Red Ion CUB5T User manual

1
LCD, REFLECTIVE OR RED/GREEN LED BACKLIGHTING
0.46" (11.7 mm) HIGH DIGITS
7-DIGIT BI-DIRECTIONAL TIMING CAPABILITY
6-DIGIT CYCLE COUNTING CAPABILITY
OPTIONAL RELAY OUTPUT MODULE
OPTIONAL SERIAL COMMUNICATIONS MODULE (RS232 or RS485)
SELECTABLE TIMER RANGES AND OPERATING MODES
ELAPSED TIMER AND PRESET TIMER FUNCTIONALITY
DISPLAY COLOR CHANGE CAPABILITY AT PRESET OUTPUT
OPERATES FROM 9 TO 28 VDC POWER SOURCE
NEMA 4X/IP65 SEALED FRONT BEZEL
MODEL CUB5T - MINIATURE ELECTRONIC PRESET TIMER
AND CYCLE COUNTER
GENERAL DESCRIPTION
The CUB5T provides the ultimate in timer flexibility, from its complete user
programming to the optional relay output and serial communications capability.
The meter functions as an Elapsed Timer or Preset Timer. It also has a built-in
Cycle Counter. The display can be toggled either manually or automatically
between the Timer and Cycle Counter values. With eight different input
operating modes and 18 selectable timer ranges, the meter can be programmed
for a wide variety of timing applications.
The CUB5T has an LCD display with 0.46" (11.7 mm) high digits. The LCD
isavailableintwoversions,reflective(CUB5TR00)andbacklight(CUB5TB00).
The backlight version is user selectable for red or green backlighting with
variable display intensity.
The Timer has two signal inputs and eight input operating modes. These
modes provide level active or edge triggered start/stop operation. A Display
Hold mode will display the elapsed time for one cycle, while the next cycle
continues timing internally. The Timer Reset modes will automatically reset the
timer value when a time start edge is applied to the input. This allows sequential
timing cycles without having to manually reset the Timer.
In addition to the Timer inputs, a programmable User Input is available to
perform a variety of meter functions. All inputs are current sinking (active low)
and accept a variety of logic and open-collector output signal sources. Relay and
switch contacts can also be used as signal sources, when the software input
debounce filter is enabled.
The capability of the CUB5T can be easily expanded with the addition of a
field installable option module. When the CUB5RLY0 relay output module is
added, the meter becomes a Preset Timer. The Setpoint Output can be assigned
to the Timer or Cycle Counter values, and configured to suit a variety of control
and alarm requirements. Serial communications capability for RS232 or RS485
is added with a serial option module (CUB5COM).
The CUB5T can be powered from an optional Red Lion Micro-Line/Sensor
Power Supply (MLPS), which attaches directly to the back of a CUB5T. The
MLPS is powered from an 85 to 250 VAC source and provides up to 400 mA to
drive the meter and sensors.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the meter.
Bulletin No. CUB5T-D
Drawing No. LP0628
Released 07/12
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONS In inches (mm)
.13 (3.3)
(43.4)
1.71
2.95 (74.9)
SEL
.15 (3.8)
1.54 (39.1)
RST
(68 )
+.025
-.000
+8
-0
1.29 (32.8)
2.68
-.000
1.30
(33 )
1 2 34
-0
+6
+.024
ON ECE
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
C
C
US LISTED
US LISTED
UL
R
51EB
IND. CONT. EQ.

