Rishabh Rish Master 3444i User manual

RISH Master 3440i/3440iDL 0.2S
RISH Master 3440i/3440iDL 0.2S
Operating Manual
as per IEC62053-22


Section
Touch Screen Digital Multi-Function Meter
Installation & Operating Instructions
Contents
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.2 Menu selection
3.2.1 System Parameter selection screen
3.2.1.1 System type
3.2.1.2 Potential transformer Primary value
3.2.1.3 Potential transformer secondary value
3.2.1.4 Current transformer Primary value
3.2.1.5 Current transformer Secondary value
3.2.1.7 Demand integration time
3.2.1.8 Auto Scrolling
3.2.1.9 Low current noise cutoff
3.2.1.11 Energy resolution
3.2.1.12 Energy digit reset count
3.1.1 Change Password
INDEX
DMAN-00IM-0683_Rev.C 08/2018
3.2.1.13 Energy Update Rate
3.2.1.6 System Frequency
3.2.1.10 Number of Poles
3.2.1.14 Meter Version
1

3.2.4.1 Relay 1 output selection menu
3.2.4.1.1 Pulse output
3.2.4.1.1.1 Assignment of Energy to Pulse (Relay 1)
3.2.4.1.1.2 Pulse Duration Selection
3.2.4.1.1.3 Pulse Rate
3.2.4.1.2 Limit output
3.2.4.1.2.1 Assignment of Limit Output1 to Parameter
3.2.4.1.2.5 Limit Conguration
3.2.4.1.2.6 Trip point selection
3.2.4.1.2.7 Hysteresis selection
3.2.4.1.2.8 Energizing delay time
3.2.4.1.2.9 De-energizing delay time
3.2.4 Output Option selection screen (menu)
3.2.3.1 Resetting Parameter
3.2.3 Reset Parameter selection screen
3.2.2 Communication Parameter selection screen
3.2.2.1.1 Address Setting
3.2.2.1.2 RS 485 Baud rate
3.2.2.1.3 RS 485 Parity selection
3.2.2.1 Modbus Setting
3.2.2.2 Ethernet Setting
3.2.2.2.1 IP Address Setting
3.2.2.2.2 Subnet Mask Setting
3.2.2.2.3 Default Gateway Setting
3.2.2.2.4 Server Port Setting
3.2.4.1.2.2 Energy Count Conguration
3.2.4.1.2.3 Energy Trip point
3.2.4.1.2.4 Energy Count On Delay
2

3.2.4.2 Relay 2 output selection menu
3.2.4.3 Parameter setting for Analog Output-1
3.2.4.4 Parameter setting for Analog Output-2
3.2.8 Brightness & Contrast
3.2.4.1.4 RTC Relay
3.2.4.1.4.1 Weekdays Selection
3.2.4.1.4.2 Timer Conguration
3.2.4.1.4.3 On Time
3.2.4.1.4.4 Off Time
3.2.5.1 Event Based Datalog
3.2.5.2.1 Status
3.2.5 Datalogging Option Selection
3.2.5.2 Time Based Datalog
3.2.5.3 Load Prole Datalog
3.2.5.2.2 Time Interval
3.2.5.2.3 Parameters
3.2.6.1 Sag Threshold
3.2.6 Power Quality Settings
3.2.6.2 Swell Threshold
3.2.6.3 Sag & Swell Hysteresis
3.2.6.4 Overcurrent Threshold
3.2.6.5 Overcurrent Hysteresis
3.2.7 Date & Time Settings
3.2.4.1.3 Timer
3.2.4.1.3.1 Number of Cycles
3.2.4.1.3.2 Timer Conguration
3.2.4.1.3.3 On Delay
3.2.4.1.3.4 Off Delay
3

13. Specication
11. Installation
11.1 EMC Installation Requirements
11.2 Case Dimensions and Panel Cut-out
11.3 Wiring
11.4 Auxiliary Supply
11.5 Fusing
11.6 Earth / Ground Connections
12. Connection Diagrams
14. Connection for Optional Pulse output / RS 485 /Analog Output / Ethernet
10. Phasor Diagram
Relay Output
9.
Pulse output
9.1
Limit switch
9.2
7. Analog Output
6.3 Number of Interruption
6.2 On - Hour.
6.1 Run - Hour.
5. Phase Rotation Error screen.
4. Touch screen calibration.
6. Run Hr, On Hr & No. of Interruptions
Timer Output
9.3
PQ Measurement
8
3.2.9 RGB Color Code
3.2.10 Factory Reset
4

1. Introduction
This instrument is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the
measurement of important electrical parameters like AC voltage, AC Current, Frequency,
Power, Energy(Active / Reactive / Apparent) . The instrument integrates accurate measurement
of technology (All Voltage & Current measurements are True RMS upto 15th Harmonic) with
320x240 Pixels touch screen TFT LCD display.
This instrument can be congured and programmed at site for the following: PT Primary, PT
Secondary, CT Primary, CT Secondary (5A or1A) and 3 phase 3W or 3 Phase 4W system.
The front panel has a 3.5” Touch Screen through which the user can move across the available
measurement readings, reset the energy, Min/Max (System Voltage and System Current) and
congure the product settings.
Main menu is divided into 6 submenus. Each submenu contains a list
of options. By touching the icons on main menu, submenus can be
accessed. System submenu can be used to access RTC, harmonics,
Power Quality events and other system parameters like system
power, min, max voltage and current, THD, run hour, on hour and
number of interruptions. Voltage, current and power submenu contain
measurement of basic elecrical parameters. Energy submenu gives
the total energy and Setup submenu can be used for complete meter
settings.
5

