Controller with thermostat HMI CURTAIN
User Guide
Welcome
Thank you for buying the product! Your new controller will
provide years of reliable service. Using this digital device
will provide more uniform comfort through the seasons.
Please read this manual for complete instructions
on installing and operating your device. If you require
further assistance, please feel free to contact directly with
Reventon Group Sp. z o.o.
In the box you will find
- controller with thermostat HMI CURTAIN
- user guide
- screws (2 pieces)
Service
We offer the warranty of 24 months from the sales day.
Technical data
Temp. range: 5 - 35°C Accuracy: ±0.5°C
Timing error: <1% Power consumption: < 1.5 W
Power supply: 95 ~ 240 VAC, 50 ~ 60 Hz
Maximal current load:
•fan: 5 A (inductive)
•valve actuator: 3 A
Shell material: PC (fireproof)
Dimensions: 86 x 86 x 13,3 mm
Installation box: 86 x 86 mm lub Ø60 mm
Ambient temperature: t = 0 - 45°C, ϕ = 5-95%
Storage temperature: -5 - 55°C
RS485/Modbus RTU communication
Baudrate: 9600 bps
Degree of protection (housing): IP 20
About device
The controller with thermostat HMI CURTAIN is designed
to control the operation of the air curtain by switching ON
/ OFF its fans and valves. This controlling can be realised
depending on limit sensor position (using dry contact)
or difference between set and room temperatures. It can
work in heating, cooling or ventilation mode. The item
is microprocessor based device with LCD display.
Features of the controller
•Modern design similar as a cell phone
•Beautiful Frame CHROME creates elegant life
•Acrylic lenses to avoid the finger scratch
•Touch Button makes simple operation
•Large screen display with backlight is easy to read -
even in the dark
•Dry contact for door sensor
•One-touch temp control overrides program schedule
•Internal and external sensor selectable is suitable
for any place
•Data memory when power is off
•Easy installation
•86 x 86 mm hidden box and european 60 mm round
box is available
Home screen quick reference
Operation
1. Setting the temperature
Press or to set temperature.
2. Setting lock
Press and hold and for 5 sec. to lock the screen.
The icon will display on the screen.
Press and hold and again for 5 sec. to unlock
the screen.
3. Setting the fan
Press to select the fan speed OFF, HIGH, MED, LOW.
4. Setting the system mode
Press to change the system mode COOLING, HEATING
and VENTILATION. In the mode of VENTILATION, the valve
is off but the fan runs.
5. Set clock and day
Press and hold till subsequent minutes / hours / days
starts to flash and then define time and data and with
and .
6. Setting functions and options
During power off, press and hold and at the same
time for 5 sec. to go to system functions. Then press
to change the different items. Press or to set
the relative values according to the table.
No.
Function
Settings & Options
Default
1
Temp. calibration
-9 - 9°C
-2°C
2
Fan control
00: When room temp. reaches
the setpoint, the fan will turn off
01: When room temp. reaches
the setpoint, the fan will turn to the
set speed
00
3
Lock
00: All buttons are locked except
POWER
01: All buttons are locked
01
4
Heating / Cooling
00: Cooling only
01: Heating / Cooling
02: Heating only
01
5
Min. set. temp.
5 - 15°C
5°C
6
Max. set. temp.
15 - 35°C
35°C
7
12 / 24 Clock
00: 12 h; 01: 24 h
01
8
Display mode
00: Display both set temp. and room
temp.
01: Display set temp. only
00
9
Dead zone
1-5°C
1°C
A
Modbus IP address
0X00-0XFF
01
B
baudrate
01: 9600; 02: 19200; 03: 38400; 04:
56000; 05: 115200
1
C
Working mode
0: Thermostatic mode
1: Dry contact mode
0
The controller CURTAIN HMI controller can work in one
of two modes:
•thermostatic mode - the device is switched on / off
if the room temperature falls below the temperature
set on the controller (or rises above this temperature
if the controller is in cooling mode)
•dry contact mode - allows the operation of the device
in dependence to the door sensor connected to the dry
contact; when the dry contact is closed (i. e. closed
door in case of NC door sensor), the curtain remains
off and the valve is closed; when the dry contact
is open (i. e. door is opened for NC door sensor),
the curtain fans are switched on and the connected
valve opens
Wiring diagram
Installing
This product is suitable for box 86 x 86 mm or Ø 60 mm.
1. Connect the wire of power and other equipment into
the terminals.
2. Fix the wall plate into the wall box by a screwdriver.
3. Connect the LCD board into the wall plate.
WARNING: Please arrange the professional
technician to install this product according to installation
drawing and instruction.
RISK OF ELECTRICAL SHOCK: Disconnect power supply
before making electrical connection. Contact
with components carrying hazardous voltage can cause
electrical shock and may result in severe personal injury
or death.

Other REVENTON Controllers manuals

REVENTON HMI SINGLE User manual

REVENTON

REVENTON HMI SINGLE User manual

REVENTON HC 3.0 A User manual

REVENTON

REVENTON HC 3.0 A User manual

Popular Controllers manuals by other brands

Exlar EL120 Installation and service manual

Exlar

Exlar EL120 Installation and service manual

RLE Technologies SeaHawk 10K quick start guide

RLE Technologies

RLE Technologies SeaHawk 10K quick start guide

Licht MFC-200/P Technical manual

Licht

Licht MFC-200/P Technical manual

Vitlab 1630500 operating manual

Vitlab

Vitlab 1630500 operating manual

Micronix MMC-10 Series Reference manual

Micronix

Micronix MMC-10 Series Reference manual

Honeywell Touchpoint 1 Technical manual

Honeywell

Honeywell Touchpoint 1 Technical manual

Kelly Jaguar KLS9650NE user manual

Kelly

Kelly Jaguar KLS9650NE user manual

Moeller Xcomfort CAAE-01/01 Assembly instructions

Moeller

Moeller Xcomfort CAAE-01/01 Assembly instructions

American Dynamics ADTT16E Touch Tracker installation instructions

American Dynamics

American Dynamics ADTT16E Touch Tracker installation instructions

Smartgen HGM8100A user manual

Smartgen

Smartgen HGM8100A user manual

Parker 650V series Technical manual

Parker

Parker 650V series Technical manual

quiko QK-CE220BATRL user manual

quiko

quiko QK-CE220BATRL user manual

Superior Electric POWERSTAT FRM2000 Series instructions

Superior Electric

Superior Electric POWERSTAT FRM2000 Series instructions

LG MultiSITE VM3 Startup guide

LG

LG MultiSITE VM3 Startup guide

MOBA MOBA-Matic MMC-1000 user manual

MOBA

MOBA MOBA-Matic MMC-1000 user manual

Mini-Circuits ZHL-2425-250X+ Mounting instructions

Mini-Circuits

Mini-Circuits ZHL-2425-250X+ Mounting instructions

miniBatt PRO VR user manual

miniBatt

miniBatt PRO VR user manual

Datapath VSNMicro N600 quick start guide

Datapath

Datapath VSNMicro N600 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.