REMKO MKT 251 User manual

Assembly and operating instructions
Read the instructions prior to performing any task!
REMKO MKT 251, MKT 251 S-Line
Local Air Conditioner
0056-2014-01 Edition 2, en_GB

Installation and operating instructions (translation of the orig-
inal)
Read these operating instructions carefully before commis-
sioning / using this device!
These instructions are an integral part of the system and must
always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis-
prints!

Table of contents
1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety notes for the operator........................................................................................................... 5
1.7 Safety notes for installation, maintenance and inspection.............................................................. 5
1.8 Unauthorised modification and changes......................................................................................... 5
1.9 Intended use................................................................................................................................... 5
1.10 Warranty........................................................................................................................................ 5
1.11 Transport and packaging.............................................................................................................. 6
1.12 Environmental protection and recycling........................................................................................ 6
2 Technical data....................................................................................................................................... 7
2.1 Unit data.......................................................................................................................................... 7
3 Design and function.............................................................................................................................. 8
4Operation............................................................................................................................................... 9
5 Assembly and installation.................................................................................................................. 11
6 Electrical wiring................................................................................................................................... 15
7 Commissioning................................................................................................................................... 16
8 Troubleshooting and customer service............................................................................................ 17
9 Care and maintenance........................................................................................................................ 19
10 Shutdown............................................................................................................................................. 20
11 Exploded view and spare parts lists................................................................................................. 21
11.1 Exploded view of the unit ........................................................................................................... 21
11.2 Spare parts list ........................................................................................................................... 22
12 Index..................................................................................................................................................... 24
3

1 Safety and
usage instructions
1.1 General safety notes
Carefully read the operating manual before com-
missioning the units for the first time. It contains
useful tips and notes such as hazard warnings to
prevent personal injury and material damage.
Failure to follow the directions in this manual not
only presents a danger to people, the environment
and the system itself, but will void any claims for
liability.
Keep this operating manual and the refrigerant
data sheet near to the units.
1.2 Identification of notes
This section provides an overview of all important
safety aspects for proper protection of people and
safe and fault-free operation.The instructions and
safety notes contained within this manual must be
observed in order to prevent accidents, personal
injury and material damage.
Notes attached directly to the units must be
observed in their entirety and be kept in a fully
legible condition.
Safety notes in this manual are indicated by sym-
bols. Safety notes are introduced with signal words
which help to highlight the magnitude of the danger
in question.
DANGER!
Contact with live parts poses an immediate
danger of death due to electric shock. Damage
to the insulation or individual components may
pose a danger of death.
DANGER!
This combination of symbol and signal word
warns of a situation in which there is immediate
danger, which if not avoided may be fatal or
cause serious injury.
WARNING!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may be fatal or cause
serious injury.
CAUTION!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause injury or mate-
rial and environmental damage.
NOTICE!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause material and
environmental damage.
This symbol highlights useful tips and recom-
mendations as well as information for efficient
and fault-free operation.
1.3 Personnel qualifications
Personnel responsible for commissioning, opera-
tion, maintenance, inspection and installation must
be able to demonstrate that they hold a qualifica-
tion which proves their ability to undertake the
work.
1.4 Dangers of failure to observe
the safety notes
Failure to observe the safety notes may pose a risk
to people, the environment and the units. Failure to
observe the safety notes may void any claims for
damages.
In particular, failure to observe the safety notes
may pose the following risks:
nThe failure of important unit functions.
nThe failure of prescribed methods of mainte-
nance and repair.
nDanger to people on account of electrical and
mechanical effects.
1.5 Safety-conscious working
The safety notes contained in this manual, the
existing national regulations concerning accident
prevention as well as any internal company
working, operating and safety regulations must be
observed.
REMKO MKT
4

