Retrotec DM32 User manual

Retrotec Inc.
Operation Manual
Accessories & Parts
Speed
Control
Adapter
rev-2013-12-02

Page 2 of 10
©Retrotec Inc. 2014
1. Overview......................................................................................................3
2. What’s included ...........................................................................................4
3. Operation.....................................................................................................5
3.1 Connect Adapter between gauge and TEC fan speed controller ................................................ 5
3.2 Set the fan and range being used on the gauge.......................................................................... 5
3.3 Connect Pressure Tubing for Minneapolis Model 3™ ................................................................. 6
3.4 Connect Pressure Tubing for Minneapolis Model 4™ ................................................................. 6
3.5 Connect Pressure Tubing for Minneapolis Duct Blaster®............................................................ 8
4. Adapter Technical Details...........................................................................10
4.1 Fan Compatibility....................................................................................................................... 10
4.2 Gauge Compatibility .................................................................................................................. 10
4.3 LED Power Status Indicator .......................................................................................................10
Extra Features the DM32 gives your TEC Devices
Pressurization testing no longer requires the use of an additional tube that is run to the other side of the
cloth. DM32 takes care of this in software and always makes the correct decision.
The True Flow Grid can be corrected in the gauge without using correction tables.
Hole Flow enables you to measure the flow rate from any supply or into any exhaust device just using a
box with a hole cut in it.
Hold readings and convert to any units used worldwide without a calculator.
Blower door can be used to measure air handler flow automatically. Since our Set Pressure can be any
value, simply measure the supply pressure. Set the pressure in the gauge to this pressure, and the
blower door willl measure the air handler flow.

Page 3 of 10
©Retrotec Inc. 2014
1. Overview
Now you can use the newest and most modern gauge with features such as Touch Screen, two way
communication with laptops locally or over the Internet, WiFi and advance FanTestic software.
Fans manufactured by TEC (such as those used with the Minneapolis Duct Blaster® or Minneapolis
Blower Door™ Model 3 or 4) can be controlled by the Fan Speed control output on a Retrotec gauge
using the Retrotec Model FN275 - Speed Control Adapter (for TEC fans). The fan speed control must
have the cruise input port which is indicated by the presence of an audio jack on the side.
Figure 1: Control a TEC fan using the Retrotec gauge and fan control adapter

Page 4 of 10
©Retrotec Inc. 2014
2. What’s included
The Adapter kit comes with both connectors needed –a short yellow Ethernet-style Speed Control
Cable, and a short black cable with 3.5 mm audio connectors. The Speed Control Cable connects to the
Speed Control output on the top of the Retrotec gauge, and the black connector goes from the Adapter
to the Minneapolis Fan Speed Control Cruise input port.
The DM32 comes with a Tubing Accessory kit, so users will have the Retrotec color coded pressure
tubes.
Connecting the pressure ports to the TEC fan as described in this document will allow the Retrotec
gauge to correctly calculate results, and allow the user to follow the testing procedures shown in the
Retrotec QuickGuides.

Page 5 of 10
©Retrotec Inc. 2014
3. Operation
3.1 Connect Adapter between gauge and TEC fan speed controller
Retrotec-TEC Fan speed control Adapter is connected between the gauge and the TEC fan speed
controller, in line with the Speed Control cable as shown in Figure 2: Attach Adapter inline between
gauge Speed Control Output and Minneapolis Fan Speed Control Cruise Input.
Figure 2: Attach Adapter inline between gauge Speed Control Output and Minneapolis Fan Speed Control Cruise Input
Once connected, the Speed Control signal from the Retrotec gauge will control the fan. User can utilize
the Set Speed or Set Pressure functions, or any of the automated software solutions from Retrotec to
control the gauge, which will in turn drive the (non-Retrotec) fan.
3.2 Set the fan and range being used on the gauge
User must be sure to select the fan on the gauge corresponding to the fan installed in the Blower Door.
With the DM32, this is a matter of a few taps on the touchscreen, as shown in Figure 3.
Figure 3: User must set the type of fan on the gauge to the TEC fan in use