TABLE 1:Measurement Parameters for both models
System Voltage
System Current
Frequency
Voltage VL1-N(4wire only)
Voltage VL2-N(4wire only)
Voltage VL3-N(4wire only)
Voltage VL1-L2
Voltage VL2-L3
Voltage VL3-L1
Current L1
Current L2
Current L3
Volts
Amps
Hz
Volts
Volts
Volts
Volts
Volts
Volts
Amps
Amps
Neutral Current ( 4 wire only )
Amps
Amps
Active Import Energy (8 Digit resolution) kWh
kWh
Active Export Energy (8 Digit resolution)
Active Power (System / Phase (4 wire only) )
Reactive Power (System / Phase (4 wire only))
Apparent Power (System / Phase (4 wire only))
Power Factor (System / Phase (4 wire only))
Phase Angle ( Phase(4 wire only))
Kwatts
KVAr
KVA
Degree
kVArh
Inductive Reactive Energy (8 Digit resolution)
kVArh
Capacitive Reactive Energy (8 Digit resolution)
kVAh
Apparent Energy (8 Digit resolution)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
Units of
Measurement
Date,Time
RTC
%
Individual Harmonics V
Individual Harmonics I %
RM3440i RM3440iDL
Sag, Swell & Overcurrent Events -
Measured Parameters
6

*Note : THD Parameters are L-N in case of 3P 4W & L-L in case of 3P 3W .
KW Import Demand
KVAr Cap. Demand
KW Export Demand
KVAr Ind. Demand
Max Current Demand
Max kVA Demand
Max KW Import Demand
Max KW Export Demand
Max KVAr Ind. Demand
Max KVAr Cap. Demand
Run Hour
On Hour
Number of Interruptions
Phase Reversal Indication ( 4 wire only )
KW
KW
Amps
KVA
KW
KW
KW
KW
KW
KW
Hours
Hours
Counts
Amps
Current Demand
KVA Demand KVA
I1 THD
I2 THD
V1 THD*
V2 THD*
V3 THD*
%
I3 THD
System Voltage THD
System Current THD
%
%
%
%
%
%
%
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
count,sec,sec
Timer1 No. of Cycles, ON, OFF delay
Timer2 No. of Cycles, ON, OFF delay
Measured Parameters Units of
Measurement
count,sec,sec
TABLE 1:Continued...
RM3440i RM3440iDL
7

2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading screens out of
several screens. These screens from particular submenu may be scrolled through one at a time
in incremental order by touching the “ key” and in decremental order by touching “ key”
on that screen.
APPARENT
ENERGY
REACTIVE ENERGY
INDUCTIVE
REACTIVE ENERGY
CAPACITIVE
ACTIVE ENERGY
EXPORT
ACTIVE ENERGY
IMPORT
RESET
PARAMETERS
COMMUNICATION
MAIN MENU
SYSTEM
SYSTEM TYPE
PT PRIMARY
PT SECONDARY
CT SECONDARY
DEMAND
NOISE CUTOFF
AUTO SCROLL
(Sec 3.2.1.1)
(Sec 3.2.1.2)
(Sec 3.2.1.3)
(Sec 3.2.1.5)
(Sec 3.2.1.7)
INTEGRATION
TIME
LOW CURR.
CURRENT
VOLTAGE
SYSTEM
Max. VOLTAGE
PHASOR
RUN HOUR
A
A
SYSTEM
PARAMETERS
And CURRENT
Min. VOLTAGE
And CURRENT
ON HOUR
No. OF
INTERRUPTIONS
CT SECONDARY
DEMAND
AUTO SCROLL
(Sec 3.2.1.5)
(Sec 3.2.1.7)
INTEGRATION
TIME
POWER
SYSTEM
POWER
SYSTEM
RTC
(Sec 3.2.2.3)
PHASE VOLTAGE
% THD
Line Current
OPTIONS
(Sec 3.2.4)
POWER
CHANGE
PASSWORD
(Sec 3.1)
ENERGY
AA
A
B
A
B
LINE CURRENT
% THD
DIAGRAM
Line to Neutral
VOLTAGE
(Sec 3.2.2.3)
WAVEFORM
WAVEFORM
CURRENT
PHASE
WAVEFORM
EXPORT
ACTIVE DEMAND
IMPORT
ACTIVE DEMAND
APPARENT
DEMAND
CURRENT
DEMAND
PHASE
POWER FACTOR
PHASE ACTIVE
POWER
PHASE APPARENT
POWER
PHASE REACTIVE
POWER
PHASE
ANGLE
Parameter Screens Single Phase
SYSTEM
RPM
FREQUENCY
FACTOR
THD.VOLTAGE
AND CURRENT
DEMAND
AUTO SCROLL
(Sec 3.2.1.7)
TIME
TIMER 1
POWER QUALITY
EVENTS
INDIVIDUAL
HARMONICS
TIMER 2
TIMER
STATUS
NOTE: SCREENS MARKED WITH # ARE AVAILABLE ONLY IN RM3440iDL
#
#
#
#
#
8

