Rayleigh Instruments RI-F220 User manual

RI-F220-IM-V01
1
RI-F220-G-C
RI-F220-G-MB
RI-F220 Instrucon Manual
X 4
X 1
X 1
RTU
Pulse SO
Safety related nocaon, symbols and instrucons that appear in this
operang manual or on the equipment must be strictly followed to
ensure the safety of personnel as well as the instrument. If the
equipment is not used in a manner specied by the manufacturer it may
impair the protecon provided by the equipment
• Do not use the equipment if there are mechanical damage
• Do not exceed the stated maximum rangs of the device
• No repairs, maintenance or adjustments are possible
• Read the complete instrucon manual prior to installaon or
operang the unit
• The equipment in its installed state must not come into close
proximity to any heang sources, oils, steam, causc vapours or
other unwanted process by-products
• Do not use in hazardous or classied locaon where explosion or
other dangers can be triggered by the device
PRODUCT SAFETY INSTALLATION PRECAUTIONS
Risk of electric shock!
Only to be installed by a competent person
• To prevent the risk of electrocuon, always isolate and lock-o the
power supply to the equipment prior to undertaking any work
• Always conrm absence of electricity prior to starng work using
appropriate voltage detecon equipment
• Wiring shall be done strictly according to the terminal layout
• Conrm that all connecons are correct before energizing the
equipment
• Roung of cables shall be way from any internal EMI source
• Copper cable should be used
• All wiring to be in accordance with applicable local standards
Specicaons Accuracy
Wiring Input 3Ø 4 wire, 3Ø 3 wire, 2Ø 3 wire, 1Ø 2 wire Voltage V L-N and V L-L±0.5% of full scale
Rated Input Voltage 3x 11...300V AC (L-N), 19...519V AC (L-L) Current ±0.5% of full scale
Frequency Range 45...65Hz Frequency for L-N >20V, L-L >35V ±0.1% of full scale
CT Primary 1A/5A...10,000A congurable Acve, Reacve and Apparent Power 1%
CT Secondary 1A or 5A (max rang x1.2) Power Factor ±0.01 of Unity
VT Primary 100...500kV congurable Acve Energy Class 1 (IEC/EN 62053-21)
VT Secondary 100...500V AC (L-L) congurable Reacve Energy Class 2 (IEC/EN 62053-23)
Auxiliary / Power consumpon 85...270V AC 45...65Hz / < 8VA
Display Update Rate 1 sec all parameters Wh Resoluon and Default Pulse Weight
Operang / Storage Temperature -10…55°C / -20…75°C Wh Resoluon and Default Pulse Weight
Example
If CT = 100/5A (CT rao = 20) & VT = 350/350V (VT Rao = 1)
Wh resoluon = 0.1kWh (20 x 1 = <150) | Pulse O/P default = 0.1kwh/pulse
Humidity 0...85% non-condensing
Protecon Degree (IEC/EN60529) IP54 Front only (rubber gasket ed)
Pulse Output External 5...27V DC / 100mA max
Pulse Resoluon / Duraon 0.01...99.99kWh per imp / 0.1...2 sec
Communicaon Modbus RTU over RS485
MBus (EN13757)
CT Rao x VT Rao <15 <150 <1500 <15k <150k ≥150k
Wh / VArh / VAh 0.01k 0.1k 1k 0.01M 0.1M 1M
INT 0.01k 0.1k 1k 0.01M 0.1M 1M
0.001k 0.01k 0.1k 1k 0.01M 0.1M
MECHANICAL INSTALLATION
Installaon & Environmental
Panel mounted, indoor used only.
Installaon category: III
Altude: up to 2000 m
Protecon Class: II
Polluon degree: II
All terminal covers must be ed aer wiring
EO&E: Document subject to change
x4

RI-F220-IM-V01
2
WIRING
Modbus / MBus
Wiring Topology
Daisy Chain Star Network
A | B
Modbus ✓
+ | -
MBus ✓✓
1 | 2
Typical Modbus
conguraon shown
For MBus interface
follow Wiring
Topology below
500m Max, ≤ 32 meters
Fuse class CC UL / fast acng 600V
Rang 0.5A
For ’Volt-free’ PLC or digital input,
voltage must be provided by the addion
of a DC PSU
Single Core
0.5 > 4mm2
Ø 2.5mm max
Stranded
0.5 > 2.5mm2+
7mm
Ø 2.5 mm
0.6 Nm
Max
3P4W
3 CTs
1P2W
1 CT
2P3W
2 CTs
2 VTs
2P3W
2 CTs
3P3W
2 CTs
2 VTs
3P3W
2 CTs
3P4W
3 CTs
3 VTs
Voltage
and current
must be
from same
phase
L1, L2 or L3
RS485 PULSE
O/P RS485 PULSE
O/P RS485 PULSE
O/P
RS485 PULSE
O/P
RS485 PULSE
O/P RS485 PULSE
O/P
RS485 PULSE
O/P
RS485 PULSE
O/P

