Refine Wh100 User manual

Refine Wh100
USER MANUAL
NO.10 Yanshan Road, Beilun,
Ningbo, Zhejiang, China.
sales@refineindustry.com
support@refineindustry.com
www.refineindustry.com

1
How it Works
Installation Requirements
Installation
Electrical Requirements
Water (Condensate) Removal
Ducted Applications
Unita Diagram
Maintenance
Dehumidifier Storage
Specifications
Troubleshooting
Remote Control Instructions
Spare Parts
10
8
7
6
6
5
4
4
4
3
2
2
2

2 3
Capacity@80℉/60%RH:120PintsPerDay
Operating Relative Humidity Range: 36%-90%
Amperage Usage: 7.6 Amps
Sound Level: 60 dBa
Airflow @ 0.0” SP: 300CFM
COP: 2.8 L/kWh
Power Supply: 115V/60Hz/Single Phase
Dimensions LxWxH: 23.75” x 14” x 16”
Operating Temp. Range: 33-105°F
Refrigerant: R410A
Outlet Requirement: 15 Amp, 3 Prong, GFCI
ETL Listed: Yes
Specifications
Howitworks
Unipdry dehumidifiers use an integrated humidistat to monitor the conditioned
space. When the relative humidity goes above the selected setpoint, the
dehumidifier will energize. Air is then drawn across an evaporator coil, which is
cooler than the dew point of air. This means moisture will condense out of the air.
The air is then reheated through the condenser coil and distributed back into the
room.
Installation
Installation Requirements
If the unit is installed in a crawl space, all vents should be sealed.
The area where the dehumidifier is located should be sealed with a vapor
barrier.
For the best air diffusion, install the unit so that a side panel faces the wall.
For proper ventilation, neither the inlet or discharge should be positioned
against a wall. The inlet needs a minimum of 12” clearance and the discharge
requires a minimum of 36” clearance.
Unipdry dehumidifiers are only intended for operation when the unit
is upright and level with the feet on the ground (unless using a Unipdry
Hanging Kit).
Location
The good thing with this device is that its location is versatile. It can be installed in a
variety of areas to ensure that the installer meets the client’s needs. But still, the
following aspects should be considered:
The location chosen should provide steady access to 10” power cord and a 115 VAC
power outlet.
It should be located near a suitable drain or floor. An 8’ drain hose is provided to help
boost drainage.
The device should be mounted 4” above the drain.
The unit should never be located very close to open water.
Also, ensure that you avoid any possible obstruction to the air inlet and exhaust. Give it at
least one foot for aeration.
•
•
•
•
•
The simplest form of installation is to place the unit in a space where ducting is not too necessary.
Recirculation will promote the speed at which the gadget works. Recirculation of air into the inlet
could damage the unit system.
Duct Supply and Return
In order to promote the rate at which dehumidification occurs, you can add the supply and/or
return duct to help circulate air. You can make use of the return duct to draw moist and warm air
from the near ceiling in order to obtain optimal drying. In a simpler remote installation procedure,
you can make use of the humid room and the Uni-P discharge room. The Uni-P dehumidifier inlet
usually draws air from the room where it is installed. For that reason, this installation procedure
works well if the unit is installed in a room that has got adequate air flow. Such rooms may
include rooms with the wall grill, louvered doors, and/or high door undercut. Such conditions
promote airflow and hence, eliminates the requirement to remote mount the humidity controller.
Warning: it is important that you first seek guidance from a qualified device operator before you
opt to use the device as described above. The experts will provide you with instructions on how
to complete the procedure. If backdraft devices are such as the hot water heater are present in
the place that needs to be dehumidified, it is important that the manufacturer or certified service
provider completes the installation.
It may be necessary to slightly pressurize and/or dehumidify the room if the dehumidifier is to be
located in a smaller room that is separate from the main area that requires dehumidification. The
purpose of pressurization is to make sure that any open combustion devices present in the room
do not backdraft. Backdraft can be prevented by simply allowing the Uni-P dehumidifier to
release dehumidified air into the room where it is located. It can also be prevented by installing a
circulation pipe from the humid room into the dehumidifier inlet. All in all, there should be
adequate air circulation between the two rooms for this procedure to work well.

