RCNTEC RPCM DC ATS 76A User manual

Resilient Power Control Module
RPCM
Quick Install Guide
Models:
RPCM DC ATS 76A
RPCM DC 232A
Version 2 19 821 121

1
Dear Customer!
Please accept our congratulations on your purchase of RPCM - Resilient Power Control Module.
This device will allow you to be in control of your power supply infrastructure with great user
e perience.
We have paid a lot of attention to craft the device the way we would want it to be for ourselves. In
many ways, physically, ergonomically, architecturally, electrically it is designed to be one stop shop
for many power control tasks that people meet in many circumstances.
We have made every effort to make RPCM useful both in enterprise environment behind firewall and
in less strict environment with access to Internet, where all the power of the Cloud comes to your
service.
We have tried to make interfaces as intuitive as possible and prepared detailed documentation to
assist you in every case that may be not obvious or e pected for this class of equipment.
Bon voyage! We hope you enjoy it!
RCNTEC Team
1. Congratulations on purchase of your RPCM!
2. Mounting onto a Rack
1. Install the cage (mounting) nuts as shown in the Fig. 1.
2. Place RPCM on the rack and secure it as shown in Fig. 2.
3. Prepare to connect the power lines as shown in Fig. 3.
. Connect the power cables to the inputs.
5. Connect wires for connecting the devices to be supplied with power to the outlets.
Fig.1. Installation of mounting cage nuts on rack

Input 1
First line
Resilient Power Control Module (RPCM)
Outlets RPCM 0-9
0 1 2 3 4 5 6 7 8 9
Input 2
Second line
Auto-
switch
first
line
Auto-
switch
second
line
Note. Second input is used to connect RPCM DC ATS
76A. If two inputs are connected, priority is for an
input with higher voltage.
RPCM DC 232A has single input.
Note. In order to protect outlets from short circuits, short circuit protection selectivity has to be ensured in
the electrical design.
For RPCM DC ATS 76A, RPCM DC 232A — short circuit protection engages at ~87.5A current on the
outlet.
To ensure selectivity, the circuit breakers at the inputs must be selected so that the tripping does not
occur at short-circuit currents <87.5A, the lower threshold of the tripping current of the upstream
circuit-breakers must be chosen so that the tripping does not occur at the short-circuit current at the
consumer connection point.
2
Fig. 3. Wiring Diagram for Resilient Power Control Module
Fig. 2. Installation of RPCM DC

++
3
Legend:
11
3
2
4 5
1
6
12
Fig. 4. Elements on RPCM DC
ATS 76A
Fig. 5. Elements on the rear panel
of RPCM DC 232A
1 — Top control button
2 — Bottom control button
3 — System status display
— Input indicator (RPCM DC 232A has
single indicator)
5 — Outlet indicators 0-9
6 — Ethernet control port RJ 5
1413
10987
7 — Outlets 0-9
8 — LED outlet indicators 0-9
9 — Inputs terminals of RPCM DC ATS 76A
10 — Inputs indicators of RPCM DC ATS 76A
11 — Ground connect screw
12 — Serial label
13 — Input terminals of RPCM DC 232A
1 — Input indicator of RPCM DC 232A
3. External Elements

+
-
4
IMPORTANT! No mechanical loads should be transferred to the Push-in spring clip, otherwise
the electrical connection may be damaged.
For this, the cable may, for example, be secured in front of the push-in clamp using a cable clip.
Note. To disconnect, you must also
insert a screwdriver into the
rectangular shaft next to the clip.
4. Conductors Connection
Carefully study the labeling and polarity
of the connection.
Remove the insulation from the wire.
When using flexible wires without
ferrule, you must first open the spring.
To do this, insert a screwdriver into the
rectangular shaft near the clamp.
Fig. 6. Connecting wires to the inputs RPCM DC ATS 76A
+
-
To connect the conductors to the terminals, use the terminals in
the form of a push-in clamp.
Conductors Connection to Outlets of RPCM DC ATS 76А and RPCM DC 232А
Fig. 7. Connect the conductor to the RPCM DC ATS 76A
or RPCM DC 232A outlet terminal
To connect the conductor to the
RPCM DC ATS 76A or RPCM DC
232A terminal you must:
Remove the insulation from the
conductor.
Insert the conductor directly into the
round hole of the terminal.
To open the spring, press the orange
Push button with a screwdriver.
Similarly connect the second
conductor.
Note. To remove the conductor, you
also need to push in the orange Push
button with a screwdriver.
Connection to Inputs of RPCM DC ATS 76А