1.6 Safety notes for the operator
The operational safety of the units and compo-
nents is only assured providing they are used as
intended and in a fully assembled state.
nThe units and components may only be set up,
installed and maintained by qualified per-
sonnel.
nProtective covers (grille) over moving parts
must not be removed from units that are in
operation.
nDo not operate units or components with
obvious defects or signs of damage.
nContact with certain unit parts or components
may lead to burns or injury.
nThe units and components must not be
exposed to any mechanical load, extreme
levels of humidity or extreme temperature.
nSpaces in which refrigerant can leak sufficient
to load and vent. Otherwise there is danger of
suffocation.
nAll housing parts and device openings, e.g. air
inlets and outlets, must be free from foreign
objects, fluids or gases.
nThe units may not be used in environments
containing a great deal of dust or chlorine, or in
places with atmospheres containing ammonia.
nThe units must be inspected by a service tech-
nician at least once annually. Visual inspec-
tions and cleaning may be performed by the
operator when the units are disconnected from
the mains.
nThe local room air conditioner is designed for
flexible use in living and work spaces. Year-
round operation is not recommended.
nDo not leave the appliance running for an
extended period unsupervised.
1.7 Safety notes for installation,
maintenance and inspection
nAppropriate hazard prevention measures must
be taken to prevent risks to people when per-
forming installation, repair, maintenance or
cleaning work on the units.
nThe setup, connection and operation of the
units and its components must be undertaken
in accordance with the usage and operating
conditions stipulated in this manual and comply
with all applicable regional regulations.
nLocal regulations and laws such as Water
Ecology Act must be observed.
nThe power supply should be adapted to the
requirements of the units.
nUnits may only be mounted at the points pro-
vided for this purpose at the factory. The units
may only be secured or mounted on stable
structures, walls or floors.
nMobile units must be set up securely on suit-
able surfaces and in an upright position. Sta-
tionary units must be permanently installed for
operation.
nThe units and components should not be oper-
ated in areas where there is a heightened risk
of damage. Observe the minimum clearances.
nThe units and components must be kept at an
adequate distance from flammable, explosive,
combustible, abrasive and dirty areas or
atmospheres.
nSafety devices must not be altered or
bypassed.
1.8 Unauthorised modification
and changes
Modifications or changes to units and components
are not permitted and may cause malfunctions.
Safety devices may not be modified or bypassed.
Original replacement parts and accessories
authorised by the manufactured ensure safety. The
use of other parts may invalidate liability for
resulting consequences.
1.9 Intended use
Depending on the model, the equipment and the
additional fittings with which it is equipped is only
intended to be used as an air-conditioner for the
purpose of cooling or heating the air in an
enclosed room..
Different or additional use shall not be classed as
intended use. The manufacturer/supplier assumes
no liability for damages arising from an unintended
use of the equipment. The user bears the sole risk
in such cases.
Using the equipment as intended also includes
working in accordance with the operating manual
and installation instructions and complying with the
maintenance requirements.
Under no circumstances should the threshold
values specified in the technical data be exceeded.
1.10 Warranty
For warranty claims to be considered, it is essential
that the ordering party or its representative com-
plete and return the "certificate of warranty" to
REMKO GmbH & Co. KG at the time when the
units are purchased and commissioned.
The warranty conditions are detailed in the "Gen-
eral business and delivery conditions". Further-
more, only the parties to a contract can conclude
special agreements beyond these conditions. In
this case, contact your contractual partner in the
first instance.
5

1.11 Transport and packaging
The devices are supplied in a sturdy shipping con-
tainer. Please check the equipment immediately
upon delivery and note any damage or missing
parts on the delivery and inform the shipper and
your contractual partner. For later complaints can
not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous
toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to
children!
1.12 Environmental protection
and recycling
Disposal of packaging
All products are packed for transport in environ-
mentally friendly materials. Make a valuable contri-
bution to reducing waste and sustaining raw mate-
rials. Only dispose of packaging at approved
collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufac-
ture of the devices and components. Help protect
the environment by ensuring that the devices or
components (for example batteries) are not dis-
posed in household waste, but only in accordance
with local regulations and in an environmentally
safe manner, e.g. using certified firms and recy-
cling specialists or at collection points.
REMKO MKT
6