4 5
Electrical Requirements
Normally, the CoAiro dehumidifier plugs into one major grounded outlet on a relatively 110 to
120 VAC 15 Amp circuit. In some cases the use of the GFCI (Ground Fault Circuit
Interrupter) is advisable. The unit, however, is not suitable for areas affected by flooding too
much rainfall.
Caution: in order to maintain proper drainage, it is advisable that you raise the unit high
enough such that the outlet of the drain is at least 4” above the floor. Also, it must be fully
supported under the base.
When fixing the drain hose it is important to ensure that the feet are extended in a way that
the device is raised two and a half feet from the ground. After the hose gets in contact with
the ground, ensure that you coil the drain hose beneath itself or try to position a spacer to
help lift the hose at least one feet from the ground. This way the process will create a trap
that helps to ensure that the unit drains well.
Water (Condensate) Removal
You can condensate the drains easily by gravity through the drain port. Use 0.75” male PVC
NPT pipe. Also, route every single drain to drain. If possible install a trap. All in all, be careful
when installing the drain pipe to the drain port. You can make use of an adjustable wrench to
protect the drain port from damage. An optional water removal pump kit may be fixed if a lift
is needed to dispose of the water. You can contact the company if you would like to order a
pump kit.
• Be sure to secure the ducting with tie wrap.
• Maximum total length of duct run = 10’
• Inlet and outlet duct adapters are optional accessories
Duct Adapter Installation
• Screw in the 4 screws on each duct
adapter.
Flex Duct Installation
• Slide ducting over adapter
and secure with tie wrap or
clamps
Ducted Applications
Ducting the dehumidifier allows the unit to be in one room while
conditioning an adjacent room. Both the inlet/return grille and the supply
grille are designed for 10” flex ducting
Unit Diagram
Handle
Side Panel
Filter Cover
Pre-Filter
Discharge Grille
Power Cord
Auxiliary Terminals
Drain Hose
Connection

6 7
Maintenance
**For more detailed instructions, visit www.unipdry.com**
WARNING: Always unplug the unit before doing any maintenance.
Cleaning the Machine Body
• Use a soft, damp cloth to clean the exterior of unit. Do not use any
soap or solvents
Coil Maintenance
Once per year, clean the coils with an approved coil cleaner. Thecoil cleaner should be a self-rinsing,
foaming, cleaner, such asWEB® Coil Cleaner.
Cleaning the Filter
1. Unplug the unit.
2. For PreFilter:
a. Remove prefilter from inlet of machine.
b. Vacuum or wash with warm water (no soap).
3. For MERV-10/HEPA/Carbon Filters:
a. Replace as necessary- we recommend checking the filters
at least 1x/year
Electrical Access
• Unscrew the 13 screws on the side panel.
• Remove the screw on the
control board cover.
Dehumidifier Storage
If the unit will be stored for an extended period of time, complete the
following steps:
1. Turn off the unit and allow it to dry.
2. Complete steps 1-3 in Advanced Pump Cleaning to clean out the
pump reservoir.
3. Wrap and secure the power cord.
4. Cover the filter mesh.
5. Store in a clean, dry space.
Troubleshooting
Display is Blank
No Airflow
Error Code:E1
Error Code:E4
Error Code:LO
Error Code:HI
Tripped GFCI
Outlet or Breaker
Cause Solution
Poor Connection
Power Outage
Filter is dirty
Air Inlet or Outlet
is Blocked
Humidity Sensor or
Communication Error
Problem with Pump
Room Temperature
is below 33℉
Room Temperature
is above 105℉
Not a Dedicated Circuit
Defective GFCI Outlet
Dirt, Dust, or
Moisture on Outlet
Lightning or Externa
Electrical Surge
Possible Dehumidifier
Issue
Verify that both ends of the
cord are plugged in
Resetpower
Clean the Filter
Clean theblockage
Check to ensure that the sensor wire
is connected at both ends. if no issues
are visible, the sensor may be faulty.
Verify that the pump is properly
installed and functioning. If so, unplug
the unit for two minutes,then restart.
Increase the room temperature so it is
within operating range (above 33℉). If
error still displays, check sensor.
Decrease the room temperature so it is
within operating range (below 105℉).
If error stille displays, check the
sensor
Identify all sources connected to outlet
and confirm source of trip.If it is
dehumidifier, contact technical
support. If not, move dehumidifier to
dedicated circuit for future use.
Replace Outlet
Clean or Replace Outlet as necessary
Reset or Replace Breaker/GFCI, as
necessary
If none of above options work, contact
technical support
Symptom