5
Power and Grounding Requirements
Voltage: 8V. Electric current level: <76А for RPCM DC ATS 76A, <232А for RPCM DC 232А.
Grounding must be connected. Conductor requirements:
RPCM DC ATS 76A — 1.5mm2 1 AWG min – 16mm2 AWG MAX Strip 18mm 66A cULus CSA
RPCM DC 232A — Solid 25mm2 3AWG min – 95mm2 000AWG MAX Strip 27mm
Flexible 35mm2 2AWG min – 95mm, 000AWG MAX Strip 27mm
2 conductors 6mm2 AWG – 35mm2 2AWG Strip 27mm 200A cULus CSA
Note. If only one input is connected, RPCM DC ATS 76A will function properly except ATS
operations.
Connection to input RPCM DC 232А
To connect the input to the electrical circuit uses two
terminals with screw terminals for the positive and
negative conductors.
CAUTION! There is a danger of electric shock. The funnel-shaped hole for cable entry is not
protected against contact. Do not connect or disconnect live terminals. Appropriate measures should
be taken to protect against contact with conductive materials.
Fig. 8. Connect the conductor to the input
terminal RPCM DC 232A
For connecting cables to the screw terminal:
Remove insulation from wire.
Insert the wire into the contact hole.
Insert the hex screwdriver into the side hole to
tighten the screw.
Torque the screw with a force of 10Nm min - 12Nm max.
Connect the second conductor in the same way.
4. Starting to Operate
Determining the IP or MAC address
Receiving an IP address
IP address is obtained by default via DHCP. If there is no DHCP server or it is temporarily
unavailable, RPCM will obtain IP through Automatic Private IP Addressing (APIPA) thanks to Zero
Configuration.
When this method of configuring network addresses is used, IP ranging from 169.25 .xxx.xxx,
Netmask 255.255.0.0 (CIDR standard — 169.25 .0.0/16) are automatically assigned.
To reset the device, hold the top button on the front panel for 20 seconds.
Reset to Factory Settings
To find out the IP address, you will need to press the bottom button 3 times in succession (press
times for the MAC address. Before pressing the next time, you will need to wait for a reaction
to the previous press).
When you press the first time, a running message regarding the electric current level (for example
«10Amps») will be displayed. Only numerical figures will be displayed after 5 seconds.
When you press the second time, the power level will be displayed also as a running message. Only
numerical figures will be displayed after 5 seconds.
When you press the third time, RPCM will switch over to IP address display mode.
When you press the fourth time, the MAC address will be displayed.

6
6. Connecting via Web Interface
This type of control is based on use of application level protocols: HTTP/(HTTPS). The IP address
or domain name of the device registered in DNS is indicated in the browser field. For example:
http://192.168. .yyy is our device's IP.
Authentication is performed using username and password.
Default user name and password: user name — rpcmadmin
password — rpcmpassword
RPCM’s web interface supports an array of browser models and versions:
●Chrome — version 61.0.3163.100 and higher.
●Safari — version 10.1.1and higher.
●Firefox — version 56.0 and higher.
●Opera — version 8.0.2685.32 and higher.
After going to the specified webpage, the authentication window will open up where you can enter
username and password, as well as select a different language for the interface. Then you will be sent
to RPCM’s main web interface window - the Dashboard, where general information is provided in
addition to system controls.
1 — Web interface language selection menu
2 — Entry field for username
3 — Entry field for password
— LOGIN button to confirm credentials and to enter RPCM’s web interface
5 — Link for launching SSH-client with this address as a parameter
Fig. 9. System entry window
Designation:
Please Note: For more
detailed information
about RPCM
capabilities, please
consult the User Manual
available at
http://rpcm.pro/docs
2
3
4
5
1