2 Technical data
2.1 Unit data
Series MKT 251 MKT 251
Operating mode Local compact air conditioning unit for cooling
Nominal cooling output 1) kW 2.60
Energy efficiency ratio - cooling A
Energy efficiency rating EER 1) 2.63
Energy consumption, hourly kWh/60 min 0.99
Approx. application area (room volume) m³ 80
Adjustment range indoor unit °C +16 to +32
Operating range - indoor unit °C/%r.F. +16 to +35 / +35 to +85
Refrigerant R 410A 3)
Refrigerant, basic capacity kg 0.5
Max. operating pressure / cooling cycle kPa 1800 / 3600
Air flow volume per stage m³/h 240 / 270 / 320
Sound pressure level per stage 2) dB(A) 49 / 52 / 53
Sound power level max. dB(A) 62
Power supply V/Ph/Hz 230 / 1~/ 50
Enclosure class IP 20
Electr. rated power consumption 1) kW 0.99
Electr. rated current consumption 1) A 4.78
Elec. starting current max., LRA A 17
Exhaust air hose, length / diameter mm 1500 / 125
Dimensions - height mm 770
Dimensions - width mm 435
Dimensions - depth mm 430
Weight kg 33.0
Standard colour white silver
Serial number 1254... 1255...
EDP no. 1612255 1612256
1) Room air temperature TK 35 ℃, FK 24 ℃
2) Distance 1m free field
3) Contains greenhouse gas according to Kyoto protocol
7

3 Design and function
Unit description
The local air conditioning unit is particularly well
suited to flexible use.
The local room air conditioner comprises a floor-
standing unit for the indoor area and an exhaust air
hose to conduct the heat away. The indoor unit
extracts the heat from the room to be cooled by
means of an evaporator (heat exchanger) and
transfers it to the internal cooling cycle. This
releases the heat back to the outside via another
heat exchanger (condenser) by means of the flex-
ible exhaust air hose.
The condensate arising during cooling mode is
continually drained off via the condenser by means
of a condensate pump located in the unit - the con-
denser evaporates the condensate and discharges
it to the outside via the exhaust air hose.
The unit filters and dehumidifies the air thereby
creating a comfortable room climate. It works fully
automatically and offers numerous additional
options thanks to its microprocessor controller. The
unit can be conveniently operated by means of the
infrared remote controller included.
2
1
3
5
B
A4
Fig. 1: Front view
A: Air inlet, recirculation
B: Air outlet, recirculation
1: Recessed grip
2: Infra-red receiver
3: Ventilation louvres
4: Control panel
5: Conveyor rollers
B
A
A
1
2
3
Fig. 2: Rear view
A: Air inlet, recirculation
B: Air outlet, exhaust air
1: Air filter, recirculation
2: Condensate drainage with stopper
3: Exhaust air hose
REMKO MKT
8

4 Operation
The system can be operated by means of the control panel on the unit or via the standard infrared remote
controller. The functional operation of the keys among themselves is identical, however, the designation can
vary. The batteries must be correctly inserted before the infrared remote control is used.
9
1
10 11
12 13
14
2 3 4 56
7
8
Fig. 3: Control panel
Legend
1
On / off "Power" key
2
Operating mode "MODE" key
3
"Fan Speed" key
4
"Timer" key
5
+
6
keys
Temperature/time adjustment
"Timer/Temp Adjust":
5
Higher,
6
lower
7
Display
8
Red malfunction LED:
Reservoir full
An acoustic and optical signal indicates that the
liquid level switch in the internal reservoir has
switched off the operation of the unit. The acoustic
signal ceases after a short time, the LED remains
active.
9
LED operating mode indicator
Green: "Cool" orange: "Dehumidify" yellow: Venti-
late "Fan"
10
Orange LED indicator
Fan stages with "High"/"Med"/"Low" fan speeds
11
Green LED indicator
"Timer"
12
Green LED indicator
"Room Temp"
(If this LED illuminates the current room tempera-
ture is shown in the display (
7
))
13
Green LED indicator
Target temperature "Set Temp"
14
Infra-red receiver
15
"°C/°F" changeover key
(Only on the remote control)
16
Infrared transmitter
(Only on the remote control)
9