1. DISPLAY: 8 digit LCD 0.46" (11.7 mm) high digits
CUB5TR00: Reflective LCD with full viewing angle
CUB5TB00: Selectable transmissive red or green backlight LED with
viewing angle optimized. Display color change capability at preset when
using a relay module.
2. POWER: Input voltage range is +9 to +28 VDC with short circuit and input
polarity protection. Must use an RLC model MLPS or a Class 2 or SELV
rated power supply.
3. TIMER DISPLAY: 7-digits
Display Designator: “t” to the left side of the display
Display Range: 0 to 9999999
Overflow/Underflow Indication: Display flashes “t OVEr”
Minimum Digit Resolution: 0.001 Sec.
Maximum Single Digit Resolution: 1 Hr.
Timing Accuracy: ±0.01%
4. CYCLE COUNTER DISPLAY: 6-digits, may be disabled if not used
Display Designator: “C” to the left side of the display
Display Range: 0 to 999999
Overflow/Underflow Indication: Display flashes “C OVEr”
Maximum Count Rate:
All Count Sources except Input B: 10 Hz
Input B Count Source:
With Timer Input Filter ON: 10 Hz
With Timer Input Filter OFF: 500 Hz
5. TIMER SIGNAL INPUTS (INPA and INP B)
Logic Inputs, Current Sinking (active low)
Input A:
Internal 7.8Kpull-up resistor to +9 to 28 VDC
Trigger levels: VIL = 1.25 V max; VIH = 2.75 V min; VMAX = 28 VDC
Input B:
Internal 10Kpull-up resistor to +9 to 28 VDC
Trigger levels: VIL = 0.7 V max; VIH = 2.4 V min; VMAX = 28 VDC
Inputs A and B:
Timer Input Pulse Width: 1 msec min.
Timer Start/Stop Response Time: 1 msec max.
Filter: Software filtering provided for relay or switch contact debounce.
Filter enabled or disabled through programming. If enabled, results in
50 msec start/stop response time for successive pulses applied to the
same input terminal.
6. USER INPUT (USR): Programmable function input
Logic Input, Current Sinking (active low)
Internal 10Kpull-up resistor to +9 to 28 VDC
Trigger levels: VIL = 0.7 V max; VIH = 2.4 V min; VMAX = 28 VDC
Response Time: 5 msec typ.; 50 msec debounce (activation and release)
7. MEMORY: Nonvolatile E2PROM memory retains all programming
parameters and timer/counter values when power is removed.
8. CONNECTIONS: Wire clamping screw terminals
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 5 inch-lbs (0.565 N-m) max.
9. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range for CUB5TR00: -35 to 75°C
Operating Temperature Range for CUB5TB00 depends on display color
and intensity level as per below:
INTENSITY LEVEL TEMPERATURE
Red Display 1 & 2 -35 to 75°C
3 -35 to 70°C
4 -35 to 60°C
5 -35 to 50°C
Green Display 1 & 2 -35 to 75°C
3 -35 to 65°C
4 -35 to 50°C
5 -35 to 35°C
Storage Temperature: -35 to 85°C
Operating and Storage Humidity: 0 to 85% max. relative humidity (non-
condensing)
Vibration According to IEC 68-2-6: Operational 5 to 500 Hz, in X, Y, Z
direction for 1.5 hours, 5 g.
Shock According to IEC 68-2-27: Operational 40 g, 11 msec in 3 directions.
Altitude: Up to 2000 meters
10. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA22.2 No. 61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Outdoor Enclosure rating (Face only), UL50
IECEE CB Scheme Test Report #E179259-V01-S02
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
EmissionsandImmunitytoEN61326:ElectricalEquipmentforMeasurement,
Control and Laboratory use.
Notes:
1. Criterion A: Normal operation within specified limits.
Refer to EMC Installation Guidelines for additional information.
11. CONSTRUCTION: This unit is rated for NEMA4X/IP65 requirements for
outdoor use. Installation Category I, Pollution Degree 2. High impact plastic
case with clear viewing window. Panel gasket and mounting clip included.
12. WEIGHT: 3.2 oz (100 g)
2
GENERAL METER SPECIFICATIONS
ORDERING INFORMATION
MODEL
NUMBER DISPLAY COLOR INPUT CURRENT
WITHOUT
CUB5RLY0
INPUT CURRENT
WITH
CUB5RLY0
CUB5TR00 --- 10 mA 30 mA
CUB5TB00 Red (max intensity) 85 mA 115 mA
CUB5TB00 Green (max intensity) 95 mA 125 mA
Class AEN 55011Emissions
Emissions: 30 A/m
3 V/rms
Criterion A
Criterion A
EN 61000-4-8
EN 61000-4-6RF conducted interference
1 kV L-L,
Criterion AEN 61000-4-5Surge 1 kV signal
2 kV power
Criterion AEN 61000-4-4Fast transients (burst)
2 kV L&N-E power
10 V/m
Criterion AEN 61000-4-3Electromagnetic RF fields 8 kV air discharge
4 kV contact discharge
Criterion AEN 61000-4-2Electrostatic discharge
Immunity to Industrial Locations:
Power frequency magnetic fields
TYPE MODEL NO. DESCRIPTION PART NUMBER
CUB5 CUB5TR Preset Timer and Cycle Counter with Reflective Display CUB5TR00
CUB5TB Preset Timer and Cycle Counter with Backlight Display CUB5TB00
Optional Plug-in Cards CUB5RLY Single Relay Option Card CUB5RLY0
CUB5COM RS485 Serial Communications Card CUB5COM1
RS232 Serial Communications Card CUB5COM2
Accessories MLPS +12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out MLPS1000
+24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max out MLPS2000
CBLPROG Programming Cable RS232 (RJ11-DB9) CBLPROG0
CBPRO Programming Cable RS485 (RJ11-DB9) CBPRO007

3
ADDING OPTION CARDS
The CUB5T meters can be fitted with optional relay card and/or serial
communications cards. The details for the plug-in cards can be reviewed in the
specification section below. The plug-in cards, that are sold separately, can be
installed initially or at a later date.
RELAY CARD
Type: Single FORM-C relay
Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.
Working Voltage: 150 Vrms
Contact Rating: 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive
Life Expectancy: 100,000 minimum operations
Response Time:
Turn On Time: 4 msec max.
Turn Off Time: 4 msec max.
Time Accuracy: ± 0.01%
WARNING: Disconnect all power to the meter before
installing Plug-in card.
RS485 SERIAL COMMUNICATIONS CARD
Type: RS485 multi-point balanced interface (non-isolated)
Baud Rate: 300 to 38400
Data Format: 7/8 bits; odd, even, or no parity
Bus Address: 0 to 99; max 32 meters per line
Transmit Delay: Selectable. 2 msec min. or 50 msec min.
RS232 SERIAL COMMUNICATIONS CARD
Type: RS232 half duplex (non-isolated)
Baud Rate: 300 to 38400
Data Format: 7/8 bits; odd, even, or no parity
OPTIONAL PLUG-IN CARDS
1.0 INSTALLING THE METER
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed. The
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel
gasket over the rear of the unit to the back of the bezel. The unit should be
installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit
so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten the latch screws evenly until the unit is snug in the panel (Torque to
approx. 28 to 36 in-oz [0.202 to 0.26 N-m]). Do not over-tighten the screws.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating
temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
2.0 DIP SWITCHES
2.68
(68 )
+.8 1.30
-.0
(33 )
-.000
+.6
-.0
-.000
+.024
+.025
The DIP switches on the main circuit board are not used with the CUB5T and
must be left in the factory set position (all down). Setting any switch to the up
position may cause improper operation of the meter.
PANEL
GASKET
BEZEL PANEL MOUNTING SCREW
NUT FASTENER
MOUNTING CLIP

WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that the power
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed
(stranded wires should be tinned with solder.) Insert the lead under the correct
screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro-
Magnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, source or coupling method into the meter may be different for various
installations. The meter becomes more immune to EMI with fewer I/O
connections. Cable length, routing, and shield termination are very important
and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the meter and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be ran in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far as possible
from contactors, control relays, transformers, and other noisy components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC# FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC# LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC# SNUB0000.
4.0 WIRING THE METER
4
The Plug-in cards are separately purchased option cards that perform specific
functions. The cards plug into the main circuit board of the meter after the rear
cover is removed
WARNING: Disconnect all power to the meter before
installing Plug-in Card.
REMOVING THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd
input terminals. To release the tab, insert a small, flat blade screwdriver between
the tab and the plastic wall below the terminals. Inserting the screwdriver will
provide enough pressure to release the tab locks. To replace the cover, align the
cover with the input terminals and press down until the cover snaps into place. CAUTION: The Plug-in cards and main circuit board contain static
sensitive components. Before handling the cards, discharge static
charges from your body by touching a grounded bare metal object.
Ideally, handle the cards at a static controlled clean workstation.Also,
only handle the cards by the edges. Dirt, oil or other contaminants
that may contact the cards can adversely affect circuit operation.
3.0 INSTALLING PLUG-INCARDS
ECEON
4132
Comms Card Relay Card
Locking Tab

