INSTALLATION AND OPERATING INSTRUCTIONS
11/2011
STE Motor Protecting Relays
Basic data
(1 STE relays are not used with RF fans 30/… or any RO fans which
are equipped with their own integrated thermal protection (serial
thermo-contact).
(2 STE relays are not used if the protection and switching are
properly ensured by the control unit or TRE controller.
Note: Comprehensive protection of power controlled drives and frequently switched
drives can only be ensured by direct monitoring of the motor winding tempera-
ture using thermo-contacts or thermistors. Common protection of motors (using
magnetic and thermal triggers) is not able to check the actual motor temperature,
which can result in motor failure.
Application
STE protecting relays are intended to start up, switch
off and protect single-phase motors of RP, RPH, RQ
and RF (1 fans unless the protection is ensured by other
approved means (2.
Operating Conditions and Position
STE protecting relays are designed for indoor as well as
outdoor application in chemical-free environments wit-
hout explosion hazard. The STE relay's plastic box can
be mounted on the wall or partially embedded (30 mm)
in plaster. The STE relay can also be installed without
the plastic box directly on the DIN bar inside the distri-
bution board (module width 3.75, IP 20).
Functions and Operation
Basic features, properties and mode of operation are
described in the following articles:
 Fan Control
Press the (I) button to switch the fan on, press the (0)
button to switch the fan off.
 Comprehensive Fan Protection
If the fan fails, the STE protecting relay will automatica-
lly switch it off. The switching-off signal is provided by
opening of the TK thermo-contact in the motor winding.
Once the failure has been removed, the fan can be
restarted using the (I) button. If the power supply fails
(STE stays closed), the fan will be automatically started
once the power supply has been resumed.
 Power Supply Line Protection
The power supply line is protected by the short-circuit
relay and over-current relay.
 Auxiliary Contacts
This relay is equipped with a pair of auxiliary contacts(1
circuit-opening contact and 1 circuit-closing contact)
which can be used for remote signalling of the device
status, respectively for other working signals.
Wiring
Installation, adjustment, maintenance and replacement
of the STE relay may only be performed by a qualied
person authorized in accordance with ČÚBP Regulation
No. 50/78 Sb. § 6.
 Each installation of the relay must be performed on
the basis of a project.
 Before putting the relay into operation, a wiring
inspection and prescribed procedures must be perfor-
med.
Basic technical data
Full type designation.........................................STE T10B
Rated voltage ........................ 1 x 230 V, 50 Hz + N + PE
Operating voltage ......................................... 60 až 250 V
Maximum motor current............................................. 10 A
Minimum motor current............................................. 0,4 A
Auxiliary contacts (AC15) .............230 V / 4 A (24 V / 6 A)
Max. pre-protection................................................... 16 A
Protection Class ............................................... II IEC 536
Degree of protection..................................................IP54
Permissible ambient temperature.............. -25 až +40 °C
Dimensions (W x H x D) .......................70 x 141 x 92 mm
Weight .................................................................... 0,6 kg
Conductor cross-section.............................. max. 10 mm2
Conductor cross-section for TK and aux. contacts
..... max. 2,5 mm2
Fig. 1
Fig. 2



















