manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Redback
  6. •
  7. Measuring Instrument
  8. •
  9. Redback A 4567A User manual

Redback A 4567A User manual

Doc PS1398
Page 1
The A 4567A is a line monitoring unit or LMU. An
LMU monitors the condition of 100V PA speaker
lines and alerts you if there is a problem with the
wiring.
The A 4567A comes standard with ten separate
zones that have individual LEDs to indicate the
condition of the Line.
Features
• Up to 10 zones monitored
• LED’s to indicate condition of the Line
• Loud alert sound if there is a fault
• Separate rear outputs for the condition LED’s
Installing the A 4567A LMU
The A 4567A can be powered by a 240Vac or
24Vdc. Terminals on the rear are supplied for both.
Hook up the 100V PA amplifier/s to the inputs on
the rear. All the inputs are isolated from each other
so up to 10 amplifiers can be used or any
combination below that number e.g. one amplifier
connected to 2 or more inputs. NEVER connect 2 or
more amplifiers to one zone it will cause major
damage to the A 4567A and the amplifiers.
The output terminals can now be connected to
the speaker lines. A maximum of 500 Watts of load
per zone is allowed. Any more than this will damage
the A 4567A. Any number of 100V line transformer
/ speaker combinations can be used as long as the
total load for each zone is below 500 Watts.
Setting up the speaker runs so they work with the
A 4567A is as easy as installing a 22uf BP capacitor
at the input of each transformer / speaker (please
see figure 3). Install an end of line resistor or EOL at
the very end of the wiring run before the final
transformer / speaker. The end of line resistor must
be 100K Ohm in value and at least .25 Watt or
above. Unused outputs from the A 4567A need to
have a EOL resistor installed across positive and
negative terminals. If these are not installed the
A 4567A will bring up a fault condition for the non
EOL terminated zones.
Powering up the A 4567A
When the A 4567A is powered up the unit then
pauses for about 10 seconds to allow the protected
zones to be checked for the condition they are in.
If there is a fault the A 4567A will alert you with a
loud pulsing beep and the Cancel switch LED will
flash. A short on a zone is indicated on the front
panel by a red LED. An open condition on a zone
will be indicated on the front panel by a yellow LED.
If there are no faults detected, all zones will indicate
good condition with a green LED.
If the A 4567A goes into alarm mode and the
beeping is heard it can be stopped by pushing the
CANCEL button. The fault LED indicators will remain
on until the fault on the zone is corrected. Any new
fault conditions will result in the alarm tone
sounding again and the Cancel switch LED to flash.
From then on no matter how many times the
cancel button is pushed the A 4567A will go into
alarm mode any time there is a new fault condition
on any of the zones. The alarm will not sound again
if a zone goes from a fault (open or short) condition
to good condition.
Remote monitoring of faults
The fault status of the zones can be monitored
remotely by connecting an external buzzer or
warning light to 24Vdc switched outputs. There are
three switched outputs.
One for an open condition, another for a short
condition and a third for either a short or open
circuit condition (combined out). All three outputs
switch 24Vdc in either failsafe or normal mode.
Fault Finding
The A 4567A does not power up: Check that
power is applied to the unit either by a 240Vac or
an external 24V dc source.
Unit continues to go into alarm mode and emits
a loud continuous beep: Push the cancel button
and check the LED display. See which zone is
causing the problem (if all zones are showing
“normal” the buzzer will not sound continuously).
The SHORT LED is coming up on a zone: First
check and see if you have installed the 100K EOL
resistor at the end of the line and the 22uf BP
capacitors on each of the transformer / speakers
that are installed on that line (see Fig.3). If they are
all installed there must be a short across the line,
once removed the A 4567A will go into NORMAL.
The OPEN LED is coming up on a zone: First
check and see if you have installed the 100K EOL
Resistor at the end of the line and the 22uf BP
Capacitors on each of the transformer / speakers
that are installed on that line (see Fig 3.). If they are
all installed there must be a break in the line, once
this is removed the A 4567A will go into NORMAL.
®
10 Zone Line Monitoring Unit
REDBACK A 4567A Line Monitoring Unit
Redback A 4567A Line Monitoring Unit
Page 2
Doc GL835
Fig 1. Rear Panel Legend
1 240V ac Input
2 24V dc Input
3 Connectors (Zones 1 - 10)
Figure 1: A 4567A rear panel
3
21
Fig 2. Front Panel Legend
1 Zone Indicators 1-10
2 Piezo Buzzer
3 Cancel Button
4 Power Led
5 Power Switch
12 3 4 5
Figure 2: A 4567A front panel
Out
+
In
+
-
+
-
+
-
+
Fig. 3 Connection Details
Max Load, 500W per zone. Unused zones must have 100k 0.25W end of
line resistor installed. Max wire run, 200m.
Amplifier
22uf capacitors
100K 0.25W end
of line resistor.
Note: Speakers on any zone must
be wired in a ‘loop in’ ‘loop out’
configuration. ‘Star’ wiring on ‘tee
offs’ are not permitted and will
cause the system to go into
alarm.

