Safety Instructions:
• Read these instructions carefully and completely before instal-
lation. These instructions cannot cover every possible installa-
tion, operation or maintenance situation. Further information
can be obtained from the product datasheets, which can be
downloaded, from the Internet at http://www.automationdi-
rect.com.
• These converters are constructed in accordance with the safety
requirements of IEC/EN60950-1, UL60950-1 and UL508.
They are approved (UL and cUL) in accordance with UL508,
and fulfill the requirements of the Low Voltage Directive
(LVD).
• Before any installation, maintenance or modification work, be
sure that the main switch is switched off and prevented from
being switched on again. Non-observance, touching of any live
components or improper handling of this power supply can
result in death, severe personal injury or substantial property
damage. Proper and safe operation is dependent on proper
storage, handling, installation and operation.
• Compliance with the relevant national regulations (in the USA,
Europe and other countries) is required. Before operation is
started the following conditions must be met:
• Connection to the source in compliance with national
regulations.
• Use of stranded wires, all strands must be fastened in
the terminal blocks.
• Input cables must be sufficiently fused.
• Degree of protection I to IEC536.The non-fused
protective earth connection must be connected to the
FG terminal (Protection Class I).
• All output wires must be rated for the power supply
output current and must be connected with the
correct polarity.
• Sufficient cooling must be assured.
• Never work on the DC/DC converter if power is connected!
There is risk of electric arcs and electrical shock, which can
cause death, severe personal injury or substantial property
damage.
• Warning: Hazardous voltages and components storing a very
substantial amount of energy are present in this power supply
during normal operating conditions. However, these are inac-
cessible. Improper handling may result in an electric shock
or serious burns! Do not open the converter until at least 5
minutes after it has been disconnected from the input source
on all poles.
• Allow only trained personnel to open the converter.
• Do not insert any objects into the converter. Actuate the
output voltage adjustment potentiometer by using an insulated
screwdriver only.
• Keep away from fire and water.
Installation Instructions:
• This converter is designed for professional indoor systems. The
converter must not be accessible while in operation. Allow
installation and service by qualified personnel only.
• Do not operate without PE connection! To comply with
EMC and safety standards (CE mark, approvals) the power
supply is to be operated only if PE terminal is connected to the
non-fused ground conductor.
• Mount the unit horizontally on a flat vertical surface to provide
proper ventilation. You cannot mount the unit vertically,
upside down, or on a horizontal surface. Do not cover any
ventilation holes. Please allow minimum free space of and
50mm (2”) above and below the converter for air convection.
Observe power derating.
• The internal fuse is not accessible, as it is not to be replaced
by the user. If this internal fuse has blown, the converter most
likely has an internal defect and, for safety reasons, must be
discarded, or, if under warranty, returned. In case this internal
fuse has to be replaced in the field, replace only with same type
and rating of fuse for continued protection against risk of fire.
• Recycling: The unit contains elements that are suitable for recy-
cling, and components that need special disposal. Please make
sure that the power supply is recycled in an environmentally
friendly way at the end of its service life.
• Warning: To minimize the risk of potential safety problems,
follow all applicable local and national codes that regulate the
installation and operation of your equipment. These codes
vary from area to area and it is your responsibility to determine
which codes should be followed and to verify that the equip-
ment, installation and operation are in compliance with the
latest revision of these codes.
• Equipment damage or serious injury to personnel can result
from the failure to follow all applicable codes and standards.
We do not guarantee the products described in this publica-
tion to be suitable for your particular application, nor do we
assume any responsibility for your product design, installation
or operations.
• If you have any questions concerning the installation or opera-
tion of this equipment, or if you need additional information,
please call us at 770-844-4200.
• This publication is based on information that was available
at the time it was printed. At Automationdirect.com® we
constantly strive to improve our products and services, so we
reserve the right to make changes to the products and/or publi-
cations at any time without notice and without any obligation.
This publication may also discuss features that may not be
available in certain revisions of the product.
RHINO Industrial Power Supplies PSP Series , DC - DC models Installation Instructions Rev: 06/18 1-800-633-0405
To Install
1. Read and follow Safety and Installation instructions.
2. Hook top of converter’s DIN rail clip on DIN rail.
3. Push down tab on top of converter to open DIN rail clip.
4. Rotate converter into DIN rail and release tab.
5. Verify the DIN rail clip is securely fastened on DIN rail.
6. Connect wires as indicated on converter.
The unit can be mounted on a
chassis or wall using the includ-
ed mounting bracket.