5
4.1 POWER WIRING
INP COMM
USR
+9-28 VDC
INP B
INP A
PWR COMMON
+
-
DC Power
+9 to +28 VDC: +VDC
Power Common: -VDC
4.2 USER INPUT WIRING
INP COMM
USR
+9-28 VDC
INP B
INP A
PWR COMMON
Sinking Logic
INP COMM
USR
The user input of the meter is
internally pulled up to +9 to +28 V
with 10 K resistance. The input is
active when it is pulled low.
Connect external switching device between the
User Input terminal and Input Common.
}
4.3 INPUT WIRING
CAUTION: Power input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the power input
common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not,
hazardous voltage may be present at the User Inputs and User Input Common terminals.Appropriate considerations must then be given to the potential
of the user input common with respect to earth ground; and the common of the plug-in cards with respect to input common.
+9-28 VDC
PWR COMMON
INP COMM
USR
INP A
INP B
O.C.
NPN
INP B
INP A
INP COMM
USR
+9-28 VDC
PWR COMMON
Interfacing With TTLCurrent Sinking Output
Input A
Switch or Isolated Transistor; Current Sink
Input A
+9-28 VDC
PWR COMMON
USR
INP COMM
INP B
INP A
COMMON
+5 V
4.4 SETPOINT (OUTPUT) WIRING
4.5 SERIAL COMMUNICATION WIRING
COM
N.C.
N.O.
COM N.O. N.C.
ELECTRICAL CONNECTIONS
SETPOINT RELAY PLUG-IN CARD
N/C
RS485
2
COMM
A+
B-
N/C
534
N/C
RS232
5
N/C
TX
N/C
43
COMM
COMM
2
RX
61 61
SERIAL COMMUNICATIONS PLUG-IN CARD RJ11 CONNECTOR PIN OUTS
Input A

6
PROGRAMMING MODE ENTRY (SEL KEY)
It is recommended all programming changes be made off line, or before
installation. The meter normally operates in the Display Mode. No parameters
can be programmed in this mode. The Programming Mode is entered by
pressing and holding the SEL key. If it is not accessible, then it is locked by
either a security code, or a hardware lock (See Module 3).
MODULE ENTRY (SEL & RST KEYS)
The Programming Menu is organized into separate modules. These modules
group together parameters that are related in function. The display will alternate
between and the present module. The RST key is used to select the desired
module. The displayed module is entered by pressing the SEL key.
MODULE MENU (SEL KEY)
Each module has a separate module menu (which is shown at the start of each
module discussion). The SEL key is pressed to advance to a particular parameter
to be changed, without changing the programming of preceding parameters.
After completing a module, the display will return to . Programming
may continue by accessing additional modules.
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and
the selections/value for that parameter. The RST key is used to move through the
selections/values for that parameter. Pressing the SEL key, stores and activates the
displayed selection/value. This also advances the meter to the next parameter.
For numeric values, press the RST key to access the value. The right hand
most digit will begin to flash. Pressing the RST key again increments the digit
by one or the user can hold the RST key and the digit will automatically scroll.
The SEL key will advance to the next digit. Pressing and holding the SEL key
will enter the value and move to the next parameter.
PROGRAMMING MODE EXIT (SEL KEY)
The Programming Mode is exited by pressing the SEL key with
displayed. This will commit any stored parameter changes to memory and
return the meter to the Display Mode. (If power loss occurs before returning to
the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 and proceed through each module
in sequence. When programming is complete, it is recommended to record the
parameter programming and lock out parameter programming with the user
input or programming security code.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 3. This is useful
when encountering programming problems.
Pressing the RST key on power-up will load the factory settings and display
rESEt. This allows operation in the event of a memory failure or corrupted data.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will
appear. This is used to illustrate the display alternating between the parameter
on top and the parameter’s Factory Setting on the bottom. In most cases,
selections and values for the parameter will be listed on the right.
6.0 PROGRAMMING THE METER
Setpoint
Output
Parameters
Timer Input
Parameters
Pro
DISPLAY
MODE
Cycle Counter
Parameters
3-dSPLAY
Display and Front
Panel Key
Parameters
NO
SEL
RST
SEL SEL SEL SEL
2-Count
1-INPUt 4-SEtPt 5-SEriAL
SEL
Serial
Setup
Parameters
OVERVIEW
PROGRAMMING MENU
Indicates Program Mode Alternating Display
Factory Settings are shown.
Parameter
Selection/Value
LEVEL
INPUtsOP
5.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
SEL RST
1
KEY DISPLAY MODE OPERATION ENTERING PROGRAM MODE PROGRAMMING MODE OPERATION
SEL Select display (timer or cycle counter) Press and hold for 2 seconds to activate Store selected parameter and index to next parameter
RST Reset value(s) per Front Panel Reset setting Advances through the program menu
Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
“t” - To the left of the display is the timer value.
“C” - To the left of the display is the cycle counter value. “1” - To the upper left of the display indicates the setpoint status.
If display scroll is enabled, the display will toggle automatically every four seconds between the timer and cycle counter values.

