Rezontech RFD-2000X User manual

Flame detector ( UV/IR Type )
RFD-2000X User’s Manual
Rezontech Co., Ltd

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 1 -
TABLE OF CONTENTS
1 Product Overview
1.1 Product Introduction
1.2 Contents of User Manual
1.3 Revision of User Manual
1.4 Warranty
2 Technical Specifications
2.1 Electrical Specifications
2.2 Mechanical Specifications
2.3 Environmental Specifications
3 Installation
3.1 Unpacking & Checking
3.1.1 Product Compositions
3.1.2 Components
3.1.3 Necessary tools
3.2 Selection of Installation Location
3.2.1 Cone of Vision
3.2.2 Range of Detection
3.2.3 Environment points to be considered when use
3.3 Installation and Electrical Wiring
3.3.1 Wiring Detector
3.3.1.1 Conduit Installation
3.3.1.2 Cable Selection for Electrical Wiring
3.3.1.3 Conduit or Gland Standard (Connector)
3.3.2 Using of bracket during installation
3.3.2.1 Bracket Specification
3.3.2.2 Installation of detector with bracket to the wall or the ceiling
3.3.3 Terminal Wiring
3.3.3.1 Relay Signal
3.3.3.2 4-20mA (Current Source Wiring Contact)
3.3.3.3 RS485
3.3.3.4 External Recovery Signal Electrical Wiring
3.3.3.5 Signal of Electrical wiring for external remote self-test
3.3.4. Installation/Setting
3.3.4.1 Sensitivity setting
3.3.4.2 Setting of delay time
3.3.4.3 Setting of others function
3.3.5. Ground connection
3.3.5.1 Internal Ground connection method
3.3.5.2 External Ground connection method

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 2 -
4 Operation
4.1 Product checklist
4.2 Initial Operation of Product
4.3 Safety Handling
4.4 Product Testing
5 Maintenance & Troubleshooting Instructions
5.1 Tools of Maintenance and Products Training
5.2 Maintenance Procedures
5.3 Troubleshooting
5.3.1 No LED responds after the power connection.
5.3.2 Yellow LED blinking (2Hz)
5.3.3 When receiver unable to detect various signal
6 Customer Support
6.1 Contacts Information
7
A
ppendix
7.1
A
bbreviation
7.2 Choosing of Wiring
7.2.1 Reference: Standard Chart for Power Supply Electrical Wiring during
setting (AWG Standard)
7.2.2 Things to be consider when choosing electrical wiring for power supply
7.3 Certification & Approvals

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 3 -
1. Product Overview
1.1 Product Introduction
Model RFD-2000X from Rezontech Co., Ltd. is UV/IR type flame detector. It activates
alarm signal or fire extinguishing system via fire or flame detection. This function can be
used directly with output terminal and through connected control circuits are also available.
Various output methods are available for choice:
ㆍ Dry contact Relays (Fire, Fault, Warning)
ㆍ 4~20mA Current Output
ㆍ RS-485 Communication
RFD-2000X is a product with additional Internal/External recovery feature which enables to
be widely used in difference applications.
1.2 Contents of User Manual
All the information about detectors and its features are described on this handling manual.
its contents consist of 7 different sections as per stated on [Table 1] below .
Title Content
1. Product Introduction General introduction, products overview, brief
introduction on each part
2. Technical Specification Electrical, mechanical and environmental specifications
3. Installation Wiring, mode select, proper installation
4. Operation Operation mode and user interface display
5. Maintenance &
Troubleshooting Maintenance and technical support procedure
6. Customer Support About This product will be customer service will
describe the information
7. Appendix Abbreviations, authentication, and parts will be describe
information about products
[Table 1] Contents of User Manual