2
1
15
5
3
7
16
4
6
Fig. 4: Infrared remote control
Selection of the operating mode "Mode"
nCooling "Cool"
The unit provides room cooling. It filters and
dehumidifies the air thereby creating a comfort-
able room climate.
nDehumidifying "Dehumidify"
In dehumidifying mode moisture is removed
from the air in the room.
nVentilate "Fan"
The unit recirculates the room's air, filters it
and provides an even air flow.
Cooling mode "Cool"
1. Attach the exhaust air hose to a wall pass-
through or window
2. Switch the unit on with the "Power" key
1
.
3. Press the "Mode" key
2
until the "Cool" LED
9
illuminates.
4. Select the setting for the fan via the "Fan
speed" key
3
:
"High" highest fan speed
"Med" medium fan speed
"Low" lowest fan speed.
5. If the "Room Temp" LED
12
illuminates the
current room temperature is shown in the dis-
play
7
.
6. As soon as the
4
/
5
/
6
key is pressed, the
display changes over from room temperature
to target temperature (LED
13
illuminates)
and shows the desired temperature for 15
seconds.
7. Adjust the desired room temperature via the
"Timer/Temp Adjust"
5
/
6
key. The up arrow
5
increases the setpoint shown in the dis-
play
7
, the down arrow
6
decreases the
setpoint displayed.
Dehumidifying mode "Dehumidify"
1. Attach the exhaust air hose to a wall pass-
through or window
2. Switch the unit on with the "Power" key
1
.
3. Press the "Mode"
2
key until the "Dehu-
midify"
9
LED illuminates, the fan will be
automatically switched on at the "Med" fan
speed.
Ventilate mode "Fan"
1. Switch the unit on with the "Power" key
1
.
2. Press the "Mode" key
2
until the "Fan" LED
9
illuminates.
3. Select the setting for the fan via the "Fan
speed" key
3
:
"High" highest fan speed
"Med" medium fan speed
"Low" lowest fan speed
4. The room temperature is not affected and
remains constant. For this reason the "Timer/
Temp. Adjust" keys
5
/
6
cannot be used.
REMKO MKT
10

"Timer"
You can switch the unit on and off automatically
with the timer. The switch on delay or switch off
delay can be programmed for this.
Automatic switch on
1. Switch the unit on with the "Power" key
1
.
2. Select the operating mode and implement all
settings for the desired operating mode.
3. Switch the unit off with the "Power" key
1
.
4. Press the "Timer"
4
key.
5. Adjust the time via the "Timer/Temp. Adjust"
5
/
6
key. You can only enter full hours.
6. LED
11
flashes.
Automatic switch off
1. The unit operates in the previously selected
operating mode.
2. Press the "Timer"
4
key.
3. Adjust the remaining runtime via the "Timer/
Temp. Adjust"
5
/
6
key. Only full hours can
be entered.
4. LED
11
illuminates.
5. Unit switches off automatically after the
preset time.
NOTICE!
You will achieve a pleasant room temperature
if you set the desired target temperature max.
4 to 7 °C below the outside temperature.
Help save on energy consumption in stand-by
mode! If the device, system or component is
not in use, we recommend disconnecting the
power supply. Components with a safety func-
tion is excluded from our recommendation!
5 Assembly and
installation
Assembly and unit installation instructions
The unit is positioned at the desired location with
the discharge side pointing into the room. When
positioning, observe the following instructions:
nAfter unpacking the unit let it sit on its transport
rollers for at least 5 minutes before you switch
it on.
nSet the unit down in a stable position on a level
and firm floor. If the floor is uneven then this
can lead to vibrations and disturbing noises.
Fig. 5: Unit installation
NOTICE!
There must be a minimum clearance of 20 cm
between the rear of the unit and the wall.
nAll extensions to the power supply must be of a
sufficient cable size and must only be used
fully rolled out.
Fig. 6: Power supply
11