Page 6 of 10
©Retrotec Inc. 2014
In order to use the color-coded pressure input ports, diagrams are provided indicating how to hook up
each of the TEC fans using the Retrotec color codes. Equivalent set up is shown for each model fan, and
whether the fan is being used for pressurizing or depressurizing.
Once the pressure tubing is hooked up using the Retrotec color scheme, Retrotec QuickGuides and
manuals describing the various procedures encountered while using Blower Door equipment can be
followed without translation of the tubing color.
When discussing Pressurize and Depressurize, the diagrams assume that the operator and the gauge are
on the inside of the space being pressurized or depressurized. Another term for Depressurize is “Flow
towards Operator”, and for Pressurize is “Flow Away from Operator”.
3.3 Connect Pressure Tubing for Minneapolis Model 3™
Figure 4: View of Retrotec gauge tubing when used with Model 3
When pressurizing, the Retrotec gauge internally compensates for the back pressure on the non-self-
referenced fans such as the MN Model 3 using the induced pressure measured on Channel A between
the room and the outdoors, so only one tube needs to be run to the outdoors.
Figure 5: Comparison of connections using a Retrotec gauge instead of the TEC gauge using Model 3
3.4 Connect Pressure Tubing for Minneapolis Model 4™

Page 7 of 10
©Retrotec Inc. 2014
Figure 6: View of Retrotec gauge tubing when used with Model 4
In both Pressurize and Depressurize set ups with a Retrotec gauge, both yellow and green tubes go to
the brass taps on the Model 4 fan, for the later Model 4 fans with two pressure taps, which are self-
referencing. If the Model 4 fan you have has only one pressure tap, you must be passing the clear tube
through the door panel as instructed by TEC. In that case, the yellow tube on the Retrotec gauge is
replacing the clear tube so the yellow tube will be wherever the clear tube was in your previous set up.
It is important that both the yellow and green tube are used with the Retrotec gauge when the fan type
is chosen as Model 4, just as the TEC gauge requires both the red and clear tubes.
There is no change in the tubing from gauge to fan when changing between pressurize and depressurize,
the only difference is that the fan is taken out of the cloth, turned around and put back into the cloth
facing the other way.
Figure 7: Comparison of connections using a Retrotec gauge instead of the TEC gauge using Model 4

Page 8 of 10
©Retrotec Inc. 2014
3.5 Connect Pressure Tubing for Minneapolis Duct Blaster®
Figure 8: View of Retrotec gauge tubing when used with Duct Blaster (no need for green in Pressurize)
In both Pressurize and Depressurize set ups with a Retrotec gauge, the yellow tube goes to the brass tap
on the Duct Blaster fan.
When using the Retrotec gauge in a Depressurize setup, the Green tube goes to the plastic port on the
Flow Conditioner which MUST be used when depressurizing and must include the piece of rigid foam
with holes that looks like a piece of packing material but is essential to allowing the Duct Blaster to
measure in the depressurization direction accurately.
Figure 9: Flow conditioner installed for Depressurize*
Figure 10: Duct Blaster Flow conditioner plastic tap*
*Flow conditioner pictures courtesy of The Energy Conservatory, Inc.

Page 9 of 10
©Retrotec Inc. 2014
Figure 11: Comparison of connections using a Retrotec gauge instead of the TEC gauge using Duct Blaster
Note that in Pressurize set up, the gauge green tube is not required as the Flow Conditioner will be
removed from the Duct Blaster.

Page 10 of 10
©Retrotec Inc. 2014
4. Adapter Technical Details
4.1 Fan Compatibility
The Speed Control Adapter (for TEC fans) (Retrotec part number FN275) is designed to convert the fan
speed control output from Retrotec gauges to a Pulse Width Modulation (PWM) scheme required by the
cruise input on TEC fan speed control unit.
The Adapter thus works with any fans that use the TEC fan speed control unit, or a compatible PWM
speed control scheme.
4.2 Gauge Compatibility
The Speed Control Adapter is designed to work with the fan speed control output from Retrotec gauges,
including the DM32 and the DM-2. Given that DM-2 are reaching end of lifecycle, it would be prudent
for Speed Control Adapter users to use the DM32 to control their TEC fans.
4.3 LED Power Status Indicator
The LED on the front indicates the status of power internal to the Adapter. The Adapter uses an AA
battery to supplement the power provided by the Speed Control Output. A green light when plugged in
means that the Adapter battery has adequate charge.
When the battery voltage falls to +5.4V, the red light will come on as a ‘low battery’ indication, meaning
the internal battery needs to be changed (9V battery).
Battery life when used with the DM32 gauge is expected to be unlimited, since power from the battery
is only required when the fan is running at 90-100% speed.
When used with a DM-2 gauge, the battery will need to be changed at regular intervals, since the DM-2
speed control output needs more boosting.
Other manuals for DM32
4
Table of contents
Other Retrotec Measuring Instrument manuals