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 4 -
1.3 Revision of User Manual
Version Date of Revision Content Remarks
1.0 March, 2010 Registration of document
2.0 March, 2012 para# 2.2, 3.2.2, 3.3.2,
3.3.4 amendment
3.0 March, 2013 para# 3.2.2.1, 3.3.3.3,
3.3.4.1, 6.1, 7.3 amendment
[Table 2] Revision of User Manual
1.4 Warranty
Rezontech warrants the Models RFD-2000X to be free from defects in workmanship or
material under normal use and service within two years from the date of shipment.
Rezontech will repair or replace without charge any such equipment found to be defective
during the warranty period. Full determination of the nature of, and responsibility for,
defective or damaged equipment will be made by Rezontech’ personnel.
Defective or damaged equipment must be shipped to Rezontech’ plant or representative
from which the original shipment was made. In all cases this warranty is limited to the
cost of the equipment supplied by Rezontech. The customer will assume all liability for
the misuse of this equipment by its employees or other personnel.
All warranties are contingent upon proper use in the application for which the product was
intended and does not cover products which have been modified or repaired without
Rezontech’ approval, or which have been subjected to neglect, accident, improper
installation or application, or on which the original identification marks have been removed
or altered.
Except for the express warranty stated above, Rezontech disclaims all warranties with
regard to the products sold, including all implied warranties of merchantability and fitness
and the express warranties stated herein are in lieu of all obligations or liabilities on the
part of Rezontech for damages including, but not limited to, consequential damages
arising out of, or in connection with, the performance of the product.

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 5 -
2. Technical Specifications
2.1 Electrical Specifications
[Figure 1] TB1 Terminal address at product cover
2.1.1 Electrical
ㆍ Recommended Operating Voltage : 24VDC
ㆍ Rating Voltage : 17VDC ~ 32VDC
ㆍ Max Input Voltage : 36VDC
ㆍ Max Consumption Power : 1.8W (at 32VDC )
ㆍ Normal Average Current : approximate 35mA (at 24VDC)
ㆍ Max Operating Current : approximate 70mA
(at 17VDC, during detection of fire or self-diagnosis test)
2.1.2 Relay Output
ㆍ 2A 28VDC, 4A 125VAC, 2A 250VAC
ㆍ Dry Contact
ㆍ A(Normally Open) or B(Normally closed)
2.1.3 4~20mA Current Output
ㆍ Non-isolation output, Common 24V-_IN(-Power)
ㆍ Max. Terminating Resistance : 500Ω
ㆍ 0mA (+0.5mA) : Connection Fault
ㆍ 2mA (±0.5mA) : Self-diagnosis test Fault
ㆍ 4mA (±0.5mA) : Normal
ㆍ 8mA (±0.5mA) : IR Detection
ㆍ 12mA (±0.5mA) : UV Detection
ㆍ 16mA (±0.5mA) : Warning (UV and IR Detection, fire occurs during delay time)
ㆍ 20mA (±0.5mA) : Fire Detection

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 6 -
2.1.4 RS485 Communication
ㆍ Non-isolation output (2 wiring)
ㆍ Communication Speed : 9600bps
2.1.5 LED Indicator
ㆍ Two LED's(Yellow, Red) indicator
- Yellow LED : Provides indication of Normal or Fault state
- Red LED : Provides indication of Warning or Alarm state
ㆍ Product reset process : Yellow & Red LED intersection blinking repeatedly (3 sec)
ㆍ Normal : Yellow LED blinking (0.5Hz)
ㆍ Power supply or Self-diagnosis test fault : Yellow LED blinking (2Hz)
ㆍ Warning : Yellow LED blinking (0.5Hz) and Red LED blinking (2Hz)
ㆍ Alarm : Yellow LED blinking (0.5Hz) and Red LED lighting
ㆍ Warning at BIT Fault : Yellow LED blinking (2Hz) and Red LED blinking (2Hz)
ㆍ Alarm at BIT Fault : Yellow LED blinking (2Hz) and Red LED lighting
[Figure 2] Product Image LED position indicator
Yellow LED Green LED
Grounding

