RI-D440-IM-V02
1
RI-D440 Instrucon Manual
X 1
Safety related noficaon, symbols and instrucons that appear in this
operang manual or on the equipment must be strictly followed to
ensure the safety of personnel as well as the instrument. If the
equipment is not used in a manner specified by the manufacturer it may
impair the protecon provided by the equipment
· Do not use the equipment if there are mechanical damage
· Do not exceed the stated maximum rangs of the device
· No repairs, maintenance or adjustments are possible
· Read the complete instrucon manual prior to installaon or
operang the unit
· The equipment in its installed state must not come into close
proximity to any heang sources, oils, steam, causc vapours or
other unwanted process by-products
· Do not use in hazardous or classified locaon where explosion or
other dangers can be triggered by the device
PRODUCT SAFETY INSTALLATION PRECAUTIONS
Risk of electric shock!
Only to be installed by a competent person
· To prevent the risk of electrocuon, always isolate and lock-off the
power supply to the equipment prior to undertaking any work
· Always confirm absence of electricity prior to starng work using
appropriate voltage detecon equipment
· Wiring shall be done strictly according to the terminal layout
· Confirm that all connecons are correct before energizing the
equipment
· Roung of cables shall be way from any internal EMI source
· Copper cable should be used
· All wiring to be in accordance with applicable local standards
Specificaons Accuracy
Wiring Input 3Ø 4 wire
1Ø 2 wire - P1, P2, P3 Voltage V L-N and V L-L ±0.5% of full scale
Rated Input Voltage 3x 60...300V AC (L-N), 104..520V AC (L-L) Current ±0.5% of full scale
Frequency 45...65Hz Frequency for L-N > 20V, L-L > 35V ±0.1% of full scale
CT Primary 5...10,000A configurable Acve, Reacve and Apparent Power 1%
CT Secondary 0.01...1(1.2)A (Meter Input: 330mV) Power Factor ±0.01 of Unity
VT Primary 100V...10kV AC (L-L) configurable Acve Energy Class 1 (IEC/EN62053-21)
VT Secondary 100...500V AC (L-L) configurable Reacve Energy Class 2 (IEC/EN62053-23)
Auxiliary / Voltage Rated Burden Supplied from V1 only / < 8VA
Display Update Rate 1 sec all parameters Wh Resoluon and Default Pulse Weight
Operang / Storage Temperature -10…55°C / -20…75°C
Example
If CT Primary = 200A (CT rao = 200/1 = 200) & VT = 350/350V (VT Rao = 1)
Wh resoluon = 1kWh (200 x 1 = <1500) | Pulse O/P default = 1kWh/pulse
Humidity 0...85% non-condensing
Protecon Degree (IEC/EN60529) IP54 (front of Housing), IP20 (terminals)
Communicaon Modbus RTU over RS485
MBus (EN13757)
CT Rao x VT Rao <15 <150 <1500 <15k <150k
Wh / VAh / VArh 0.01k 0.1k 1k 0.01M 0.1M
INT 0.001k 0.01k 0.1k 1k 0.01M
DIN rail mounted, this device must be installed within a
suitable IP rated enclosure. Indoor use only.
Installaon category: III (300V L-N)
Protecon Class: II
Polluon degree: II
Altude: up to 2000 m
All terminal covers must be fied aer wiring
MECHANICAL INSTALLATION
DISMOUNT
EO&E: Document subject to change
1x 3Ø
1x 1Ø
RI-D440-G-C
RI-D440-G-MB
RTU
Pulse SO