8 9
Remote Control Instructions
Unipdry Dehumidifiers can be controlled using an optional remote accessory. The remote
connects to your dehumidifier via a 25’ CAT 5 cable, with the integrated sensor giving you
multiple options for monitoring surrounding conditions.
Example #1- Install the dehumidifier in the laundry room and duct it into the living room.
Mount the remote in the living room and use the remote sensor.
Example #2- Install the dehumidifier in your crawl space with the remote mounted in
your garage.
NOTE: The symbols indicated below only
show when the remote is powered on.
1.On/Off (Power) Button
Press the on/off button and the machine
will start running. Press the button again
to turn the machine off.
2.Up Button/ Down Button
Use the up and down arrows to
adjust the humidity level.
3.Mode
Use the mode button to switch between dehumidifier and a ductedapplication.
• The symbol on the display indicates the sensor on the remote
control is being utilized.
• The symbol on the display indicates the sensor on the dehumidifier
is being utilized.
4. Temperature
The T button changes the temperature reading on your remote. Theremote comes from the
factory in Celsius. Press this button once toswitch to Fahrenheit.
5. Continuous
Press this button to switch the unit into continuous mode. “CONT.” willappear on the
display screen.
6. Drain Pump
Use this button if the unit will not be used for an extended period of time.This button will
remove water from the pump reservoir.
Remote Control Instructions
1.Start the machine
• Press the power key to turn the dehumidifier on.
2.Adjust the settings
• Use the up and down arrow keys to adjust your desired setpoint (typically 50-55%)
3.Stop the machine
• Press the power button again and the dehumidifier will stop. Note that the fan will continue to
operate for 1 minute after the unit has shut off. DO NOT DISCONNECT THE POWER CORD
TO FORCE THE UNIT TO STOP.
4. Water Drainage
• The Rfeine Wh100 has an integrated condensate pump.During normal operation, the
Rfeine Wh100 will automatically drain as required.
• If you would like to store or move your unit, press the drain button to drain water from the
pump reservoir. The drain will operate for 15 seconds each time the button is pushed. It may
be necessary to push the button more than once.

10
Spare Parts
Fan Components
Filter + External Components
Cables
Duct + Ventilation Accessories
N-100
N-101
N-102
N-1209
N-1206
N-1208
N-1207
Main Control Board
Display Board
RH/Temp. Sensor
Fan Motor
Complete Fan Assembly
Fan Capacitor
N-1210
N-1211
N-1205
N-1200
N-1201
N-1202
N-1203
N-125
Prefilter
MERV 8
HEPA
Carbon Filter
Foot adjustable
Display/Control
Inernal Components
N-120
N-121
N-122
Temp/RH Sensor Cable
Display Ribbon Cable
CaТ: 5 Port Internal Cable
N-1204 Supply Duict Collar
Assembly
Compressor
Compressor Capacitor
Coil Assembly
Condensate Pump
Assembly
Table of contents
Other Refine Dehumidifier manuals
Popular Dehumidifier manuals by other brands

EUROM
EUROM Coolsilent 100 Wifi instruction manual

Hitachi
Hitachi BD-155EX instruction manual

Altec AIR
Altec AIR PUREGAS P1500W Series user guide

Goldstar
Goldstar DH300M owner's manual

Be Cool
Be Cool BC18LEF2201 instructions

Pahwa Group
Pahwa Group Delair RD Series Operating, installation and maintenance manual