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 7 -
2.2 Mechanical Specifications
[Figure 3] Front, inch[mm]
[Figure 4] Side, inch[mm]
[Figure 5] Combination of Detector and Bracket, inch[mm]
ㆍ Enclosure (Material) : 316 Stainless Steel
ㆍ Weight : Body - approximate 2.4㎏, Overall - approximate 3.4㎏
ㆍ Dimension(Body) : W5.3[134] × H4.6[117] × D4.7[120] (inch[mm])
ㆍ Dimension(Overall) : W5.3[134] × H6.4[163] × D14.4[366] (inch[mm])
ㆍ Color : Metal
ㆍ Electrical connection (External) : 1/2 inch NPT-14, M20 X 1.5(Option)
ㆍ Wire gauge (Power supply & Signal) : AWG #14 (2.08㎟) ~ #24 (0.205㎟)
ㆍ Hazardous Area Approvals : Class I Div.1 Groups B,C and D
Class II Div.1 Groups E,F and G
Class III

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 8 -
ㆍ Explosion proof : ATEX Ex db IIB+H2 T6 (75℃)
ㆍ Water and Dust Tight : IP67, NEMA Type 4X
2.3 Environmental Specifications
ㆍ Operating Temperature : -40℃ ~ +75℃
ㆍ Storage Temperature : -50℃ ~ +80℃
ㆍ Humidity : Relative humidity 95%

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 9 -
3. Installation
3.1 Unpacking & Checking
Please check the external condition of detector when unpacking the product carefully. If
there is any damage on the products, please contact the local distributor immediately or
any trouble in used products, please send it to A/S center with fee applied.
3.1.1 Product Compositions
ㆍ RFD-2000X 1EA
ㆍ BK-2(Bracket) 1EA
ㆍ Spare Bolt 1set
3.1.2 Components
3.1.2.1 Fundamental components
Component standard Q'ty (pcs) Description
Hexagon wrench Bolt M6×10 2 Join the Detector and Bracket
Hexagon wrench Bolt M6×35
(OEM) 4 Join the Detector
Metric button screw (+) M5×30 4 Install the Bracket
[Table 3] Fundamental components
3.1.2.2 Spare components
Component Standard Q'ty (pcs) Description
Hexagon wrench Bolt M6×10 2 Join the Detector and Bracket
Hexagon wrench Bolt M6×35
(OEM) 4 Join the Detector
Metric button screw (+) M5×30 4 Install the Bracket
[Table 4] Space Components
3.1.3 Necessary tools
Tool name Standard Q'ty (pcs) Description
Hexagon wrench driver Metric,5M 1 Join the detector, bracket
[Table 5] Necessary tools

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 10 -
3.2 Selection of Installation Location
Minimum information will be provided below for the location selection of installation.
Please refer the information according to the purpose of your use.
3.2.1 Cone of Vision
3.2.1.1 Fuel
ㆍ N-Heptane
3.2.1.2 Cone of Vision
ㆍ Horizontal / Vertical : 90° ( 45° up, down, left, right at 50% of detection range )
[Figure 6] Cone of Vision
3.2.2 Range of Detection
The detection distance for the alarm level is 99ft(30m) from the standard fire.
The detector has two response levels.
ㆍWarning
ㆍAlarm
3.2.2.1 Detection Range of Fuels
Type Of Fuel Maximum Distance (ft / m)
N-Heptane 99 / 30
[Table 6] Range of Fuels Detection