nCheck whether the stopper in the condensate
drain is present and correctly installed. There is
a risk of uncontrolled condensate leakage after
commissioning.
1
Fig. 7: Condensate drain
1: Condensate drainage with stopper
nNever operate the unit without the air inlet filter.
Otherwise, the fins of the heat exchanger can
become dirty and the unit loses performance.
1
Fig. 8: Air inlet filter
1: Recirculated air filter
nEnsure that persons and sensitive objects,
such as plants, are not placed directly in the air
flow emerging from the unit.
In addition, with direct solar radiation close the
curtains and blinds and keep the windows and
doors closed during operation.
Conduct the warm exhaust air away
NOTICE!
The exhaust air hose should always be laid
rising in the direction of air flow and must not
be extended!
In cooling mode the unit creates warm moist
exhaust air, which must be conducted away from
the room to be cooled. For this reason it is neces-
sary to plug the exhaust air hose into the outlet
opening on the rear of the unit.
nEnsure that the catches for the exhaust air
hose latch securely into the two openings of
the connection aperture. In order to be sure of
effective operation, do not lay the flexible
exhaust air hose with tight bends and do not
kink it and to prevent damage resulting to avoid
air carrying components!
Fig. 9: Latch the hose into place
nThe exhaust air of the unit contains a certain
amount of moisture. For this reason it is advis-
able to feed the exhaust air to the outdoor area
or to outdoors.
Exhaust air routing variants
You can route the exhaust air out of the building as
follows:
Via a flat nozzle
The flat nozzle supplied can be used in various dif-
ferent ways. It is possible to feed the flat nozzle
through an open window and fasten it by means of
Velcro and a window suction cup (Fig. 10). Like-
wise the flat nozzle can be hung in a tilted window
(Fig. 11).
REMKO MKT
12

Via a wall pass-through
The hose supplied is firmly attached to a wall pass-
through. A suitable wall pass-through is available
as an accessory (Fig. 12).
Fig. 10: Exhaust air with open window
Fig. 11: Exhaust air with tilted window
Fig. 12: Wall pass-though
NOTICE!
In some circumstances routing the exhaust air
via a firmly attached exhaust air hose, e.g.
through closed doors or windows, can lead to
negative pressure in the room in which the unit
is being used. If this should reduce the per-
formance of the unit then arrange for the pres-
sure to be equalised (provide ventilation if nec-
essary on-site).
13

Installation scheme for wall pass-though (accessory)
2
34
1
min. 400 mm
Fig. 13: Installation example
1: External grill
2: Telescopic tube
3: Non-return flap
4: Sealing cover
Installation instructions
1. Create a core hole in the exterior wall (max. wall thickness 480 mm) with a diameter of at least
135 mm. Watch out for any supply lines in this area!
2. Insert the slide tube into the wall pass-through created such that the outer tube (larger diameter) is on
the inside of the wall. In order to avoid cold bridges insulate the telescopic tube with suitable insulation
material.
3. Brick the slide tube into the core hole such that it sits flush on both sides of the wall.
4. Fasten the protection grid on the outside of the wall with 4 screws. Take rain ingress into account when
fitting the grid.
5. Insert the interior flap valve and fasten this likewise with 4 screws. The "Top" legend on the flap valve
must be visible from the inside.
6. When decommissioning the unit, e.g. before the start of the winter period, seal the opening in the flap
valve with the sealing cover in order to prevent air circulation.
REMKO MKT
14

6 Electrical wiring
Electrical drawings
A2517-160
A
B
C
2
1
4
3
56
Fig. 14: Electrical drawings
A: Mains power circuit board
B: Control panel control board
C: Power plug
1: Microswitch (reservoir)
2: Temperature sensor, recirculated air
3: Evaporator fan
4: Compressor
5: Condenser fan
6 Condensate motor
Colour coding:
Br Brown
Bu Blue
Rd Red
Wh White
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process
15

