
INSTRUCTION MANUAL
Model: RWB2
Red Wireless Base V2
SMOKE ALARMS
Specifications:
Main Power Source 220-240V ac, 50 Hz
Secondary Power Source 3V Sealed Lithium battery
Operating Current ≤40 mA
Temperature Range 0 °C to 45 °C
Humidity Range 5% to 95%
Interconnecting 40 alarms for wireless
40 alarms over 150 metres maximum
Transmit Frequency 433.92 MHz
RF Range 100 m free air
30 m indoors (line of sight)
Terminals Active, Neutral, Loop and Interconnect
terminals each accommodates 2×1.5 mm
Pairing duration 2.5 min (recount after each success pairing)
Visual Indicators Red LED for warning and low battery
indication
Approval AS4268
Product Description
• The Red Wireless Base is a wireless cable/ conduit mounting
base, which is suitable for use with Red Smoke Alarms R240 and
R240RC 240V smoke alarms.
• Not compatible with 3rd party products, systems or fire panels.
• Not compatible with model R10 and R9.
• Wirelessly interconnect with the RF Lithium Battery powered
smoke alarm R10RF.
• This product must be installed by a licensed electrician. Failure to
install correctly can result in a fatal shock or fire hazard.
Feature
• Two side knockout for easy cable or conduit surface mount, the
knockout space is 20x22mm.
• One internal knockout for ceiling internal mount, the knockout
space is 17x42mm.
• RF Pairing Chips with a RF Pairing Button at side
• A plastic cover is provided to prevent any exposure of cables and
wires.
IMPORTANT - EQUIPMENT INSTALLATION
HAZARD
• Only install indoors.
• All interconnected smoke alarms (max 40) must be supplied from
the same interconnection. A common Neutral must be from the
same interconnection. A common Neutral must be used for the
interconnect to operate.
• DO NOT connect the interconnect wire to Active or Neutral.
WARNING: Failure to follow these instructions may result in
equipment damage or injury.
Wireless Connection Setup Guide:
1. Complete installation and turn on the mains power supply.
2. Select one of the wireless bases as the MASTER unit. place the
MASTER label near the wireless self-pairing button. Treat all other
units as BRANCH units.
3. On the MASTER wireless bases, by hand, press and hold the
wireless self-pairing button for 5 seconds. The unit is now in
self-learn pairing mode indiciated by the LED remaining on for 2.5
minutes.
NOTE: To exit self-learn pairing mode, press the wireless self-pair-
ing button one time. The Red LED will turn off.
4. While the MASTER unit’s LED is on, pair the BRANCH units by
pressing their wireless self-pairing button 2 time squickly (within a
second). The BRANCH unit’s LED will flash 5 times indiciating
successful interconnection.
NOTE: If a BRANCH UNIT does not flash its LED 5 times, the
wireless connect has failed. In this case, check that the MASTER
unit’s LED remains ON and is still in self pairing mode while pairing
the BRANCH unit. Make sure only one unit is the MASTER, and all
others are subordinate BRANCH. Previously paired unit do not have
to be paired again if activating master self-pairing mode again.
Hardwire Installation & Interconnect Guide:
WARNING: First disconnect the mains from the circuit to be used.
1. Remove the plastic cover by using a screwdriver to loosen both
of the security screws.
2. Remove the two side knockout for cable or conduit surface
mount, or remove the internal knockout for ceiling internal mount.
3. Screw the mounting base to the ceiling and bring the house wires
through it.
4. Connect the house wires to the terminal block on the mounting
base.
5. Repeat step 4 on all other BRANCH units.
6. After all units has been paired, exit self-pairing mode on the
master unit, then press and hold the MASTER unit’s Test/Hush
button until all other wireless RF interconnect units alarm sound (all
units may take some time to sound.)
Cable
Entry
Hinge
RF Pairing
Button
Latch
Ceiling Screw
Hole
Plastic Cover
Phillips Head
Security Screws
Mounting Base
Knockout
Knockout
Fig.1
RF Pairing Button
Fig.3
LED INSIDE HOUSING
ILLUMINATES WHILE
BUTTON IS PRESSED
Mounting Base: Ø130mm 36.5mm
Electrical terminal index:
A: Active / Line
E/LOOP: Earth or Loop
N: Neutral
I: Interconnect
Fig.4
Active
Neutral E/loop
Interconnect
Cable
WARNING: Never hardwire the
Live/Neutral to the interconnect
terminal as this will damage the
alarm device.
WARNING: Never use E/loop
wire for interconnect wiring.
Fig.2
Refer to the manual for more details on the correct circuit wiring.
5. Cover all the wires with the plastic cover, use a screwdriver to
tighten the plastic cover with the security screws.
6. Clip the Red Smoke Alarm main unit to the hinge of the mounting
base and lock the unit by clipping the latch.