RCNTEC RPCM Series User manual

Resilient Power Control Module
RPCM
Quick Install Guide
For models:
RPCM 1502 (16А)
RPCM 1532 (32А)
RPCM ME 1563 (63A - Mining Edition)
Version 201908210021

2 Mounting onto a Rack
1. Install the cage (mounting) nuts as shown in the Fig. 1.
2. Place RPCM on the rack and secure it as shown in Fig. 2.
3. Prepare to connect the power lines as shown in Fig. 3.
. Connect the power cables to the inputs.
5. Plug in the IEC-320-C1 connectors for connecting the devices to be supplied with power to the
outlets.
Fig.1. Installation of mounting cage nuts on rack
1
Dear Customer!
Please accept our congratulations on your purchase of RPCM - Resilient Power Control Mo ule.
This evice will allow you to be in control of your power supply infrastructure with great user
experience.
We have pai a lot of attention to craft the evice the way we woul want it to be for ourselves. In
many ways, physically, ergonomically, architecturally, electrically it is esigne to be one stop shop
for many power control tasks that people meet in many circumstances.
We have ma e every effort to make RPCM useful both in enterprise environment behin firewall an
in less strict environment with access to Internet, where all the power of the Clou comes to your
service.
We have trie to make interfaces as intuitive as possible an prepare etaile ocumentation to
assist you in every case that may be not obvious or expecte for this class of equipment.
Bon voyage! We hope you enjoy it!
RCNTEC Team
1 Congratulations on purchase of your RPCM!

Fig. 2. Installation of RPCM
Fig. 3. Wiring Diagram for Resilient Power Control Mo ule
Please Note: Note. In order to prevent short-circuit protection of the terminals in the RPCM from
tripping circuit breakers installed on the inputs, it is necessary to ensure complete selectivity of
protection.
For RPCM 1502, RPCM 1532, RPCM ME 1563, the operation current of protection against short
circuit on the terminals RPCM ~ 7 to 17 iNom for 10A or from ~ 70 to ~ 170 A, the response time for
short circuit is about 2 milliseconds. the upper threshold of the tripping current of the upstream
circuit breakers must be chosen so that the tripping does not occur at the fault current measured at the
point connect the consumer. To ensure complete selectivity, the use of selective circuit breakers with
a trip delay at short circuit 10ms is recommended.
2
Input 1
Active
Main
power
line
Resilient Power Control Module (RPCM)
RPCM 0-9 outputs
0 1 2 3 4 5 6 7 8 9
Input 2
Passive
Reserve
power
line
Auto-
switch
of main
line
Auto-switch
of reserve
line
Please Note: Reserve power line is only for RPCM
1502 (16A) and RPCM 1532 (32A). By default, the
main one is Input 1. When using the reverse order,
you must change the configuration settings.
RPCM ME 1563 has only one inlet and can't
connect to a secondary power line.

1 — Top control button
2 — Bottom control button
3 — System status indicator
— Input indicator 1
5 — Input indicator 2
6 — Outlet indicators 0-9
3
1
2
74 5 6
3 External Elements
8
9
11
10
Fig. 4. Elements on the front panel of RPCM 1502 (16A) an RPCM 1532 (32A)
Fig. 5. Elements on the rear panel of RPCM 1502 mo el (16A)
Designation:
13 — Inputs indicators 1-2 of
RPCM 1532
1 — One input indicator of
RPCM ME 1563
15 — One input of RPCM ME
1563
3
7 — Ethernet control port RJ 5
8 — Outlets 0-9
9 — LED outlet indicators 0-9
10 — Serial tag
11 — Inputs 1-2 of RPCM 1502
12 — Inputs 1-2 of RPCM 1532
Fig. 6. The ifference of elements on the rear panel of RPCM 1532 (32A)
12
13