RI-F220-IM-V01
3
F220-G-C
F220-G-MB
Seng Default Adjustment Range Network
& CT
Must
congure
VT
Adjust if
Using VT
Comms
Modbus /
MBus
Pulse O/P
Adjust if
ulised
System
Sengs
Oponal
11Change Password 1000 NO / YES (0000 - 9998) ✓
22Phase Network Selecon 3P4W 3P4W
3P3W
1P2r (Phase 1)
1P2Y (Phase 2)
1P2b (Phase 3)
✓
33CT Secondary (see CT Label) 51A / 5A ✓
44CT Primary (see CT Label) 51A/5A to 10,000A ✓
55PT Secondary 350 100V > 500V ✓
66PT Primary 350 100V > 500kV ✓
77Demand interval method Sliding Sliding / Fixed ✓
88Demand interval duraon 15 1 > 30 ✓
99Demand interval length 11 > 30 min ✓
10 10 Pulse Weight 0.10 0.01 > 99.99 kWh/imp ✓
11 11 Pulse Duraon 0.1 0.1 > 2.0 Sec ✓
12 12 Run Hour Selecon 00 > 10% ✓
13 13 Slave ID Modbus:
MBus (Primary ID):
1
1
1 > 255
1 > 250 ✓
14 14 Baud rate Modbus:
MBus:
9600
2400
300 > 19200 bps
1200 > 9600 ✓
15 15 Parity Modbus:
MBus:
None
Even
None / Odd / Even
Even ✓
16 16 Stop Bit Modbus:
MBus:
1
1
1 / 2
1✓
17 17 Back Light O (0000 = Never) 0000 0 > 7200 Sec ✓
X18 MBus Secondary ID Serial # 0000 0000 > 9999 9999 ✓
18 19 Factory Default No No / Yes Does not reset energy & demand values ✓
19 20 Reset Energy & Demand No No / Yes (Password +1) Once entered, reset each value individually ✓
CONFIGURATION
Step A: Enter Conguraon Menu Step B: Congure each seng, as required, referring to
Sengs Table below, using the buons as follow:
1Press buon once to make digit or opon ash, press
again to move ashing cursor
2Press to change digit or opon, press to move
cursor posion as required
3Press to save and move to next seng opon, Exit
menu once all sengs are congured (see Step 1)
Hold 3 Secs to
Enter Cong
(same to Exit)
Password = 1000
(Refer to Step B)
2
1

RI-F220-IM-V01
4
OPERATION
1 Funcons & displayed measurement indicators:
RS485 communicaon in progress
1,2,3 Phase L-N
12,23,13 Phase L-L
IM Imported Energy (posive value)
EP Exported Energy (negave value
Total Sum of 3-phase
DMD Max/Min Demand
TH Total Harmonic Distoron (THD)
Net Sum of 3-Phase Energy
2 Funcon buons and funcon symbols
3 Phase, total or average instantaneous measurements
(V, A, PF, Hz, kW, kVAr, kVA) >> V/I/VAF/PF/P buons
4 Accumulave Energy (kWh/kVArh/kVAh) >> E buon
No. of
Presses V/I VAF PF/P E
x1 Voltage (L-N) L1: V/A/Hz Power Factor L1 IM Acve Energy - kWh
x2 Voltage (L-L) L2: V/A/Hz L1: kW/kVAr/kVA/PF L2 IM Acve Energy - kWh
x3 Voltage THD (L-N) L3: V/A/Hz L2: kW/kVAr/kVA/PF L3 IM Acve Energy - kWh
x4 Voltage THD (L-L) Avg: V/A/PF/Hz (L-N) L3: kW/kVAr/kVA/PF L1 EP Acve Energy - kWh
x5 Current Avg: V/A/PF/Hz (L-L) ∑: kW/kVAr/kVA/PF L2 EP Acve Energy - kWh
x6 Current THD Max DMD: kW/kVAr/kVA L3 EP Acve Energy - kWh
x7 Current Max DMD Min DMD: kW/kVAr Net IM Acve Energy - kWh
Net EP Acve Energy - kWh
L-N parameters not displayed For 3P3W
Parameters in BOLD not displayed for 1P2W Net Acve Energy - kWh (IM+EP)
L1 IM Reacve Energy - kVArh
L2 IM Reacve Energy - kVArh
L3 IM Reacve Energy - kVArh
L1 EP Reacve Energy - kVArh
L2 EP Reacve Energy - kVArh
L3 EP Reacve Energy - kVArh
Net IM Reacve Energy - kVArh
Net EP Reacve Energy - kVArh
Net Reacve Energy - kVArh (IM+EP)
L1 Apparent Energy - kVAh
L2 Apparent Energy - kVAh
L3 Apparent Energy - kVAh
Net Apparent Energy - kVAh
Run Hour (0.01 hr = 36 sec)
Number of Auxiliary Switch ON
Voltage Phase Sequence
Serial Number
Page Scroll
OK-CLK = L1 → L2 → L3
ANTI-CK = Incorrect Order
INVAL Id = Missing Phase
✓
Rayleigh Instruments Limited (Head Oce)
Raytel House, Cutlers Road, South Woodham Ferrers, Chelmsford, Essex. CM3 5WA
W: www.rayleigh.com E: sales@rayleigh.com
Rayleigh Instruments Limited SP. Z o.o. (European Oce)
Ul. Aleje Jerozolimskie 214, Warsaw, Poland, 02-486
W: www.rayleigh.pl E: sales@rayleigh.pl
x8
x9
x10
x11
x12
x13
x14
x15
x16
x17
x18
x19
x20
x21
x22
x23
x24
Hold 3 sec
Hold 10 sec
de = Display Voltage Screen aer
60 sec of non-acvity
AUtO = Automac page scroll
Change every 5 sec
MAnL = Manually change page only
Hold 3 sec
Hold again to change
This manual suits for next models
2
Other Rayleigh Instruments Measuring Instrument manuals