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 11 -
3.2.2.2 Detection Range of False Alarm
The detector is immune to a variety of false alarm sources. Representative samples of
detector's response from false alarm sources are listed below.
Radiation Source Immunity Distance ft(m)
Indirect or reflected sunlight No fire alarm
Incandescent lamp 100W No fire alarm
Fluorescent light 40W No fire alarm
Resistive electric heater 1500W No fire alarm
Blue, Green dome light XXXW No fire alarm
Hot plate (200℃) No fire alarm
Halogen lamp 500W (Glass) No fire alarm
Halogen lamp 1000W (Quartz lamp) 14.5 (4.4)
Grinding metal 3.3 (1)
Arc welding (5mm, 200A) 20 (6)
[Table 7] Types of False Alarm source and Its Relationship between Flame Detection
3.2.3 Environment points to be considered when use
ㆍ Installation places and availability of fuels (Family of Hydrocarbon and related
flame detection)
ㆍ install product according to its Installation space and it areas of dangerous
(internal/external etc)
ㆍ Select place of installation according to detection range and field of view
ㆍ Temperature range [Min/Max] of operation/installation
ㆍ Select the place to avoid the area with obstructed object for the appropriate installation
ㆍ Select the place to avoid the area with false alarm statuses affect to the fire detection
※ The above points of considerations are based on the basic environmental standard and
they are vary different between countries in terms of environment, usage, users etc.

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 12 -
3.3 Installation and Electrical Wiring
3.3.1 Wiring the Detector
3.3.1.1 Conduit installation
ㆍ Use 1/2 inch NPT-14 or M20X1.5 conduit connection or suitable explosion-proof gland
to assemble the cable and conduit to the detector.
ㆍ When using conduit connection for Division installation, conduit seals must be installed
within 18 inches (450mm) from the enclosure.
ㆍ When using conduit connection for ATEX installation, conduit seals must be placed at
enclosure.
ㆍ Install the conduit including drain holes place downward to avoid water condensation in
the detector.
ㆍ Any conduit entry not used during installation shall be plugged with suitably rated and
approved conduit/blanking plug.
3.3.1.2 Cable Selection for Electrical Wiring
ㆍ All cables to the detector should be well shielded for EMC.
ㆍ Wire gauge for detectors power supply wires.
AWG No. Diameter(㎜) Cross section(㎟)
24 0.511 0.205
23 0.573 0.258
22 0.644 0.326
21 0.723 0.410
20 0.812 0.653
19 0.912 0.653
18 1.02 0.823
17 1.15 1.04
16 1.29 1.31
15 1.45 1.65
14 1.63 2.08
[Table 8] American Wire Gauge Standard
3.3.1.3 Conduit or Gland Standard (Connector)
ㆍ Cable Conduit Standard : 1/2 inch NPT-14, M20 X 1.5(Option)
ㆍ Water and Dust : IP67, NEMA Type 4X
3.3.2 Using of bracket during installation

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 13 -
3.3.2.1 Bracket Specification
ㆍ Angle adjustment : Horizontal 180° , Vertical 180°, scale indications 15° each
When you arrange the angle, M4 Set Screw and M10-25 Hexagon Wrench Bolt
has to be released first and tighten again with 24 (N・m) Torgue for Hexagon
Wrench Bolt and 1.5 (N・m) Ttorgue for Set Screw.
ㆍ Enclosure Material : 316 Stainless Steel
ㆍ Weight : Body - approximate 2.4㎏, Overall - approximate 3.4㎏
ㆍ Dimension(Body) : W5.3[134] × H4.6[117] × D4.7[120] (inch[mm])
ㆍ Dimension(Overall) : W5.3[134] × H6.4[163] × D14.4[366] (inch[mm])
ㆍ Color : Metal
ㆍ Wall mounted size : 6Φ × 4 (5mm bolt)
[Figure 7] Bracket BK-02
3.3.2.2 Installation of detector with bracket to the wall or the ceiling
ㆍ Necessary tool : Hexagon Wrench Driver, Screw Driver
ㆍ component : Metric M6-10 × 2 pcs, Metric M5-30 × 4pcs
ㆍ Flame detector's body and cover has to be combined with M6-35 Hexagon Wrench
Driver at 5(N・m) Torque.
ㆍ Flame detector and bracket is connected with Hexagon Wrench Bolt at 5(N・m) Torque.