Other Redback Measuring Instrument manuals

Redback Q 2003 User manual

Redback

Redback Q 2003 User manual

Redback A 4567C User manual

Redback

Redback A 4567C User manual

Redback Q 2004 User manual

Redback

Redback Q 2004 User manual

Redback Q 2012 User manual

Redback

Redback Q 2012 User manual

Redback A 4567 User manual

Redback

Redback A 4567 User manual

Redback A 4567B User manual

Redback

Redback A 4567B User manual

Redback Q 2007 User manual

Redback

Redback Q 2007 User manual

Redback RS40k User manual

Redback

Redback RS40k User manual

Popular Measuring Instrument manuals by other brands

Kobastar WEI user manual

Kobastar

Kobastar WEI user manual

HT I-V400w-SOLAR I-Vw user manual

HT

HT I-V400w-SOLAR I-Vw user manual

Niigata seiki WCDI-50D instruction manual

Niigata seiki

Niigata seiki WCDI-50D instruction manual

Zolix Instruments Omni-l200i Series Operation manual

Zolix Instruments

Zolix Instruments Omni-l200i Series Operation manual

UE Systems ULTRAPROBE 10000 Pumps and Cavitation Inspection

UE Systems

UE Systems ULTRAPROBE 10000 Pumps and Cavitation Inspection

Phynix SURFIX PRO X instruction manual

Phynix

Phynix SURFIX PRO X instruction manual

PCB Piezotronics 3503A1160KG Installation and operating manual

PCB Piezotronics

PCB Piezotronics 3503A1160KG Installation and operating manual

Ecom DP Operation manual

Ecom

Ecom DP Operation manual

Agilent Technologies L4532A Series Service guide

Agilent Technologies

Agilent Technologies L4532A Series Service guide

Megger Fault Sniffer 2 operating manual

Megger

Megger Fault Sniffer 2 operating manual

NeuroTek Elite Series quick start guide

NeuroTek

NeuroTek Elite Series quick start guide

Ultraflux MiniSonic P manual

Ultraflux

Ultraflux MiniSonic P manual

dallmeier DLS 4 Operation manual

dallmeier

dallmeier DLS 4 Operation manual

Monroe Electronics Digital Stat-Arc 2 Operator's manual

Monroe Electronics

Monroe Electronics Digital Stat-Arc 2 Operator's manual

EXFO LTK-1 user guide

EXFO

EXFO LTK-1 user guide

Klein Tools ET160 instruction manual

Klein Tools

Klein Tools ET160 instruction manual

Agilent Technologies 4339B user guide

Agilent Technologies

Agilent Technologies 4339B user guide

Nidec DT-105A Operation manuals

Nidec

Nidec DT-105A Operation manuals

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.