Form CP-MAPSIII-D19, Doc No 303069, Page 6
3.1 Supply Fan
Control
Uponacallforthesupplyfan,thesupplyfanwillstart.Iftheunitisconguredwitha
100% outside air damper, the damper actuator is electrically interlocked such that the
supply fan cannot start until the damper is 80% open.
When the Supply fan is commanded off, any active heating or cooling operation will be
shut down and the supply fan will stop after an adjustable time delay.
Whenthesupplyfan,cooling,heatinganddehumidicationcontactsareopenthesupply
fan is OFF. No other functions can automatically turn the fan ON except test mode.
A 30-second acceleration and deceleration rate for the supply fan to ramp between the
minimum and maximum motor frequency is factory set via the unit variable frequency
drive.
The supply fan will operate in one of the following six conditions.
1. High - Low Fan Speed Control (VFC1)
The variable frequency drive is commanded ON from NO1. There are two fan
speed states - active heating/cooling and fan only. When the fan is ON and the
heating or cooling contacts are closed, the unit will operate to high fan speed.
When the fan is ON and the cooling or heating contacts are open, the supply fan
will operate on low fan speed.
2. Duct Static Pressure Control (0.0” to 2.5” iwc) (Option VFC3)
The variable frequency drive is commanded ON from NO1. The fan modulates
between the user adjustable minimum and maximum fan speed setpoints using a
PI loop to maintain the duct static pressure setpoint (+0.5”w.c. default).
3. Summer/Winter Constant Volume (Option VFC9)
The variable frequency drive is commanded ON from NO1. The unit ramps up to
a user set supply fan speed setting. There are two individual supply fan speed
% setpoints one for heating and one for cooling. When the unit is in Space or
Neutral Air Heating, the supply fan will use the heating speed % setpoint. When
the unit is in any other mode, the supply fan will use cooling speed % setpoint.
The intake dampers operate based upon state, mode, and one of six user selected
sequences. The dampers are normally open and operational in the occupied mode and
closed to outside air in the unoccupied mode, depending on the user selection.
1. 100% OA, (Option GF2A)
When the unit is to start, the outside air damper will modulate (point Y1 =
10Vdc) and the supply fan will be commanded ON (point NO1 = On). If the
unit is equipped with an outside air damper, the damper actuator is electrically
interlocked to the fan start/stop such that the supply fan cannot start until the
damper is 80% open. Options AR8, AR2D, AR2L, and AR2Y are electrically
interlocked with the supply fan.
OFF and Alarm Modes
The damper will be closed (Y1 = 0%).
2. External 0-10vdc Input, (Option GF1)
Occupied & Unoccupied Mode
The dampers will modulate from 0-100% (point Y1 = 0 to 10 Vdc) based user
supplied 0 - 10 Vdc input. 0 Volts input is 0% damper while 10V input is 100%
damper position. This is not allowed with Options AR8, AR2D, AR2L & AR2Y. The
software does not prevent the selection of this option. The fan status switch will
handletheblockowcondition.ThedamperisNOTelectricallyinterlockedwith
the supply fan.
Unoccupied OFF and Alarm Modes
The damper will be closed (Y1 = 0%).
NOTE: For unoccupied operation of this damper control option, set the unoccupied
ventilation enable variable to ON
3.0 Controls
3.2 Intake Damper
Control