7 Commissioning
Before every commissioning the air inlet and outlet
openings should be checked for foreign bodies and
the air inlet filter must be checked for dirt. Blocked
or soiled grids and filters must be cleaned immedi-
ately, see "Care and maintenance" chapter.
Cooling mode
1. Switch the unit on with the "POWER" key.
2. Select cooling mode with the "MODE" key.
The "COOL" LED must illuminate.
3. Set the desired target temperature with the
"TIMER/TEMP/ADJUST" key. The selected
target temperature will be shown in the dis-
play. If the fan stage selected is too large or
too small then this can be adjusted with the
"FAN SPEED" key.
Recirculation mode
1. Switch the unit on with the "POWER" key.
2. Select ventilation mode with the "FAN
SPEED" key. The "HIGH/MED/LOW" LED
must illuminate.
REMKO MKT
16

8 Troubleshooting and customer service
The unit has been manufactured using state-of-the-art production methods and has been tested several
times to ensure that it works properly. If malfunctions should occur, please check the unit as detailed in the
list below. Please inform your dealer if the unit is still not working correctly after all the function checks have
been performed.
Operational malfunctions
Fault description Cause Remedy
The unit does not operate, the control
panel remains dark
Mains voltage Ensure that mains voltage is present (fuse)
Power failure Check voltage and if necessary wait until
turned on again.
Mains fuse or con-
troller fuse faulty
Arrange to have exchanged
Power plug not
inserted in socket
Insert power plug
Power supply
defective
Check power supply for damage
The unit is working with reduced per-
formance
Exhaust air or
outlet openings are
dirty or blocked by
foreign bodies
Clean the openings, remove foreign bodies
Filter soiled Clean the filter in accordance with the
instructions
Cooling load of the
room excessive
Reduce the thermal load
The unit does not work, LED indicator
"Timer" is flashing
"Timer" Timer is programmed, delete the timer set-
ting.
The unit does not work, display shows
"E1"/"H1"
Room temperature This lies outside the operational limits of 16
to 35°C. Wait until the room temperature
lies within the operating range (reduce the
solar radiation and close windows and
doors if necessary).
The unit switches itself off automatically,
malfunction LED flashes and a signal
sounds (reservoir full)
Reservoir full Proceed as follows to empty the reservoir:
1. Switch unit off, pull out power plug.
2. Place a shallow container underneath
the drain outlet and loosen the stopper.
3. After the condensate has drained off,
plug the stopper back in again firmly.
17

Fault description Cause Remedy
The unit does not cool prop-
erly
LED cooling indicator The "Cool" LED indicator must illuminate
Close windows, doors,
blinds and curtains
Exhaust air hose Must be properly attached. It must not be kinked,
sloping downwards or laid in bends that are too
tight.
Air feed and air exhaust There must be no foreign bodies impairing these
(observe minimum clearance)
Ventilation louvres Must be free of dirt and foreign objects
Target temperature
adjustment
Must not be set too high (unit operating range
+16 to +35 °C).
The unit does not respond to
the remote control
Remote control There must be no objects between the remote
control and the unit (range ca. 5 m).
Batteries Ensure that
the batteries are in good working order, other-
wise replace the batteries
the batteries have been inserted with the correct
polarity (see markings)
Condensate leaks out of unit Unit standing at an
angle
Position vertically, ensure stable horizontal base
Stopper in condensate
drain hose missing
Seal the hose so that it is watertight again
Exhaust air hose not
correctly seated
Connect correctly
REMKO MKT
18