Timer Input
Operation
Timer Input
Filter
Timer Run
State At
Power-up
Timing
Direction
Timer Start
Value
Flash Timer
Annunciator
Timer Reset
At Power-up
Timer
Range
SEL
RANGE INPUt OP FILtEr t-dir t-Strt t-FLASH
Run P-UP
RSt P-UP
1-INPUt Pro
USEr INP
User Input
Function
USEr ASN
User Input
Assignment
t-StOP
Timer Stop
Value
7
6.1 MODULE 1 - TIMER INPUT PARAMETERS (1-INPUt)
PARAMETER MENU
5555555
RANGE
This parameter determines how the Timer Input Signals affect the Run/Stop
status of the Timer. Timing diagrams are shown below for level active and edge
triggered (1-input or 2-input) operation. For single input modes (Input A only),
Input B provides a level active Timer Inhibit function. In the Display Hold
mode, the timer display value remains held and only updates when a Timer
Start (Input A) or Timer Stop (Input B) edge occurs.
The timer reset (rSt) operating modes are identical to the other modes in the
diagrams, except the timer display value is reset at the Time Start edges.
The Timer can also be stopped at a Timer Stop Value or at Setpoint output
activation or deactivation. This type of Stop condition is cleared when a Timer
Reset occurs, or another start edge is applied on the timer input.
For Reset Modes (rSt), the timer is reset at Time Start edge.
18 TIMER RANGE SELECTIONS
(S = SEC; N = MIN; H = HR; d = DAY))
TIMER RANGE
LEVEL
INPUtsOP
Level Active (Gated) Operation
INPUT A
INPUT B - Timer Inhibit (Level Active)
Time
Start
Time
Stop
Time
Start
Time
Stop
Edge Triggered Operation -1 Input
INPUT A
INPUT B - Timer Inhibit (Level Active)
Time
Start
Time
Stop
Time
Start
Time
Stop
Ed9E-1, Ed-1srSt
LEVEL, LEVsrSt
TIMER INPUT OPERATION
HHHHH.HH 99999.99 0.01 HR
HHHHHHH 9999999 1 HR
HHHHHH.H 999999.9 0.1 HR
HOURS
NNNNNN.N 999999.9 0.1 MIN
NNNNN.NN 99999.99 0.01 MIN
MINUTES
NNNNNNN 9999999 1 MIN
55555.55 99999.99 0.01 SEC
5555.555 9999.999 0.001 SEC
5555555 9999999 1 SEC
555555.5 999999.9 0.1 SEC
MAXIMUM
DISPLAY DISPLAY
RESOLUTION
RANGE
SELECTION
SECONDS
DAYS/HOURS/MINUTES
ddd.HH.NN 999.23.59 1 MIN
HHH.NN.SS 999.59.59 1 SEC
HOURS/MINUTES/SECONDS
HHHH.NN.N 9999.59.9 0.1 MIN
HHH.NN.NN 999.59.99 0.01 MIN
HOURS/MINUTES
HHHHH.NN 99999.59 1 MIN
NNN.SS.SS 999.59.99 0.01 SEC
NNNNN.SS 99999.59 1 SEC
NNNN.SS.S 9999.59.9 0.1 SEC
MAXIMUM
DISPLAY DISPLAY
RESOLUTION
RANGE
SELECTION
MINUTES/SECONDS
LEVsrSt
LEVEL
Ed-1srSt
Ed9E-1
HOLdsrSt
HOLd-2
Ed-2srSt
Ed9E-2
ON OFF
TIMING DIRECTION
Bi-directional timing capability. Select the timing direction desired for the
application.
0000000 to 9999999
ON
FILtEr
UP
t-dir
0000000
t-Strt
TIMER INPUT FILTER
Provides a 50 msec software debounce for the Timer Inputs (A and B). Select
ON when using relays or switch contacts as a signal source.
TIMER START VALUE
The Timer returns to this value whenever a Timer Reset occurs. The value is
entered in the same display format as the Timer Range selected. Non-zero
values are normally used for “timing down” applications, but they can also
provide an offset value when timing up.
Edge Triggered Operation - 2 Input
INPUT A
INPUT B
Time
Start
Time
Start
Time
Stop
Time
Stop
Edge Triggered Operation - 2 Input,
with Display Hold
INPUT A
INPUT B
Time Stop,
Display Update
Time Start,
Display Update
Time Start,
Display Update
Display
Update
HOLd-2, HOLdsrStEd9E-2, Ed-2srSt
dnUP
NO YES
FLASH TIMER ANNUNCIATOR
Select YES to have the timer annunciator (t) flash when the timer is running.
YES
t-FLASH
NO YES
TIMER STOP VALUE
The Timer stops when this value is reached regardless of the signal levels on
the timer inputs. Selecting YES displays a sub-menu where the Stop Value is
entered in the same display format as the Timer Range selected. This stop
condition is cleared when a Timer Reset occurs or another start edge is applied
on the timer input. Select NO if a Stop Value is not desired.
NO
t-StOP
StOP SAVE
TIMER RUN STATE AT POWER-UP
Determines the Run/Stop state of the Timer at Power-up. This parameter
does not apply to LEVEL Input Operation.
StOP - Timer Stopped at power-up, regardless of prior Run/Stop state
SAVE - Timer assumes the Run/Stop state it was in prior to power-down
StOP
RunsP-UP
0000000 to 9999999
0000000
StOP VAL

8
6.2 MODULE 2 - CYCLE COUNTER PARAMETERS (2-Count)
SEL
Cycle Counter
Count Source
Cycle Counter
Enable
Cycle Counter
Counting
Direction
Cycle Counter
Start Value
Cycle Counter
Reset At
Power-up
2-Count
Cnt Enb Cnt Src Cnt dir Cnt Strt RSt P-UP
Pro
PARAMETER MENU
CYCLE COUNTER ENABLE
When set to NO, the remaining Cycle Counter parameters are not accessible.
This parameter selects the source from which the Cycle Counter derives
counts. The Timer Reset (t-rESEt)selection generates a count when either a
manual or automatic timer reset occurs (See Module 4 for programming
Automatic Reset). The Input B (INPUt b) selection generates a count each time
Input B is activated. This selection overrides the timer inhibit function of Input
B, when the timer is programmed for Level or Edge-1 operating mode (See
Module 1 for Timer Input Operating Modes).
The User Input (USr1NP)selection generates a count each time the User Input
is activated. When selected as the count source, the User Input can still be set
to perform a User Function described in Module 1. In this case, the Cycle
Counter will count the number of times the selected User Function occurred.
The Output ON/OFF selections generate a count when the Setpoint output
either activates or deactivates. These selections will only generate counts when
an optional Setpoint module is installed.
CYCLE COUNTER COUNT SOURCE
t-rESEt
OUt-ON
OUt-OFF
INPUtsb
USrsINP
CYCLE COUNTER START VALUE
CYCLE COUNTER COUNTING DIRECTION
Bi-directional counting capability. Select the counting direction desired for
the application.
The Cycle Counter returns to this value whenever a Counter Reset occurs.
Non-zero values are normally used for “down counting” applications, but can
also provide an offset value when counting up.
UP dn
000000 to 999999
USER INPUT ASSIGNMENT
The User Input Assignment only applies if the cycle counter is enabled and
a selection of reset, display hold, hold and reset, inhibit, or print and reset is
selected in the User Input Function menu.
USER INPUT FUNCTION
USER INPUT FUNCTION (Cont’d)
MODEDISPLAY
No Function
NO
DESCRIPTION
User Input disabled.
Program Mode Lock-out
Pro Loc
Display Select
(Edge triggered)
d-SELECt Toggle display with each
activation.
Maintained Reset
rESEt Level active reset of the
selected value(s).
Display Hold
d-HOLd
Hold and Reset
HOLd-rSt Edge triggered reset of the
selected value(s) after
storing the time or count.
t-VALUE
C-VALUE
both t-C
See Programming Mode
Access chart (Module 3).
Freeze display for the selected
value(s) while allowing time or
counts to accumulate internally.
NO
USErsINP
t-VALVE
USErsASN
YES
CntsEnb
UP
Cntsdir
t-rESEt
CntsSrc
000000
CntsStrt
CYCLE COUNTER RESET AT POWER-UP
The Cycle Counter can be programmed to Reset at each meter power-up.
NO YES
NO
RStsP-UP
YESNO
NO YES
TIMER RESET AT POWER-UP
The Timer can be programmed to Reset at each meter power-up.
YES
RStsP-UP
Print Serial transmit of the active
parameters selected in the Print
Options menu (Module 5).
Print Request
r5t OUt
Prnt-r5t
Edge triggered deactivation of
the Setpoint Output.
Same as Print Request followed
by a momentary reset of the
selected value(s).
Reset Output
Print and Reset
Inhibit Inhibit timing or counting for the
selected value(s).
d-LEVEL Increase intensity one level
for each activation. (backlight
version only)
DISPLAY DESCRIPTION
Inhibit
Display Intensity Level
(Edge Triggered)
MODE