RPCMCli version 0.7.78 is starting
user rpcmadmin successfully authenticated from 192.1 8.xx.yy, access level superuser
Auto-logout time is set to 3 00 seconds
[Serial Name]: DobriyVolk [Temperature]: 28C
[Serial Number]: RU2017101100000002MO01DN02 [Ground]: GOOD
[Firmware Version]: 0.9.743 [Firmware Release Date]: 20190515093438
[Software Version]: 0.7.78 [Software Release Date]: 20190518105432
[Model/Hardware Version]: 407 /RPCM DC ATS 7 A [Uptime]: 7087d+20:00:49
-----------------------------------------------------------------------------------
[Input 1]: 47.8V 2.338A 0.493KW (ACTIVE, PRIORITY)
[Input 2]: 47.8V 0.000A 0.000KW
-----------------------------------------------------------------------------------
[Output 0]: OFF <admin: ON> 0mA 0W (SHORT)
[Output 1]: ON <admin: ON> 58 mA 125W (OVERLOAD)
[Output 2]: ON <admin: ON> 223mA 4 W
[Output 3]: ON <admin: ON> 530mA 112W
[Output 4]: ON <admin: ON> 251mA 52W
[Output 5]: ON <admin: ON> 223mA 4 W
[Output ]: ON <admin: ON> 525mA 112W
[Output 7]: ON <admin: ON> 0mA 0W
[Output 8]: ON <admin: ON> 0mA 0W
[Output 9]: OFF <admin: OFF> 0mA 0W
Type 'help' to get suggestions
DobriyVolk [192.1 8.xx.zz] 0 rpcmadmin >
7. Connecting via SSH
To connect via SSH protocol in UNIX-based systems, it will be sufficient to indicate from within
the terminal's emulator the command: ssh ip_address.
In the MS Windows environment, you can use the PUTTY program. You will need to configure
settings in the Sessions section of this program. If you have any question about SSH clients, e.g.
PUTTY, please consult the relevant documentation.
RPCM's system during access via SSH uses username and password authentication.
Default user name and password: user name — rpcmadmin
password — rpcmpassword
Example our device's IP is 192.168.xx.yy:
ssh 192.168.xx.yy
In response, username and password will be requested:
login as: rpcmadmin
[email protected]'s password:
Alternatively, you can create a username right away:
In this case, the system will request that you enter only the password:
[email protected] password:
Fig. 10. An e ample of the console screen when logging in via SSH to the RPCM DC ATS 76A
http://rpcm.pro
Tel: +7 ( 95) 009 87 87, +7 (800) 302 87 87
E-mail: [email protected]
Contacts: Feedback:
http://rcntec.com/feedback
This manual suits for next models
2
Table of contents
Other RCNTEC Control Unit manuals
Popular Control Unit manuals by other brands

Pentair
Pentair Anderson Greenwood 93 Series Installation and maintenance instructions

Gifas-electric
Gifas-electric TrafficLED installation instructions

Paxton
Paxton Switch2 quick start guide

DEEP SEA ELECTRONICS
DEEP SEA ELECTRONICS DSE8910 installation instructions

Innodisk
Innodisk EGSS-32R1 manual

Meynell
Meynell V8/3 product manual

Burkert
Burkert Robolux 2036 quick start

Roland
Roland TM-6 PRO quick start

Allen-Bradley
Allen-Bradley ControlNet 1786-RPCD installation instructions

SEW-Eurodrive
SEW-Eurodrive MOVIFIT basic operating instructions

Dungs
Dungs DMV 11 eco Series Operation and assembly instructions

Honeywell
Honeywell TR80UWD Installation and operating guide