12
4−4.Cautioninthesystemengineering
Unstablepowerandnoisemaycauseerrorofperformanceandalarm.
Forthesystemtousethisunit,itisrequiredtomakedesignbasedonthismanual
descriptions.
(1) Stablepowerused
Whilethesystemgetsstableatpoweronorinstantaneouspowerfailure,theexternaloutputandalarmcontact
maybeonandthecareforitmustbetaken.Insuchcase,usethestandbybatteryortakeanappropriate
actioninthereceiverside.Supplythefollowingpowertothisunit
Powervoltage DC24V±10%
Powerfailure
tolerancetime
Approx50msec.
(Forpowerfailureof50msec,itre-starts)
To warrant the continuous operation, install the UPS
(UninterruptedPowerSupply)orstandbybatteryoutside.
Others
Donotsharethepowerinvolvingwithhighpowerloadand
highfrequencynoise.
Accordingtorequirement,uselinefilterandseparateitfrom
noisesource.
(2) Designingtoconsiderradiation
Wheninstalltheclosedself-standingcontrolpanel,mountthefansintheupperandlowerpart.
(3) Lightningmeasures
Lightningsurge
Thereistheproblem“Lightning”.Whenmakeoutdoorwiringofcableatfactoryorplantsetcor
whenmakeaparallelwiringinthesameductwiththecableinfromoutdoorevenattheindoor
wiring.Ifthelightningisahugegenerationsource,thecableisareceptionantennaandthereis
thecasethatcableconnectinginstrumentisbroken.Itisimpossibletopreventthegenerationof
lightning. Ifthecableshouldputinmetaltubeorlaidintheunderground,itisimpossibletoprevent
theinductivelightningsurgegeneratingfromthethunder.
Lightning
measures
Thereisnotthecompletecountermeasureforitbutthefollowingmethodcanbeconsidered.
Makethesuitabletreatmentaccordingly.
a) Thetransmissionsignalrouteisarrangedforconnectionbytheopticalfibercableetc.
b) Countermeasurebythelightingarrester(Cablesafetyretainer).Thereisthewaytoinstall
the lightning arrester just before the field apparatus and the central control station. The
positionofthelightningarresterinstallationisateachpointofcablelaidoutfromtheoutdoor
totheindoor.Thelightningarresterbuildsinthecircuittoremovethesurgevoltagetobethe
sourceforthedamageoffieldapparatus(Protectionresistor,zerodiodeetc.)andisdesigned
toprotecttheapparatus.Butasthesignalmaybeattenuatedduetothelightningarrester,
checktheactionanditisrequiredtouse.
Grounding Surgenoiseshallbegeneratedfromthethunderlightningorexceptit.
Toprotectdetectorfromthesecause,besuretomakegrounding.
*Inthelightningrod,thereisthecircuittoremovethesurgevoltagetobeacauseofdamagefromfieldinstruments.
Byinstallingthelightningrod,thesignalmaybeattenuated. Wheninstallthelightningrod,itisrequiredtocheck
theperformanceinadvance.
CAUTION