Flex™ H6EX-A2 Installation Manual

H6EX-A2 Installation Manual
Rev D
Page 1 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
Table of Contents
Table of Contents .................................................................................................. 1
List of Figures....................................................................................................... 1
Sensor Description ................................................................................................. 2
Hazardous Location Information ................................................................................. 2
Applicable Standards .............................................................................................. 3
Normal Locations ............................................................................................... 3
Hazardous Locations............................................................................................ 3
EMC ............................................................................................................... 3
H6EX-A2 Instructions for Safety .................................................................................. 4
Putting into Service............................................................................................. 4
Use ................................................................................................................ 4
Assembling and Dismantling ................................................................................... 4
Maintenance ..................................................................................................... 5
Installation and Mounting ...................................................................................... 5
Adjustment ...................................................................................................... 6
Markings ............................................................................................................. 7
H6EX-A2 Connector Wiring Tables ............................................................................... 8
Revision History .................................................................................................... 9
List of Figures
FIGURE 1: H6EX-A2 CONTROL DRAWING ........................................................................................................................ 4
FIGURE 2: H6EX-A2 DIMENSIONS AND MOUNTING (INCHES [MM]).................................................................................... 5
FIGURE 3: H6EX-A2 AXIS ORIENTATIONS........................................................................................................................ 6
FIGURE 4: TOP SURFACE MARKINGS FOR MODEL AND HAZARDOUS LOCATION INFORMATION ................................................... 7
FIGURE 5: FRONT SURFACE MARKINGS FOR SERIAL NUMBER............................................................................................... 7
FIGURE 6: FACTORY CONFIGURED DEFAULTS LABEL ........................................................................................................... 7

H6EX-A2 Installation Manual
Rev D
Page 2 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
Sensor Description
The H6EX-A2 sensor is an Intrinsically Safe inclinometer that provides high accuracy, dual axis inclination over a
range of ±180° for Hazardous Locations. The H6EX-A2 must be used with a certified isolation barrier. It is
ATEX/IECEx/MET (US)/CSA approved for use in the following hazardous locations:
•Class I & II, Division 1
•Zone 0 & 20.
The sensor incorporates MEMS accelerometers referenced to gravity with integrated temperature compensation
over the full operating range of -40° to +85°C for absolute accuracy. It has both current and voltage analog
output options available. Each output is linear with respect to the input angle directly.
The H6EX-A2 provides two continuous, fully configurable, analog outputs. These outputs are individually
settable to current from 4mA to 20mA or voltage from 0V to 10V, are settable to any axis, and are factory
configurable to match any angle range and min/max analog values.
Hazardous Location Information
Intrinsically safe equipment is defined as “equipment which is incapable of releasing sufficient electrical or
thermal energy under normal or abnormal conditions to cause ignition of a specific hazardous atmosphere
mixture in its most easily ignited concentration.”
The H6EX-A2 is approved to:
ATEX and IECEx (Gas):
II 1G Ex ia IIC T4 Ga (-40°C≤Tamb≤+85°C)
ATEX and IECEx (Dust):
III 3D Ex ia IIIC T200°C Da (-40°C≤Tamb≤+85°C)
US and Canada (Gas):
Class I, Division 1, Groups A, B, C, D
Class I, Zone 0, AEx ia IIC T4 Ga (-40°C≤Tamb≤+85°C)
US and Canada (Dust):
Class II, Division 1, Groups F, G
Zone 20, AEx ta IIIC T200°C Da (-40°C≤Tamb≤+85°C)
Certificate Numbers:
SEV 18 ATEX 0217
IECEx SEV 18.0042
MET E114209
The H6EX-A2 sensor is intrinsically safe and suitable for all areas except mining, can be used in areas with
continuous, long, or frequent periods of exposure to hazardous gas or dust, is suitable for explosive gas Groups
IIA to IIC and A to D and dust Groups IIIC & F to G, and has temperature group T4 for gas & T200°C for dust. It
also has an extended operating temperature range of -40°C to +85°C.
WARNING: If the equipment is used in a manner not specified by the manufacturer, the protection provided by
the equipment may be impaired.
AVERTISSEMENT: Si l’équipement est utilisé de façon non spécifiée par le fabricant, la protection assurée par
l’équipement peut être altérée.