4 Starting to Operate
Determining the IP or MAC address
To find out the IP address, you will need to press the bottom button 3 times in succession (press
times for the MAC address. Before pressing the next time, you will need to wait for a reaction
to the previous press).
When you press the first time, a running message regarding the electric current level (for example
«10Amps») will be displayed. Only numerical figures will be displayed after 5 seconds.
When you press the second time, the power level will be displayed also as a running message. Only
numerical figures will be displayed after 5 seconds.
When you press the third time, RPCM will switch over to IP address display mode.
When you press the fourth time, the MAC address will be displayed.
Receiving an IP address
IP address is obtained by default via DHCP. If there is no DHCP server or it is temporarily
unavailable, RPCM will obtain IP through Automatic Private IP Addressing (APIPA) thanks to Zero
Configuration.
When this method of configuring network addresses is used, IP ranging from 169.25 .xxx.xxx,
Netmask 255.255.0.0 (CIDR standard — 169.25 .0.0/16) are automatically assigned.
4
14
15
Fig. 7. The ifference of elements on the front panel of RPCM ME 1563 (63A — Mining E ition)
Fig. 8. The ifference of elements on the rear panel
of RPCM ME 1563 (63A — Mining E ition)
To reset the device, hold the top button on the front panel for 20 seconds.
Reset to Factory Settings

5 Connecting via Web Interface
This type of control is based on use of application level protocols: HTTP/(HTTPS). Connection is
performed through an Internet browser via standard port 80. The IP address or domain name of the
device registered in DNS is indicated in the browser field. For example: http://192.168.xxx.yyy is our
evice's IP.
Authentication is performed using username and password.
Default user name and password:
user name — rpcmadmin password — rpcmpassword
RPCM’s web interface supports an array of browser models and versions:
●Chrome — version 61.0.3163.100 and higher.
●Safari — version 10.1.1and higher.
●Firefox — version 56.0 and higher.
●Opera — version 8.0.2685.32 and higher.
After going to the specified webpage, the authentication window will open up where you can enter
username and password, as well as select a different language for the interface. Then you will be sent
to RPCM’s main web interface window - the Dashboard, where general information is provided in
addition to system controls.
1 — Web interface language selection menu
2 — Entry field for username
3 — Entry field for password
— LOGIN button to confirm credentials and to enter RPCM’s web interface
5 — Link for launching SSH-client with this address as a parameter
Fig. 9. System entry win ow
Designation:
Please Note: For more
detailed information
about RPCM
capabilities, please
consult the User Manual
available at
http://rpcm.pro/ ocs
5
1
2
3
4
5

RPCMCli version 0.7.7 is starting
user rpcmadmin successfully authenticated from 192.16 .xx.yy, access level
superuser
Auto-logout time is set to 3600 seconds
[Serial Name]: SuperGeroy [Temperature]: 2 C
[Serial Number]: RU2017101100000002MO01DN01 [Ground]: GOOD
[Firmware Version]: 0.9.454 [Release Date]: 201 0515164154
[Software Version]: 0.7.7 [Software Release Date]: 201 05151 5713
[Uptime]: 02:20:32 [Model/Hardware Version]: 1502/RPCM
[Force Failback]: OFF [Failback Delay in Seconds]: 0
-------------------------------------------------------------------------------
[Input 1]: 233V @ 49.99Hz 2.33 A 0.493KW (ACTIVE, PRIORITY)
[Input 2]: 232V @ 49.99Hz 0.000A 0.000KW
-------------------------------------------------------------------------------
[Output 0]: OFF <admin: ON> 0mA 0W (OVERLOAD)
[Output 1]: ON <admin: ON> 251mA 52W (OVERLOAD)
[Output 2]: ON <admin: ON> 223mA 46W
[Output 3]: ON <admin: ON> 530mA 112W
[Output 4]: ON <admin: ON> 5 6mA 125W
[Output 5]: ON <admin: ON> 223mA 46W
[Output 6]: ON <admin: ON> 525mA 112W
[Output 7]: ON <admin: ON> 0mA 0W
[Output ]: ON <admin: ON> 0mA 0W
[Output 9]: OFF <admin: OFF> 0mA 0W
Type 'help' to get suggestions
SuperGeroy [192.16 .xx.yy] 0 rpcmadmin >
6 Connecting via SSH
To connect via SSH protocol in UNIX-based systems, it will be sufficient to indicate from within
the terminal's emulator the command: ssh ip_a ress.
In the MS Windows environment, you can use the PUTTY program. You will need to configure
settings in the Sessions section of this program. If you have any question about SSH clients, e.g.
PUTTY, please consult the relevant documentation.
RPCM's system during access via SSH uses username and password authentication.
Default user name and password:
user name — rpcmadmin
password — rpcmpassword
Example our device's IP is 192.168.xx.yy:
ssh 192.168.xx.yy
In response, username and password will be requested:
login as: rpcmadmin
[email protected]'s password:
Alternatively, you can create a username right away:
In this case, the system will request that you enter only the password:
[email protected] password:
Fig. 10. An example of the console screen when logging in via SSH for the RPCM 1502 or
RPCM 1532 mo els (RPCM ME 1563 has one input)
6

