Rayleigh Instruments RI-D440 User manual

RI-D440-IM-V02
1
RI-D440 Instrucon Manual
X 1
Safety related noficaon, symbols and instrucons that appear in this
operang manual or on the equipment must be strictly followed to
ensure the safety of personnel as well as the instrument. If the
equipment is not used in a manner specified by the manufacturer it may
impair the protecon provided by the equipment
· Do not use the equipment if there are mechanical damage
· Do not exceed the stated maximum rangs of the device
· No repairs, maintenance or adjustments are possible
· Read the complete instrucon manual prior to installaon or
operang the unit
· The equipment in its installed state must not come into close
proximity to any heang sources, oils, steam, causc vapours or
other unwanted process by-products
· Do not use in hazardous or classified locaon where explosion or
other dangers can be triggered by the device
PRODUCT SAFETY INSTALLATION PRECAUTIONS
Risk of electric shock!
Only to be installed by a competent person
· To prevent the risk of electrocuon, always isolate and lock-off the
power supply to the equipment prior to undertaking any work
· Always confirm absence of electricity prior to starng work using
appropriate voltage detecon equipment
· Wiring shall be done strictly according to the terminal layout
· Confirm that all connecons are correct before energizing the
equipment
· Roung of cables shall be way from any internal EMI source
· Copper cable should be used
· All wiring to be in accordance with applicable local standards
Specificaons Accuracy
Wiring Input 3Ø 4 wire
1Ø 2 wire - P1, P2, P3 Voltage V L-N and V L-L ±0.5% of full scale
Rated Input Voltage 3x 60...300V AC (L-N), 104..520V AC (L-L) Current ±0.5% of full scale
Frequency 45...65Hz Frequency for L-N > 20V, L-L > 35V ±0.1% of full scale
CT Primary 5...10,000A configurable Acve, Reacve and Apparent Power 1%
CT Secondary 0.01...1(1.2)A (Meter Input: 330mV) Power Factor ±0.01 of Unity
VT Primary 100V...10kV AC (L-L) configurable Acve Energy Class 1 (IEC/EN62053-21)
VT Secondary 100...500V AC (L-L) configurable Reacve Energy Class 2 (IEC/EN62053-23)
Auxiliary / Voltage Rated Burden Supplied from V1 only / < 8VA
Display Update Rate 1 sec all parameters Wh Resoluon and Default Pulse Weight
Operang / Storage Temperature -10…55°C / -20…75°C
Example
If CT Primary = 200A (CT rao = 200/1 = 200) & VT = 350/350V (VT Rao = 1)
Wh resoluon = 1kWh (200 x 1 = <1500) | Pulse O/P default = 1kWh/pulse
Humidity 0...85% non-condensing
Protecon Degree (IEC/EN60529) IP54 (front of Housing), IP20 (terminals)
Communicaon Modbus RTU over RS485
MBus (EN13757)
CT Rao x VT Rao <15 <150 <1500 <15k <150k
Wh / VAh / VArh 0.01k 0.1k 1k 0.01M 0.1M
INT 0.001k 0.01k 0.1k 1k 0.01M
DIN rail mounted, this device must be installed within a
suitable IP rated enclosure. Indoor use only.
Installaon category: III (300V L-N)
Protecon Class: II
Polluon degree: II
Altude: up to 2000 m
All terminal covers must be fied aer wiring
MECHANICAL INSTALLATION
DISMOUNT
EO&E: Document subject to change
1x 3Ø
1x 1Ø
RI-D440-G-C
RI-D440-G-MB
RTU
Pulse SO

RI-D440-IM-V02
2
1 RJ45 cable
2 Fuse class CC UL / fast acng
3 Phase 600V/Single Phase 250V
3 Supply 31 addional meters (32 total)
4 For ’Volt-free’ PLC or digital input, voltage must
be provided by the addion of a DC PSU
5 For Single Phase Easywire CT - Set Phase
Network to 1P2W-P1, Voltage Reference V1
must be same phase as CT. Connect V2/V3 to N.
WIRING
Modbus / MBus
Wiring Topology
Daisy Chain Star Network
Modbus ü û
MBus ü ü
A | B
+ | -
1 | 2
Typical Modbus
configuraon shown
For MBus interface
follow Wiring
Topology below
500m Max, ≤ 32 meters
No. Meters ≤ 5 ≤ 10 ≤ 20 ≤ 32
Fuse Rang 0.5A 1A 1.5A 2A
0.5 Nm
Max
Single Core 0.5 > 4mm2
Ø 2.5mm Max Stranded 0.5 > 2.5mm2
7mm +
Ø 2.5mm
CT phase rotaon is
RH/LH dependant
refer to Configuraon
3P4W or
1P2W P1,P2 or P3