ste_mon.pm6 2.3.2004, 8:311
Single-phase
fan motor
STE
protecting relay
Auxiliary
contacts
REMAK a.s., Zuberská 2601, 756 61 Rožnov p. R., tel.: 00420 571 877 778, fax: 00420 571 877 777, e-mail: [email protected], URL: http://www.remak.eu
INSTALLATION AND OPERATING INSTRUCTIONS
11/2011
STD Motor Protecting Relays
Basic data
Basic technical data
Full type designation............................................ STD T16
Rated voltage ................................ 3 x 400 V, 50 Hz + PE
Operating voltage .......................................... 60 až 400 V
Maximum motor current (adjustable).................10 až 16 A
Max. pre-protection.................................................... 80 A
Protection Class ................................................ II IEC 536
Degree of protection................................................... IP55
Permissible ambient temperature.............. - 25 až +40 °C
Dimensions (W x H x D) ........................80 x 150 x 98 mm
Weight ......................................................................0,6 kg
Conductor cross-section................................. max. 4 mm2
Conductor cross-section for TK and aux. contacts
...... max. 2,5 mm2
Short-circuit switching ability (IEC 155-1)....... 6 kA / 400 V
Application
STD protecting relays are intended to start up, switch
off and protect three-phase motors of RP, RPH, RQ
and RF (1 fans unless the protection is ensured by other
approved means (1.
Operating Conditions and Position
STD protecting relays are designed for indoor as well
as outdoor application in chemical-free environments
without explosion hazard. The STD relay's plastic box
can be mounted on the wall or partially embedded (30
mm) in plaster. The STE relay can also be installed wi-
thout the plastic box directly on the DIN bar inside the
distribution board (module width 3.75, IP 20).
Functions and Operation
Basic features, properties and mode of operation are
described in the following articles:
 Fan Control
Press the (I) button to switch the fan on, press the (0)
button to switch the fan off. The STD relay can be loc-
ked in the opened state.
 Comprehensive Fan Protection
If the fan fails, the STD protecting relay will automatica-
lly switch it off. The switching-off signal is provided by
opening of the TK thermo-contact in the motor winding.
Once the failure has been removed, the fan can be
restarted using the (I) button. If the power supply fails
(STD stays closed), the fan will be automatically started
once the power supply has been resume.
 Power Supply Line Protection
The power supply line is protected by the short-circuit
circuit breaker and adjustable over-current relay. The
protecting value adjusted on the STD relay does not
inuence the motor overload protection (it cannot be
adjusted below 10A).
 Auxiliary Contacts ("K" extension)
This relay can be additionally equipped with a pair of
auxiliary "K" contacts (1 circuit-opening contact and 1
circuit-closing contact) which can be used for remote
signalling of the device status, respectively for other
working signals.
Wiring
Installation, adjustment, maintenance and replacement
of the STD relay may only be performed by a qualied
person authorized in accordance with ČÚBP Regulation
No. 50/78 Sb. § 6.
 Each installation of the relay must be performed on
the basis of a project.
 Before putting the relay into operation, a wiring
inspection and prescribed procedures must be perfor-
med.
Three-phase
fan motor
STD protecting relay
(1 STD relays are not used if the protection and switching are
properly ensured by the control unit or TRD controller.
Note: Comprehensive protection of power controlled drives and frequently switched
drives can only be ensured by direct monitoring of the motor winding tempera-
ture using thermo-contacts or thermistors. Common protection of motors (using
magnetic and thermal triggers) is not able to check the actual motor temperature,
which can result in motor failure
Fig. 3
Fig. 4

Popular Relay manuals by other brands

Megacon Iso4-DIN instruction manual

Megacon

Megacon Iso4-DIN instruction manual

Det-Tronics Eagle Quantum Premier EQ3720RM manual

Det-Tronics

Det-Tronics Eagle Quantum Premier EQ3720RM manual

Pilz PNOZ X5 operating manual

Pilz

Pilz PNOZ X5 operating manual

Measurement Computing USB-ERB24 user guide

Measurement Computing

Measurement Computing USB-ERB24 user guide

ABB CVE Instruction leaflet

ABB

ABB CVE Instruction leaflet

Basler BE1-50/51B-217 instruction manual

Basler

Basler BE1-50/51B-217 instruction manual

LOVATO ELECTRIC PMA30 quick start guide

LOVATO ELECTRIC

LOVATO ELECTRIC PMA30 quick start guide

Pilz PNOZ mmc7p CC operating manual

Pilz

Pilz PNOZ mmc7p CC operating manual

LSIS GIPAM 115 FI manual

LSIS

LSIS GIPAM 115 FI manual

ZIEHL TR111V operating manual

ZIEHL

ZIEHL TR111V operating manual

Arcteq AQ-R215 instruction manual

Arcteq

Arcteq AQ-R215 instruction manual

FANOX SIA-B Installation & commissioning guide

FANOX

FANOX SIA-B Installation & commissioning guide

Noark Ex9JU quick guide

Noark

Noark Ex9JU quick guide

pizzato CS AR-08 Series manual

pizzato

pizzato CS AR-08 Series manual

Rielta IR-RK installation guide

Rielta

Rielta IR-RK installation guide

Intiel EFR-01 user manual

Intiel

Intiel EFR-01 user manual

System Sensor R-10E Installation and maintenance instructions

System Sensor

System Sensor R-10E Installation and maintenance instructions

Siemens SIRIUS 3UG4651 operating instructions

Siemens

Siemens SIRIUS 3UG4651 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.