8 Requirements for Ambient Conditions During Use
Normal ambient conditions for use of Resilient Power Control Module (RPCM) are the following:
●operation range of ambient temperature is 0- 0°С;
●operation range of relative humidity is 5-85% (non-condensing);
●operation range of altitude is 0-2000m.
The surrounding environment is non-explosive, does not contain a considerable amount of
conductive dust, vapors, aggressive gases in concentrations that harmfully affect RPCM components
and materials.
WARNING! The maximum range of temperature fluctuation during storage is 20°C per hour.
Storage temperature is from -20 to 60°C. Prior to activating RPCM, it is necessary to allow the
device time of not less than 2 hours to adapt to the new conditions. Physical installation of RPCM
may continue during this acclimatization period. If there is condensation even after the 2 -hour
period, it will be necessary to wait until the specified norms have been reached before you can
activate the system.
During inspection of the exterior, the following are to be determined:
●there are no defects on and damages to the external surfaces of the product;
●there is a seal and it is intact.
The quality of the modules’ plug assembly must ensure reliable contact with connecting elements
and eliminate inadvertent disconnection.
Electric connectors must ensure uninterrupted performance of technical support components and
external connectors must allow peripheral devices to be turned off and connected during regular
operation mode without loss in connection quality and ensure reliable electrical and mechanical
contact.
The surface area of RPCM and slots used must be free of chips, scratches, dents, and other defects.
9 Inspection before Installing and Using
http://rpcm.pro
Tel: +7 ( 95) 009 87 87, +7 (800) 302 87 87
E-mail: [email protected]
Contacts: Feedback:
http://rcntec.com/feedback
Voltage < 2 0V. Frequency is 50-60Hz in a power grid.
Electric current level <16А for RPCM 1502, <32А for RPCM 1532 and <63A for RPCM ME 1563.
Voltage supply requirements:
●for RPCM 1502 — two power cables with IEC-320-C19 connectors,
●for RPCM 1532 — two sockets for plugging the 2P+E 32A 250V connectors,
●for RPCM ME 1563 — one socket for plugging the 2P+E 63A 250V.
NOTE: if only one cable is connected, the RPCM 1502 or RPCM 1532 will function properly except
for the ATS operation.
7 Power and Grounding Requirements
Other manuals for RPCM Series
2
This manual suits for next models
3
Table of contents
Other RCNTEC Control Unit manuals
Popular Control Unit manuals by other brands

LOVATO ELECTRIC
LOVATO ELECTRIC FF128EP Series Installation, operation and maintenance manual

Generac Power Systems
Generac Power Systems SMM Owners & installation manual

Rockwell Automation
Rockwell Automation Allen-Bradley 1606-XLERED20Y Reference manual

AVG
AVG PRV25F installation instructions

DOLD
DOLD SAFEMASTER C UG 6980 Translation of the original instructions

RAK
RAK RAK4600 quick start guide