RI-D440-IM-V02
3
D440-G-C
D440-G-MB
Seng Default Adjustment Range Network
& CT
Must
configure
VT
Adjust if
Using VT
Comms
Modbus /
MBus
Pulse O/P
Adjust if
ulised
System
Sengs
Oponal
1 1 Change Password 1000 NO / YES (0000 - 9998) ü
2 2 Phase Network Selecon 3P4W 3P4W, 1P2W-P1/P2/P3 ü
3 3 CT Secondary 1 Non-adjustable
4 4 CT Primary (see CT Label) 1 5 > 10000A ü
5 5 PT Secondary 350 100 > 500V ü
6 6 PT Primary 350 100 > 10000V ü
7 7 Slave ID Modbus:
MBus (Primary ID):
1
1
1 > 255
1 > 250 ü
8 8 Baud rate Modbus:
MBus:
9600
2400
300 > 19200 bps
1200 > 9600 ü
9 9 Parity Modbus:
MBus:
None
Even
None / Odd / Even
Even ü
10 10 Stop Bit Modbus:
MBus:
1
1
1 / 2
1 ü
11 11 Back Light Off (0000 = Never) 0000 0 > 7200 Sec ü
12 12 Demand interval method Sliding Sliding / Fixed ü
13 13 Demand interval duraon 15 1 > 30 min ü
14 14 Demand interval length 1 1 > 30 min ü
15 15 Pulse Weight 0.10 0.01 > 9.99 kWh/imp ü
16 16 Pulse Duraon 200 50 > 300 mS ü
X 17 MBus Secondary ID Serial # 0000 0000 > 9999 9999 ü
17 18 Factory Default No No / Yes Does not reset energy & demand values ü
18 19 Reset Energy & Demand No No / Yes (Password +1) Once entered, reset each value individually ü
CONFIGURATION
CT Phase Rotaon - RH or LH, check/change in normal operang mode
1. Hold 3 sec to check
2. Hold again to change
RH
LH
Step A: Enter Configuraon Menu Step B: Configure each seng, as required, referring to
Config Table below, using the buons as follow:
1 Press once to make digit or opon flash, press again to
move flashing cursor
2 Press to change digit or opon, press to move
cursor posion as required
3 Press to save and move to next seng opon, Exit
menu once all sengs are configured (see Step A)
Hold 3 Secs to
Enter Config
(same to Exit)
Password = 1000
(Refer to Step B)
2
1

RI-D440-IM-V02
4
OPERATION
1 Display Symbols:
Avg Average of 3-phase
tOt Total of 3-phase
MD Max Demand
L-N Line to Neutral
RS485 communicaon in progress
2 Measurement Units (refer to Funcons Table below)
V, kWh, kVArh, kVAh, A, Hz, kW, kVAr, kVA
3 Navigaon Buons: Change PARAMETER
Change PAGE
(hold 10 sec: Serial #)
4 Integraon of Energy Indicator (blinks at rate of INT)
x1
Voltage x2
Current x3
V/A/F/PF x4
PF & Power
Avg Voltage (V L-N)
Acve Energy (kWh)
Phase Voltage
(V L-N)
Phase Current
(A)
Avg Voltage (V L-N)
Total Current (A)
Frequency (Hz)
Avg Power Factor
Phase Power Factor
Frequency (Hz)
x1 Avg Voltage (V L-N)
Reacve Energy (kVArh)
Phase Voltage
(V L-L)
Avg Voltage (V L-L)
Total Current (A)
Frequency (Hz)
Avg Power Factor
Phase Acve Power (kW)
x2 Phase Reacve Power (kVAr)
x3 Phase Apparent Power (kVA)
x4 tOt Acve Power (kW)
x5 tOt Reacve Power (kVAr)
x6 tOt Apparrent Power (kVA)
x7 tOt Acve Max MD (kW)
x8 tOt Reacve Max MD (kVAr)
Energy
Parameters in BOLD not
displayed for 1P2W
Voltage Phase Rotaon
Hold 3 Sec
OK CLK: L1 → L2 → L3
ANTI-CK: Incorrect Order
INVAL Id: Missing Phase û
ü
Rayleigh Instruments Limited (Head Office)
Raytel House, Cutlers Road, South Woodham Ferrers, Chelmsford, Essex. CM3 5WA
W: www.rayleigh.com E: sales@rayleigh.com
Rayleigh Instruments Limited SP. Z o.o. (European Office)
Ul. Aleje Jerozolimskie 214, Warsaw, Poland, 02-486
W: www.rayleigh.pl E: sales@rayleigh.pl
Other Rayleigh Instruments Measuring Instrument manuals