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 14 -
[Figure 8] 4 Holes on bracket
for mounting detector
[Figure 9] Wall mount
[Figure 10]
Ceiling mount
ㆍ Mount the bracket with M5-30 × 4pcs bolts. Refer to Figure 8
ㆍ Detector can be installed on the wall or the ceiling with bracket. Refer to Figure 9, 10

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 15 -
3.3.3 Terminal Wiring
This is the reference for the user on how all the connection of the electrical wiring are
connected to each system or product as per stated below.
3.3.3.1 Relay Signal
- Fire Relay
The following signal occurs when fire is detected
ㆍ The operational status of fire relay according to detector's condition.
TB1 Fire Relay
Relay status
Normal
(De-Energized)
Fire
(Energized)
5,20 ALM_N.C Closed Open
6,19 ALM_N.O Open Closed
7,18 ALM_COM Common Common
- 2A@28VDC, 4A@125VAC, 2A@250VAC
[Table 9] Fire Relay operated
ㆍ Interlink wiring of Power Supply, Fire Relay, Fault Relay
[Figure 11] Terminal wiring diagram schematic at fire alarm relay

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 16 -
- Fault Relay
This signal shows up when product is not working properly or the fire signal is not
functional.
※ Before power supply is on, FLT_N.O is connected because Fault Relay is not in error
status.
ㆍ Fault Relay Operated
Type of Fault Descriptions
Power Supply The error status of external and internal power supply
Self Testing The error status of basic function (fire detection)
[Table 10] Fault Relay Operated
ㆍ Fault Relay operated according to detector's condition
TB1 Fault Relay
Relay Status
Normal
(Energized)
Fault
(De-Energized)
3,22 FLT_N.C Open Closed
3,22 FLT_N.O Closed Open
4,21 FLT_COM Common Common
- 2A@28VDC, 4A@125VAC, 2A@250VAC
- Change Fault Relay's FLT_N.O/N.C mode accordingly by switching the jumper.
- FLT_N.O is available by default
[Table 11] Fault Relay Operating Status

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 17 -
ㆍ Power supply Fire, Relay and Fault Relay wires interlink
(indication of Jumper setting location)
[Figure 12] Terminal wiring diagram schematic at fault relay (Internal)
[Figure 13] Terminal wiring diagram schematic at fault relay (External)

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 18 -
ㆍ Loop connection with several detectors
This is Loop type connection method which can generate alarm and fault signal. But
with this connection, detection performance is blocked when one flame detector is in fault
condition. So this method is only avaliable with specific receiver which can check fault
signal frequently and automatically.
[Figure 14] Terminal wiring diagram schematic for LOOP connection

Co.,Ltd. UV/IR Type Flame Detector RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 19 -
- Warning Relay
This signal shows when fire is detected at primary stage before the real fire is confirmed.
This signal only occurs within delay time.
ㆍ Warning Relay operated according to detector's condition
TB1 Warning Relay
Relay status
Normal
(De-Energized)
Warning
(Energized)
17 WARN_N.C Closed Open
16 WARN_N.O Open Closed
15 WARN_COM Common Common
2A@28VDC, 4A@125VAC, 2A@250VAC
[Table 12] Warning Relay Operating Status
ㆍ Interlink electrical wiring of Power supply Fire Relay, Fault Relay, and Warning Relay
[Figure 15 ] Terminal wiring diagram schematic at fault and warning relay
Table of contents
Other Rezontech Security Sensor manuals
Popular Security Sensor manuals by other brands

NA-DE
NA-DE 10970 quick start guide

Dectris
Dectris EIGER2 S 1M-RW Technical specifications

Singing rock
Singing rock SIR manual

Bosch
Bosch ISC-BPQ2-W12 installation guide

Honeywell
Honeywell Small SATCOM Operation, installation, and maintenance manual

Bosch
Bosch TriTech+ Professional ISC-PDL1-WAC30G installation manual