9
The yES selection allows the SEL button to toggle between the timer and cycle
counter displays.
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
6.3 MODULE 3 - DISPLAY AND FRONT PANEL KEY
P
ARAMETERS (3-dSPLAY)
SEL
Pro
Backlight Unit Only
Front Panel
Reset Enable
Front Panel
Display
Select
Display Scroll
Enable
Load Factory
Default
Settings
Display
Color
Programming
Security
Code
Display
Intensity
Level
3-dSPLAY
SEL Enb RSt Enb d-ScroLL d-COLOr d-LEVEL Pro CodE FACt SEt
PARAMETER MENU
The yES selection allows the RST button to reset the selected value(s). The
shaded selections only appear if the cycle counter is enabled.
FRONT PANEL RESET ENABLE (RST)
The yES selection allows the display to automatically scroll between the timer
and cycle counter values. The scroll rate is about every 4 seconds.
DISPLAY SCROLL ENABLE
Enter the desired display color, red or green. This parameter is active for
backlight units only.
DISPLAY COLOR (BACKLIGHT UNIT ONLY)
Enter the desired Display Intensity Level (1-5). The display will actively dim
or brighten as levels are changed. This parameter is active for backlight units only.
DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)
The Security Code determines the programming mode and the accessibility
of programming parameters. This code can be used along with the Program
Mode Lock-out (Pro Loc) in the User Input Function parameter (Module 1).
Two programming modes are available. Full Programming mode allows all
parameters to be viewed and modified. Quick Programming mode permits only
the Setpoint values and Timer Stop value to be modified, but allows direct
access to these values without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be entered
at the Pro CodE prompt in order to access Full Programming mode. Depending
on the code value, Quick Programming may be accessible before the Pro CodE
prompt appears (see chart).
PROGRAMMING SECURITY CODE
The yES selection will return the meter to the factory default settings. The
meter will display rESEt and then return to Pro, at which time all settings have
been changed.
Pressing the RST key on power-up will load the factory settings and display
rESEt. This allows operation in the event of a memory failure or corrupted data.
LOAD FACTORY DEFAULT SETTINGS
NOyES
C-VALUE
both t-C
dSPLAy
yES
NO
NO
t-VALUE
NOyES
6rnrEd
0to 999
yESNO
yES
SELsEnb
YES
RStsEnb
NO
d-ScroLL
rEd
d-COLOr
5
d-LEVEL
000
ProsCodE
MO
FACtsSEt
1to 5
USER INPUT
FUNCTION USER INPUT
STATE SECURITY
CODE FULL PROGRAMMING
MODE ACCESS
0Full Programming Immediate Access
not Pro Loc ______ 1-99 Quick
Programming
100-999 Pro CodE prompt With correct code entry at
Pro CodE prompt *
0Programming
Lock No Access
Active 1-99 Quick
Programming No Access
Pro Loc
100-999 Pro CodE prompt With correct code entry at
Pro CodE prompt *
Not Active 0-999 Full Programming Immediate Access
After Quick Programming
with correct code entry at
Pro CodE prompt *
MODE WHEN “SEL”
KEY IS PRESSED
* Entering Code 222 allows access regardless of security code.

