
│10
HOT WATER STORAGE TANKS RGC 120 and RGC 170 - www.regulus.eu
6 - Installation and Commissioning
Installation must meet valid rules and may be done only by qualied staff. The tank shall be placed on the
oor, as close to the heat source as possible.
Warning: Defects caused by improper installation, use or handling are not covered by warranty.
6.1 - Connection to heat sources
Connect the heating circuit to the inlet to and outlet from the heat exchanger (connection points marked X1
and X2) using G 3/4” fittings.
6.2 - Installation of an electric heating element
The G 6/4“ side tapping marked E1 is designed to accommodate an electric heating element. The hot water
storage tank can be equipped with an el. heating element depending on the tank diameter and the heating
element length. It can be controlled either directly (thermostat-equipped elements), or by a heating system
controller.
Warning: All electric heating elements shall be protected by a safety thermostat.
The installation of an electric heating element may be done by qualied staff only.
6.3 - Connection to water mains
DHW piping shall be done according to valid rules. Connect the tank to a cold water inlet (connection point
marked W1), inlet from hot water recirculation (connection point marked W3) and to DHW outlet (connection
point marked W2) using G 3/4” ttings. A 6bar safety valve shall be installed at the cold water inlet. Installa-
tion of a reducing valve to the tank inlet is recommended. If the pressure from water mains exceeds 6 bar, a
reducing valve is necessary. In order to prevent water loss, an expansion tank o fat least 5 l volume should be
installed at the cold water inlet as well.
Should the water be too hard, install a water softener before the tank. In case the water contains mechanical
impurities, install a lter.
A suitable anti-scald valve shall be installed at the hot-water outlet from the tank that prevents too hot water
from entering the taps.
Install a drain valve to the connection point U1 of the tank.
Complete DHW piping shall be properly insulated.
6.4 - Instalace elektronické anody
A so called electronic anode rod can be used instead of the magnesium one. Its principle advantage is that it
does not need to be taken out for check. Just a visual check of the electronic anode is sufficient.
Kit for hot water storage tanks of RGC 120 and RGC 170 series
Should an electronic anode rod or an el. heating element be installed, it is necessary to make a connection
between the metal tank casing and the PE line.
6.5 - Commissioning
Fill the heating circuit with the appropriate fluid and air-bleed the entire system.
Fill the tank with cold water, following this procedure:
- open the shut-off valve at the tank inlet
- open a hot water tap, as soon as water starts flowing out, tank filling is finished, close the tap
- check all connections for leaks, check the system pressure
Code El. anode length [mm] For hot water tanks
9176 600 (350/250) RGC 120 and RGC 170