requires a Normal Door Sked to return the door to normal. Can be overridden by
manual control at the control center.
Secure Door. Provides an automatic prevention of access at a specific time
period. Requires a Normal Door Sked to return to normal. Can be overridden by
manual control at the control center.
Lock Door. Provides an automatic lock door state at a specific time to return the
door to normal requiring valid cards/tokens to allow access.
Message Suppression. Provides an automatic message off/on function at a
specific time for Door and Access Granted or No Entry messages.
Access Ctl Level On/Off. Provides an automatic on/off for each of the 14 levels
dealing with the access control. Once a level is turned off, all doors are affected.
Modular Design. The D9210B can be replaced by simply disconnecting the
existing unit and connecting a new one with the same dipswitch setting. The
panel will download stored data to the new unit when it is powered up and
connected to the SDI bus.
Diagnostics. Patterns of LED activation will indicate door state and ID validity.
Other indications include SDI failure. (see Table 5, LED Trouble Shooting
Guide).
www.PDF-Zoo.com
firealarmresources.com
Other manuals for D9210B
1
Table of contents
Other Radionics Recording Equipment manuals
Popular Recording Equipment manuals by other brands

Gemini
Gemini UX-1610 Operation manual

IntesisBox
IntesisBox MH-RC-WMP-1 installation manual

myMix
myMix Networkable personal audio mixing and recording... owner's manual

TC Electronic
TC Electronic 2290 P DYNAMIC DIGITAL DELAY quick start guide

Viking
Viking FXI-1 Technical practice

Mitsubishi Electric
Mitsubishi Electric PAC-IF011B-E installation manual

Nav TV
Nav TV BMW-EVO ID6 Install manual

AND
AND HVW-27C instruction manual

MICRO-EPSILON
MICRO-EPSILON IF2035 Assembly instructions

W&T Electronics
W&T Electronics 34201 Manual handbook

Littfinski Daten Technik
Littfinski Daten Technik Interface s88 Assembly instruction

Anritsu
Anritsu MG3710A Configuration guide