H6EX-A2 Installation Manual
Rev D
Page 3 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
Applicable Standards
Normal Locations
For use in ordinary/unclassified locations, model H6EX-A2 has been investigated in accordance with:
•UL/CSA 61010 -1 3rd ed.–Electrical Equipment for Measurement, Control, and Laboratory Use; Part 1
Hazardous Locations
For use in Class I Division 1 and Zone 0, model H6EX-A2 has been investigated in accordance with:
•UL 913, 8th ed. –Intrinsically Safe Apparatus and Associated Apparatus for use in Class I, II, and III,
Division 1, Hazardous (Classified) Locations.
•CAN/CSA-C22.2 No. 60079-0:19 - Explosive Atmospheres Part 0: Equipment –General Requirements
•CAN/CSA-C22.2 No. 60079-11:14 - Explosive Atmospheres Part 11: Equipment protection by Intrinsic
Safety "i"
•IEC 60079-0:2017, Edition 7.0 (EN 60079-0:2018) –Explosive Atmospheres Part 0: General Requirements
•IEC 60079-11:2011 6th Edition (EN 60079-11:2012) –Explosive Atmospheres Part 11: Intrinsic Safety "i"
For use in Class II Division 1 and Zone 20, model H6EX-A2 has been investigated in accordance with:
•UL/CSA 60079-0 - Explosive Atmospheres Part 0: Equipment —General requirements
•UL/CSA 60079-31 - Explosive Atmospheres Part 31: Equipment Dust Ignition Protection by Enclosure “t”
•IEC 60079-0:2017, Edition 7.0 (EN 60079-0:2018) –Explosive Atmospheres Part 0: General Requirements
•IEC 60079-31:2013, 2nd edition (EN 60079-31:2014) -Explosive Atmospheres Part 31: Equipment Dust
Ignition Protection by Enclosure “t”
EMC
•EN 61326-1:2013 –Electrical equipment for measurement, control and laboratory use —EMC
requirements
•47 CFR Ch. 1 –FCC Part 15 Class A –Radio Frequency Devices –Subpart B –Unintentional Radiators
•ICES-003 –Issue 6 January 2016 Class A –Interference-Causing Equipment Standard –Digital Apparatus

H6EX-A2 Installation Manual
Rev D
Page 4 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
H6EX-A2 Instructions for Safety
Putting into Service
The H6EX-A2 must be used with a certified Isolation Barrier to supply a nominal +12VDC. The H6EX-A2 has the
following entity parameters:
FIGURE 1: H6EX-A2 Control Drawing
Notes:
A. The H6EX-A2 requires two barriers for operation:
1. A barrier to supply a nominal 12VDC to the unit (pins 1 and 2).
2. A barrier to protect the two analog outputs (pins 6 and 7).
B.
(See note C)
C. The H6EX-A2 ground (pin 2) and all attached barrier grounds MUST be connected together so that Vmax never exceeds its
allowed voltage.
D. Imax (or Ii) is the sum current of all attached barriers.
E. All grounding path connections should be secure, permanent, visible, and accessible. The grounding path resistance
from the farthest barrier to the grounding electrode should not exceed 1 ohm.
F. The installation must be in accordance with the National Electrical Code, NFPA 70, Articles 504 and 505, Canadian
Electrical Code C22.1 Section 18, and ANSI/ISA-RP12.06.01.
Use
The sensor is designed to measure dual-axis inclination and output an analog signal.
Assembling and Dismantling
The H6EX-A2 shall not be serviced, dismantled, or re-assembled by the user.
Associated Apparatus with Entity
Concept Parameters:
Voc2(or Uo2)
Isc2(or Io2)
Po2
La2 (or Lo2)
Ca2 (or Co2)
Rieker Instruments
H6EX-A2
Vmax (or Ui) = 13V
Imax (or Ii) = 270mA
Pi= 2.875W
Ci= 0.977µF
Li= 0.0mH
Associated Apparatus with Entity
Concept Parameters:
Voc1(or Uo1)
Isc1(or Io1)
Po1
La1 (or Lo1)
Ca1 (or Co1)
Hazardous (Classified) Location
Class I, Zone 0, Group IIC
Class I, Division 1, Groups A, B, C, D
Non-Hazardous Location
- (pin 2)
Aout2 (pin 7)
Aout1 (pin 6)
+ (pin 1)