10
SAVE will restore the output to the same state it was at before the meter was
powered down. ON will activate the output at power up. OFF will deactivate the
output at power up. This parameter is not active when the Setpoint Action is
selected for timed output mode.
SETPOINT OUTPUT POWER-UP STATE
Stops the Timer when the Setpoint output activates (OUt-ON) or deactivates
(OUt-OFF). Select NO if the output should not affect the Timer Run/Stop status.
The Timer Stop condition is cleared when a Timer Reset occurs, or a Time
Start edge is applied on the Timer input.
STOP TIMER
SETPOINT OUTPUT TIME-OUT
SPT ACTION DESCRIPTION OUTPUT ACTIVATES OUTPUT DEACTIVATES
LAtCH Latched Output Mode When Time or Count
= Setpoint On value At Manual Reset
(if SPt rSt = YES)
t-OUt Timed Output Mode When Time or Count
= Setpoint On value After Setpoint
Output Time-Out
ON-OFF On-Off Output Mode When Time or Count
Setpoint On value When Time or Count
Setpoint Off value
This parameter is only active if the Setpoint Action is set to Timed Output
mode (). Enter the time duration the Setpoint Output will remain ON once
it is activated. This value is always entered in minutes, seconds, and hundredths
of seconds format. The maximum value is 99 minutes 59.99 seconds.
00.00.01 to 99.59.99
SETPOINT ON
This parameter determines when the Setpoint output will activate. The output
can activate at a programmed Setpoint Value or can be set to activate when the
Timer starts (t-Strt) or stops (t-StOP).
Selecting VALUE displays a sub-menu where the Setpoint Value is entered. If
the Setpoint is assigned to the Timer, the value is entered in the same display
format as the selected Timer Range.
Automatically resets the Setpoint Assigned display value when the Setpoint
Output activates (OUt-ON) or deactivates (OUt-OFF). Select NO if the output should
not cause a display reset.
TIMER/COUNTER AUTO RESET
Select YES to have the Setpoint Output deactivate (reset) when the Setpoint
Assigned display resets. Reset can occur by the RST button or the User Input,
if programmed for that function. Select if the Setpoint output should not
reset when the display resets.
SETPOINT OUTPUT RESET WITH DISPLAY RESET
This parameter enables the backlight CUB5T to switch the display color when
the Setpoint output activates. When the output deactivates, the display color will
revert to the normal operating mode color. This parameter is only active for the
backlight version.
CHANGE DISPLAY COLOR w/SETPOINT OUTPUT STATE
00.01.00
SPtstOUt
VALUE
SPtsON
SETPOINT OFF
The Setpoint Off parameter only appears if the Setpoint Action is set to
On-Off Output mode (ON-OFF). In this mode, the Setpoint OFF parameter
determines when the Setpoint Output will deactivate. The output can be
programmed to deactivate at a Setpoint Off Value or can be set to deactivate
when the Timer starts (t-Strt) or stops (t-StOP).
Selecting VALUE displays a sub-menu where the Setpoint Off Value is entered.
If the Setpoint is assigned to the Timer, the value is entered in the same display
format as the selected Timer Range.
VALUE
SPtsOFF
OFF
SPtsP-UP
NO
StOP-t
NO
AUtOsrSt
YES
SPtsrSt
NO
Ch-COLOr
NO
Out-ON
Out-OFF
NOYES
YESNO
Out-OFF
Out-ON
NO
SAVE
ON
OFF
6.4 MODULE 4 - SETPOINT OUTPUT PARAMETERS (4-SEtPt)
SEL Backlight
Unit Only
Pro
Setpoint
Output Action
Setpoint
Assignment
Setpoint On Timer/Counter
Auto Reset
Setpoint Off Stop Timer
Setpoint
Output
Time-out
Setpoint
Output Reset
with Display Reset
Change Display
Color with
Setpoint Output
State
SPt ASN
4-SEtPt
SPt ACt SPt ON SPt OFF SPt tOUt StOP-t AUtO rSt SPt rSt Ch-COLOr
Setpoint Output
Power-up
State
SPt P-UP
PARAMETER MENU
The Setpoint Output Parameters are only active when the optional relay
module is installed in the meter. Some parameters will not appear depending on
the Setpoint Assignment and Setpoint Output Action selected.
Select the display for Setpoint assignment.
SETPOINT ASSIGNMENT
C-VALUEt-VALUE
t-VALUE
SPtsASN
SETPOINT OUTPUT ACTION
This parameter selects the action of the Setpoint output as shown below.
LAtCH
t-OUt
ON-OFF
LAtCH
SPtsACt
t-StOP
t-Strt
VALUE
t-StOP
t-Strt
VALUE
0000000 to 9999999
0000100
SPt VAL
0000000 to 9999999
0000200
SPOF VAL

11
DATA BIT
ABBREVIATED PRINTING
PRINT OPTIONS
PARITY BIT
METER ADDRESS
300 1200
600 2400
19200
38400
4800
9600
7-bit 8-bit
NO Odd EVEN
NO YES
NO YES
Module 5 is the programming module for the Serial Communications
Parameters. These parameters are used to match the serial settings of the
CUB5T with those of the host computer or other serial device. The Serial Setup
Parameters are only accessible when an optional RS232 or RS485 serial
communications module is installed in the meter.
This section replaces the bulletin shipped with the RS232 and RS485 serial
communications plug-in cards. Discard the separate bulletin when using those
serial plug-in cards with the CUB5T.
SEL
Data BitBaud Rate Parity Bit Print
Options
Meter
Address
Abbreviated
Printing
5-SEriAL
bAUd dAtA PAritY Addr Abbr Prnt OPt
Copy Program
Settings
COPY
Pro
6.5 MODULE 5 - SERIAL COMMUNICATIONS PARAMETERS (5-SEriAL)
PARAMETER MENU
BAUD RATE
Set the baud rate to match that of other serial communications equipment.
Normally, the baud rate is set to the highest value that all of the serial
communications equipment is capable of transmitting and receiving.
Select either 7- or 8-bit data word length. Set the word length to match the
other serial communications equipment on the serial link.
This parameter only appears when the Data Bit parameter is set to a 7-bit
data word length. Set the parity bit to match that of the other serial equipment
on the serial link. The meter ignores parity when receiving data and sets the
parity bit for outgoing data. If parity is set to NO, an additional stop bit is used
to force the frame size to 10 bits.
Enter the serial node address. With a single unit, an address is not needed
and a value of zero can be used (RS232 applications). Otherwise, with multiple
bussed units, a unique address number must be assigned to each meter. The
node address applies specifically to RS485 applications.
This parameter determines the formatting of data transmitted from the meter
in response to a Transmit Value command or a Block Print Request. Select NO
for a full print transmission, consisting of the meter address, mnemonics, and
parameter data. Select YES for abbreviated print transmissions, consisting of the
parameter data only. This setting is applied to all the parameters selected in the
PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent
during a full transmission.)
9600
bAUd
7-bit
dAtA
Odd
PAritY
00
Addr
NO
Abbr
NO
Prnt OPt
0to 99
This parameter selects the meter values transmitted in response to a Print
Request. A print request is also referred to as a block print because more than
one parameter can be sent to a printer or computer as a block.
Selecting YES displays a sublist for choosing the meter parameters to appear
in the print block. All active parameters entered as YES in the sublist will be
transmitted during a block print. Parameters entered as NO will not be sent.
The “Print All” (Prnt ALL) option selects all meter values for transmitting
(YES), without having to individually select each parameter in the sublist.
Note: Inactive parameters will not be sent regardless of the print option
setting. For example, the Cycle Counter and Cycle Counter Start values will
only be sent when the Cycle Counter is enabled. If disabled, these parameters
are inactive and will not be transmitted. Likewise, the Setpoint parameters will
not be sent unless an optional setpoint card is installed in the meter.
DISPLAY MNEMONIC
t-VALUE Timer YES TMR
C-VALUE Cycle Counter NO CNT
t-StOP
t-Strt
Timer Stop
Timer Start
NO
NO
TSP
TST
Cnt Strt NO CST
SPt ON NO SPT
SPt tOUt
SPt OFF
Setpoint Time-out
Setpoint OFF
NO
NO
STO
SOF
DESCRIPTION FACTORY
SETTING
Counter Start
Setpoint ON