9 Care and maintenance
Regular care and observation of some basic points
will ensure trouble-free operation and a long
service life.
DANGER!
Prior to performing any work, ensure the equip-
ment is disconnected from the voltage supply
and secured to prevent accidental switch-on!
1
Fig. 15: Filter removal
1 Filter
nClean the unit using a damp cloth. Do not use
a jet of water.
nDo not use any caustic, abrasive or solvent-
based cleaning products.
nOnly use suitable cleaning agents, even in the
event of severe soiling.
nEnsure that no moisture gets into the unit.
Clean the exhaust air and outlet openings reg-
ularly and thoroughly. This is where dirt most
often collects first
NOTICE!
Check the level of dirt on the on the exchanger
fins.
nClean the air filter on the indoor unit at regular
intervals, and more frequently if necessary.
nIt is recommended that you take out a mainte-
nance contract with an appropriate specialist
firm.
This enables you to ensure the operational reli-
ability of the plant at all times!
Filter cleaning
The unit is equipped with an air filter. This can be
withdrawn from the rear of the unit. The filter must
be cleaned at regular intervals. Clean the air filter
at intervals of no more than 100 operating hours.
Reduce this interval in the case of heavily contami-
nated air.
Please proceed as follows in order to clean the
unit:
1. Switch the unit off and pull out the power
plug.
2. Pull the filter out of the unit (Fig. 15)
3. Clean the dust off the filter. Use a vacuum
cleaner in the event of slight soiling. (Fig. 16)
4. In the case of heavy soiling clean the filter
carefully in lukewarm water. (Fig. 17)
5. Subsequently allow the filter to dry in the air.
6. Insert the filter back into the device.
7. Ensure that the filter is dry and undamaged.
NOTICE!
Never operate the indoor unit without the orig-
inal filter. The heat exchanger fins on the
indoor unit with soil up if operated without a
filter and the device will suffer performance
loss.
Fig. 16: Cleaning with a vacuum cleaner
19

Fig. 17: Cleaning with lukewarm water
10 Shutdown
NOTICE!
Never switch off the equipment by pulling out
the mains plug.
Temporary shutdown
If it is planned to shut down the unit for longer
periods e.g. during the winter, proceed as follows:
1. Let the unit run in recirculating operation for
ca. 2 hours in order to dry the surfaces of the
evaporator fins. This will transport the
remaining moisture out of the unit and this
will avoid unpleasant odours when the unit is
re-commissioned.
2. Switch the unit off with the "POWER" key,
pull out the power plug and wind up the
power supply. Ensure that the wiring is not
kinked or too severely bent.
3. Place a suitable container underneath the
condensate drain of the internal reservoir.
The condensate drain is located on the lower
rear side of the unit.
4. Pull out the stopper from the condensate
drain and collect the condensate that drains
out.
5. Then insert the stopper once again. A
missing stopper or an incorrectly inserted
stopper will result in condensate leaking out
after re-commissioning.
6. Store the unit in an upright position in a cool,
dry and dust-free location protected from
direct sunlight. Cover the unit with a synthetic
cover to protect it against dust if desired.
Permanent shutdown
The entire system should only be dismantled by a
specialist firm familiar with all environmental
aspects involved. REMKO GmbH & Co. KG or your
sales partner will be pleased to provide details of
refrigerant specialists in your area.
REMKO MKT
20
This manual suits for next models
1
Table of contents
Other REMKO Air Conditioner manuals

REMKO
REMKO RM Series Instruction Manual

REMKO
REMKO RXD 260 User manual

REMKO
REMKO ATY DC Series User manual

REMKO
REMKO MXD 203 User manual

REMKO
REMKO KWT 180 DC User manual

REMKO
REMKO MXD202 User manual

REMKO
REMKO SKT Series User manual

REMKO
REMKO RKL 460 Instruction Manual

REMKO
REMKO JBW 260 DC IT User manual

REMKO
REMKO MXW Series User manual

REMKO
REMKO MKT 290 S-Line User manual

REMKO
REMKO RXS H Series User manual

REMKO
REMKO RVD Series User manual

REMKO
REMKO KWD EC Series User manual

REMKO
REMKO SKT Series User manual

REMKO
REMKO RKL DC Series User manual

REMKO
REMKO RXT 523 DC User manual

REMKO
REMKO MXD 204 User manual

REMKO
REMKO RKS 510 User manual

REMKO
REMKO ATY 260 Guide