H6EX-A2 Installation Manual
Rev D
Page 5 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
Maintenance
No maintenance is required.
Installation and Mounting
1. On the mounting plane, prepare surface with
three tapped holes, H1-H3 for M4/M4.5
mounting screws. H2& H3 are 3.815”
[96.9mm] from H1. See Figure 2. NOTE that
the single hole on the side with the two slots
is not meant to be used for mounting.
2. Mount inclinometer to mounting plane using
M4/M4.5 mounting screws. Use the two slots
for fine adjustments.
Default Horizontal Mount Option: Axis
Orientation
The 0° orientation for the horizontal-mount
option H6EX-A2 is a desktop, level position.
•For the X-axis, looking at the unit from
the side with the connector facing to
the right (top right of Figure 3), a
clockwise rotation from the zero
position is considered positive and a
counter-clockwise rotation from the
zero position is considered negative.
•For the Y-axis, looking at the unit from
the front with the connector facing
towards you (top left of Figure 3), a
clockwise rotation from the zero
position is considered positive and a
counter-clockwise rotation from the
zero position is considered negative.
Alternate Vertical Mount Option: Axis
Orientation
The 0° orientation for the vertical-mount option of the H6EX-A2 is a vertical position with the connector down.
•For the X-axis, looking at the unit from the top side with the connector facing down (bottom left of
Figure 3), a clockwise rotation from the zero position is considered positive and a counter-clockwise
rotation from the zero position is considered negative.
•For the Y-axis, looking at the unit from the side with the connector facing down and the mounting
surface to the left (bottom right of Figure 3), a clockwise rotation from the zero position is considered
positive and a counter-clockwise rotation from the zero position is considered negative.
FIGURE 2: H6EX-A2 Dimensions and Mounting (Inches [Mm])

H6EX-A2 Installation Manual
Rev D
Page 6 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
Adjustment
No mechanical adjustment is required.
No software adjustments of H6EX-A2 analog output parameters are permitted. Scaled analog parameters can
be factory-set only and must be selected at time of purchase.
FIGURE 3: H6EX-A2 Axis Orientations

H6EX-A2 Installation Manual
Rev D
Page 7 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
Markings
The H6EX-A2 shall be marked with the following markings:
FIGURE 4: Top Surface Markings for Model and Hazardous Location Information
FIGURE 5: Front Surface Markings for Serial Number
In addition, the factory defaults label, located on the box of the H6EX-A2 sensor, provides the configured
analog output parameters.
FIGURE 6: Factory Configured Defaults Label

H6EX-A2 Installation Manual
Rev D
Page 8 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
H6EX-A2 Connector Wiring Tables
TABLE 1: H6EX-A2 MALE 8-PIN INPUT CONNECTOR WIRING
PIN
FUNCTION
1
SUPPLY VOLTAGE +12VDC
2
POWER / SIGNAL COMMON
3
NO CONNECTION
4
NO CONNECTION
5
NO CONNECTION
6
ANALOG OUTPUT 1
7
ANALOG OUTPUT 2
8
NO CONNECTION
TABLE 2: CURRENT SENSE
Rsense is dependent upon supply voltage and cable/wire resistance.
Ensure the following equation is met:
QUICK REFERENCE
SUPPLY VOLTAGE
SENSE RESISTOR
12V
200-350 OHMS
NOTE: The H6EX-A2 Sensor’s Chassis Ground is NOT the same as the signal ground for the current output
return. The analog output return must be connected to the POWER/SIGNAL COMMON (pin 2).

H6EX-A2 Installation Manual
Rev D
Page 9 of 9
RIEKER INC • 34 MOUNT PLEASANT ROAD • ASTON • PA • 19014 • USA
610-500-2000
fax: 610-500-2002
support@riekerinc.com
www.riekerinc.com
The information and material presented may not be published, broadcast, rewritten, or redistributed without the expressed written consent of Rieker®Inc.
This document is an Ex Controlled Document and may not be modified without prior Notifying and Certifying Body approval.
©2018-2021 Rieker®All Rights Reserved.
FORM NUMBER: H6EX0010_05/18 UPDATED: 4/29/2021
Revision History
Revision
Revision Date
Description of Changes
Approved By
Rev A
05/30/2018
Initial Release.
Caleb Swieson
Rev B
12/26/2018
Updated entity parameters.
Caleb Swieson
Rev C
01/20/2021
Add dust atmosphere certifications. Updated applicable standards.
Caleb Swieson
Rev D
04/22/2021
Updated Controlled Document warning per CN 21-04-008.
Caleb Swieson
Table of contents