Command String Construction
The command string must be constructed in a specific sequence. The meter
does not respond with an error message to illegal commands. The following
procedure details construction of a command string:
1. The first 2 or 3 characters consist of the NodeAddress Specifier (N) followed
by a 1 or 2 character node address number. The node address number of the
meter is programmable. If the node address is 0, this command and the node
address itself may be omitted. This is the only command that may be used in
conjunction with other commands.
2. After the optional address specifier, the next character is the command
character.
3. The next character is the register ID. This identifies the register that the
command affects. The P command does not require a register ID character. It
prints all the active selections chosen in the Print Options menu parameter.
4. If constructing a value change command (writing data), the numeric data is
sent next.
5. All command strings must be terminated with the string termination
characters * or $. The meter does not begin processing the command string
until this character is received. See timing diagram figure for differences in
meter response time when using the * and $ terminating characters.
Command String Examples:
1. Node address = 17, Write 350 to the Setpoint On value
String: N17VF350$
2. Node address = 5, Read Timer value, response time of 50 msec min
String: N5TA*
3. Node address = 0, Reset Setpoint output
String: RF*
4. Node address = 31, Request a Block Print Output, response time of 2 msec min
String: N31P$
Transmitting Data to the Meter
Numeric data sent to the meter must be limited to Transmit Details listed in the
Register Identification Chart. Leading zeros are ignored. The meter ignores any
decimal point and conforms the number to the appropriate display format. (For
example: The Timer range is set for tenths of a second and 25 is written to the
Timer Start register. The value of the register is now 2.5 seconds. In this case,
write a value of 250 to equal 25.0 seconds).
Note: Since the meter does not issue a reply to value change commands, follow
with a transmit value command for readback verification.
12
Sending Serial Commands and Data
When sending commands to the meter, a string containing at least one
command character must be constructed. A command string consists of a
command character, a value identifier, numerical data (if writing data to the
meter) followed by a command terminator character, * or $.
Command Chart
Register Identification Chart
ID Value Description MNEMONIC Transmit Details (T and V)
A Timer TMR 7 digit, per Timer Range
BCycle Counter CNT 6 digit
D
C
Timer Stop
Timer Start
TSP
TST
7 digit, per Timer Range
7 digit, per Timer Range
ECounter Start CST 6 digit
FSetpoint ON
(Reset Output) SPT per Setpoint Assignment,
same as Timer or Counter
H
G
Setpoint
Time-out
Setpoint OFF
STO
SOF
6 digit, mm.ss.ss format
per Setpoint Assignment,
same as Timer or Counter
T, V, R
T, V, R
T, V
T, V
T, V
T, V, R
T, V
T, V
Receiving Data From The Meter
Data is transmitted from the meter in response to either a transmit command
(T), a block print request command (P) or a User Input print request. The
response from the meter is either a full field transmission or an abbreviated
transmission, depending on the selection chosen in Module 5.
Full Field Transmission
* These characters only appear in the last line of a block print.
The first two characters transmitted are the meter address. If the address
assigned is 0, two spaces are substituted.Aspace follows the meter address field.
The next three characters are the register mnemonic, as shown in the Register
Identification Chart.
The numeric data is transmitted next. The numeric field (bytes 7 to 18) is 12
characters long. When a display overflow exists for a requested timer or cycle
counter value, an * (used as an overflow character) replaces a space in byte 7.
Byte 8 is always a space.
The remaining ten positions of this field consist of seven positions for the
requested value with decimal points positioned for the selected timer range. The
data within bytes 9 to 18 is right-aligned with leading spaces for any unfilled
positions.
The end of the response string is terminated with a <CR> and <LF>.After the
last line of a block print, an extra <SP>, <CR> and <LF> are added to provide
separation between the print blocks.
Abbreviated Transmission
* These characters only appear in the last line of a block print.
The abbreviated response suppresses the node address and register mnemonic,
leaving only the numeric part of the response.
Meter Response Examples:
1. Node address = 17, full field response, Cycle Counter = 875
17 CNT 875 <CR><LF>
2. Node address = 0, full field response, Setpoint On value = 250.5
SPT 250.5<CR><LF>
3. Node address = 0, abbreviated response, Setpoint On value= 250, last line of
block print
250<CR><LF><SP><CR><LF>
Byte Description
1, 2 2 byte Node Address field [00-99]
3<SP> (Space)
4-6 3 byte Register Mnemonic field
7-18
19 <CR> (carriage return)
20 <LF> (line feed)
21 <SP>* (Space)
22 <CR>* (carriage return)
23 <LF>* (line feed)
Byte Description
1-12 12 byte data field, 9 bytes for number and three bytes for
decimal points
13 <CR> (carriage return)
14 <LF> (line feed)
15 <SP>* (Space)
16 <CR>* (carriage return)
17 <LF>* (line feed)
12 byte data field; 9 bytes for number and three bytes for decimal
points
Applicable
Commands
Initiates a block print output. Registers in the
print block are selected in Print Options.
Block Print Request
(read)
P
Reset a value or the output. Must be followed
by a register ID character
ResetR
Write to register of the meter. Must be
followed by a register ID character and
numeric data.
Value Change (write)V
Read a register from the meter. Must be
followed by a register ID character.
Transmit Value (read)T
Address a specific meter. Must be followed by
one or two digit node address. Not required
when node address = 0.
Node (meter)
Address Specifier
N
NotesDescriptionCommand

