Rotary Gas Meter
RRM G010/G016/G025/G040/G65
DN050 Class 150 FF
PRECAUTIONS
medium:
Natural gas (CH4) - gas family Group 1
operating conditions: p = 0 - 20 barg / t = -25 - 70 °C
mechanical class: M2 - electromagnetic class: E1
Meter can be installed in open air.
Avoid direct sunshine on the meter.
IP-classification of index: IP67
Never use the meter as a spool piece during elding.
The meter must be depressurised before filling or adding oil.
Before removing the meter, the oil should be drained.
The meter should be transported and stored ith the rotor axis horizontal.
Use only devices ith electrical characteristics as recommended (see connection diagram)
The maximum tightening torque on the Pressure and Temperature tapping connections is: 18 Nm
To tighten the s ivel nuts; use 2 renches to avoid over tighten and damage the meter body.
Avoid mechanical shock during handling and transportation of the meter.
Avoid strong magnet fields close to the meter (particular the index), since they can affect the metrological
performance and/or interrupt the pulse generators.
Seal all plugs and sight glasses to overcome fraud and/or theft of gas.
INSTALLATION INSTRUCTIONS
1
Check the meter for damage due to transportation and handling. Insure the impellers turn freely and no objects
or contaminations are in the measuring chamber.
2
The piping on the inlet side of the meter must be clean (free of dirt, elding beads and pipe scale). It is recommended to
install a 100 micron filter upstream of the meter. For ne installations it is recommended to install a mesh ire screen (250 micron)
for the first eeks of operation.
3
Connect the meter inlet to the gas supply side of the line, insuring the gas flo ill be in the same direction as the arro on
the meter body type plate. For P and T positions see figures belo . The pressure reference connection (Pm) is al ays located
on the INLET of the meter.
Left to Right Right to Left Top to Bottom
Pressure tapping High frequency pulser
Temperature tapping Lubrication Point
4
Install the meter ithout piping strain to prevent a binding of the impellers.
Level the meter to ithin 5mm/m side-to-side and front-to-back.