
Supplied By www.heating spares.co Tel. 0161 620 6677
A smaller size than the boiler inlet
gas connection should not be used The
complete installation must be tested for
soundness as described in the above Code
N B: if the gas supply for the boiler serves
other appliances ensure an adequate
supply is available both to the boiler and the
other appliances when they are in use at
the same time.
4.6 FLUE SYSTEM
4.4.1 The terminal should be located where dis-
persal of combustion products is not imped-
ed and with due regard for the damage or
discolouration that might occur to building
products in the vicinity (see fig 6) The terminal
must not be located in a place where it is
likely to cause a nuisance In cold and/or
humid weather water vapour may condense
on leaving the flue terminal The effect of such
steaming must be considered.
The terminal must not be closer than 25 mm (1
in) to any combustible material For protection
of combustibles, refer to BS 5440.1.
Where a flue terminal is installed less than
1000 mm from a plastic, or painted gutter, or
500 mm from painted eaves, an aluminium
shield 1000 mm long, should be fitted to the
underside of the gutter or painted surface
Pluming will occur at the terminal so, where
possible, terminal positions which could
cause a nuisance should be avoided The
flue must be installed in accordance with the
recommendations of BS 5440.Part 1.
IMPORTANT:Thefollowingnotesareintended
for general guidance.
The boiler MUST be installed so that the
terminal is exposed to external air.
It is important that the position of the terminal
allows the free passage of air across it at all
times.
Minimum acceptable spacing from the ter-
minal to obstructions and ventilation opening
are specified in Fig.6
Note positions: Due to the terminal design,
installation is possible with clearances less
than those specified in BS 5440, Part .1.
IMPORTANT NOTES
For greater flue lengths see twin flue
Instructions.
Flue must be positioned in a place not likely
to cause a nuisance.
18 inches (450 mm) in front
5 inches (125 mm) above
6 inches (150 mm) below
0 2 inches (5 mm) on each side
1 inch (25 mm) in front when installed in
a cupboard
4.4 IMPORTANT NOTICE
4.4.1 If the boiler is to be fitted in a timber
framed building it should be fitted
in accordance with the British Gas
Publication Guide for Gas Installations
in Timber Frame Housing Reference
DM2. If in doubt advice must be
sought from the local gas supplier
The boiler may be installed in any room
or internal space, although particular
attention is drawn to the requirements of
thecurrentI.E.EWiringRegulations,and
in Scotland the electrical provisions of-
the Building Regulations applicable in
Scotland, with respect to the installation
of the combination boiler in a room or
internalspacecontaining abathorshower
Where a room sealed appliance is
installed in a room containing a bath or
shower, any electrical switch or appliance
control, utilising mains electricity should
be so situated that it cannot be touched by
a person using a bath or shower.
Acompartmentusedtoenclosetheboiler
MUSTbedesignedandconstructedspecif-
icallyforthispurposeanexistingcupboard,
or compartment, may be used provided it
is modified accordingly. Samples of the
CSI boiler have been examined by BG
Technology Notified Body, and is certified
to comply with the essential requirements
of the Gas Appliance Directive 90/396/
EEC, the Low Voltage Directive 72/23/
EEC and shows compliance with the
Electra Magnetic Compatibility Directive
89/336/EEC and are therefore permitted
to carry the CE Mark .
The appliance has been tested and
approved by the WRc as meeting
the requirements of G3 and L of the
Building regulations and water Bylaws
Scheme- Approved Products.
4.5 GAS SUPPLY
4.5.1 A gas meter is connected to the
service pipe by the Local Gas Region
or the Local Gas Region contractor
An existing meter should be checked
preferably by the Gas Region to ensure
that the meter is adequate to deal with
the rate of gas supply required for all
appliances it serves Installation pipes
should be fitted in accordance with BS
6891 Pipework from the meter to the boiler
must be of adequate size (22 mm) min To
within at least 3 metre of the boiler (15
mm) min can then be used for remaining
pipe work to the appliance.
10