13
Command Response Time
The meter can only receive data or transmit data at any one time (half-duplex
operation). During RS232 transmissions, the meter ignores commands while
transmitting data, but instead uses RXD as a busy signal. When sending
commands and data to the meter, a delay must be imposed before sending
another command. This allows enough time for the meter to process the
command and prepare for the next command.
At the start of the time interval t1, the computer program prints or writes the
string to the com port, thus initiating a transmission. During t1, the command
characters are under transmission and at the end of this period, the command
terminating character (* or $) is received by the meter. The time duration of t1
is dependent on the number of characters and baud rate of the channel.
t1= (10 times the # of characters) / baud rate
At the start of time interval t2, the meter starts the interpretation of the
command and when complete, performs the command function. This time
interval t2varies. If no response from the meter is expected, the meter is ready
to accept another command.
If the meter is to reply with data, the time interval t2is controlled by the use
of the command terminating character. The ‘*’ terminating character results in
a response time of 50 msec. minimum. This allows sufficient time for the
release of the sending driver on the RS485 bus. Terminating the command line
with ‘$’results in a response time (t2) of 2 msec. minimum. The faster response
time of this terminating character requires that sending drivers release within 2
msec. after the terminating character is received.
At the beginning of time interval t3, the meter responds with the first
character of the reply. As with t1, the time duration of t3is dependent on the
number of characters and baud rate of the channel. At the end of t3, the meter is
ready to receive the next command.
t3= (10 times the # of characters) / baud rate
The maximum serial throughput of the meter is limited to the sum of the
times t1, t2and t3.
Ready Ready
1
t t2
Ready t1t2Ready
t3
Command
String
Transmission
Meter
Response
Time
Command
Terminator
Received
First
Character
of Reply
Reply
Transmission
NO REPLY FROM METER
RESPONSE FROM METER
Time
Timing Diagram Figure
Communication Format
Data is transferred from the meter through a serial communication channel.
In serial communications, the voltage is switched between a high and low level
at a predetermined rate (baud rate) using ASCII encoding. The receiving device
reads the voltage levels at the same intervals and then translates the switched
levels back to a character. The voltage level conventions depend on the interface
standard. The table lists the voltage levels for each standard.
Data is transmitted one byte at a time with a variable idle period between
characters (0 to ). EachASCII character is “framed” with a beginning start bit,
an optional parity bit and one or more ending stop bits. The data format and
baud rate must match that of other equipment in order for communication to
take place. The figures list the data formats employed by the meter.
Start Bit and Data Bits
Data transmission always begins with the start bit. The start bit signals the
receiving device to prepare for reception of data. One bit period later, the least
significant bit of the ASCII encoded character is transmitted, followed by the
remaining data bits. The receiving device then reads each bit position as they are
transmitted.
Parity Bit
After the data bits, the parity bit is sent. The transmitter sets the parity bit to
a zero or a one, so that the total number of ones contained in the transmission
(including the parity bit) is either even or odd. This bit is used by the receiver
to detect errors that may occur to an odd number of bits in the transmission.
However, a single parity bit cannot detect errors that may occur to an even
number of bits. Given this limitation, the parity bit is often ignored by the
receiving device. The CUB5T meter ignores the parity bit of incoming data and
sets the parity bit to odd, even or none (mark parity) for outgoing data.
Stop Bit
The last character transmitted is the stop bit. The stop bit provides a single bit
period pause to allow the receiver to prepare to re-synchronize to the start of a
new transmission (start bit of next byte). The receiver then continuously looks
for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2
stop bits are sent from the meter.
Character Frame Figure
LOGIC RS232* RS485*INTERFACE STATE
1TXD,RXD; -3 to -15 V a-b < -200 mVmark (idle)
0TXD,RXD; +3 to +15 V a-b > +200 mVspace (active)
* Voltage levels at the Receiver

14
This page intentionally left blank.

15
RST
Backlight Unit Only
Exit
Programming
SEL
SEL
SEL
SEL
SEL
RST
RST
RST
RST
SEL
RST
Backlight
Unit Only
Timer Start
Value
Timer Input
Filter
Timer Input
Operation
Timer
Range
Timing
Direction
User Input
Function
Timer Run
State At
Power-up
Flash Timer
Annunciator
Timer Reset
At Power-up
User Input
Assignment
Timer Stop
Value
1-INPUt
Cnt dir
Cycle Counter
Counting
Direction
Cycle Counter
Count Source
Cycle Counter
Enable
Cnt Enb Cnt Src
2-Count Cnt Strt
Cycle Counter
Start Value
Cycle Counter
Reset at
Power-up
RSt P-UP
Display Scroll
Enable
RSt Enb
Front Panel
Reset Enable
Front Panel
Display
Select
SEL Enb d-ScroLL
3-dSPLAY Pro CodE
Programming
Security
Code
d-LEVEL
Display
Intensity
Level
Display
Color
d-COLOr
Load Factory
Default
Settings
FACt SEt
4-SEtPt
End
NO
Pro
Meter
Address
Addr
5-SEriAL
Data Bit
bAUd
Baud Rate
dAtA
Parity Bit
PAritY Prnt OPt
Print
Options
Abbr
Abbreviated
Printing
SPt tOUt
Setpoint
Output
Time-out
SPt ON
Setpoint OnSetpoint
Output Action
SPt ACt
Setpoint Off
SPt OFF Ch-COLOr
Change Display
Color with
Setpoint Output
State
AUtO rSt
Timer/Counter
Auto Reset
Stop Timer
StOP-t
Setpoint
Output Reset
with Display
Reset
SPt rSt
Setpoint Output
Power-up
State
SPt P-UP
SPt ASN
Setpoint
Assignment
t-Strt
RANGE FILtEr
INPUt OP t-dir USEr INP
Run P-UP
t-FLASH RSt P-UP USEr ASN
t-StOP
CUB5T PROGRAMMING QUICK OVERVIEW
Press and hold SEL key to
enter Programming Mode.

LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship
for a period limited to two years from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
herein and relies on no other warranties or affirmations.
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350
This manual suits for next models
4
Table of contents
Other Red Ion Timer manuals