APPARENT
ENERGY
REACTIVE ENERGY
INDUCTIVE
REACTIVE ENERGY
CAPACITIVE
ACTIVE ENERGY
EXPORT
ACTIVE ENERGY
IMPORT
RESET
PARAMETERS
COMMUNICATION
MAIN MENU
SYSTEM
SYSTEM TYPE
PT PRIMARY
PT SECONDARY
CT PRIMARY
CT SECONDARY
DEMAND
NOISE CUTOFF
AUTO SCROLL
(Sec 3.2.1.1)
(Sec 3.2.1.2)
(Sec 3.2.1.3)
(Sec 3.2.1.4)
(Sec 3.2.1.5)
(Sec 3.2.1.7)
INTEGRATION
TIME
LOW CURR.
CURRENT
VOLTAGE
SYSTEM
Max. VOLTAGE
PHASER
RUN HOUR
A
A
RPM
SYSTEM
PARAMETERS
And CURRENT
Min. VOLTAGE
And CURRENT
ON HOUR
No. OF
INTERRUPTIONS
DEMAND
AUTO SCROLL
(Sec 3.2.1.7)
INTEGRATION
TIME
SEQUENCE *
PHASE
INDIVIDUAL
HARMONICS
SYSTEM
RTC
(Sec 3.2.2.3)
VOLTAGE
% THD
Line Current
Neutral
OPTIONS
(Sec 3.2.4)
POWER
CHANGE
PASSWORD
(Sec 3.1)
ENERGY
A
A
B
B
LINE CURRENT
% THD
DIAGRAM *
Line to Line
VOLTAGE
Line to Neutral
VOLTAGE*
NOTE 1: SCREENS MARKED WITH * ARE AVAILABLE ONLY IN 4W SYSTEM (NOT IN 3 WIRE SYSTEM)
(Sec 3.2.2.3)
WAVEFORM
VOLTAGE
WAVEFORM
CURRENT
L3 PHASE
WAVEFORM *
L2 PHASE
WAVEFORM *
L1 PHASE
WAVEFORM *
EXPORT
ACTIVE DEMAND
IMPORT
ACTIVE DEMAND
APPARENT
DEMAND
CURRENT
DEMAND
PHASE
POWER FACTOR*
L3 PHASE
POWER *
L2 PHASE
POWER *
L1 PHASE
POWER *
PHASE
ANGLE*
Parameter Screens 3 Phase
NOISE CUTOFF
LOW CURR.
FREQUENCY
SYSTEM
CT SECONDARY
DEMAND
(Sec 3.2.1.5)
INTEGRATION
TIME
POWER FACTOR
THD.VOLTAGE
AND CURRENT
CT SECONDARY
(Sec 3.2.1.5)
POWER
SYSTEM
DEMAND
AUTO SCROLL
(Sec 3.2.1.7)
INTEGRATION
TIME
TIMER 2
POWER QUALITY
EVENTS
TIMER
STATUS
TIMER 1
Current*
A
NOTE 2: SCREENS MARKED WITH # ARE AVAILABLE ONLY IN RM3440iDL
#
#
#
#
#
9

MODBUS
(Sec 3.2.2.1)
ANALOG OUTPUT 1
(Sec 3.2.4.3)
PT PRIMARY
(Sec 3.2.1.2)
PT SECONDARY
(Sec 3.2.1.3)
CT PRIMARY
(Sec 3.2.1.4)
CT SECONDARY
(Sec 3.2.1.5)
AUTO SCROLL
(Sec 3.2.1.8)
NOISE CUTOFF
(Sec 3.2.1.9)
LOW CURR.
(Acc. To Table 7.1)
DEMAND
(Sec 3.2.1.7)
INTEGRATION
TIME
RESET MAX V & I
RESET MIN V & I
RESET RUN,ON-HR
RESET AUX INTRR.
RESET ALL
PASSWORD
SYSTEM
(Sec 3.2.1)
Setup Parameter Screens
PARAMETERS
ENTER
SYSTEM
(Sec 3.2.1)
PARAMETERS
PARAMETERS
COMMUNICATION
(Sec 3.2.2)
PARAMETERS
(Sec 3.1)
SYSTEM TYPE
(Sec 3.2.1.1)
BRIGHTNESS
& CONTRAST
(Sec 3.2.8)
CHANGE
PASSWORD
(Sec 3.1.1)
RESET
(Sec 3.2.3)
PARAMETERS
OPTIONS
OUTPUT
(Sec 3.2.4)
(Sec 3.2.4.1)
RELAY
OUTPUT 1
RESET DEMAND
RESET ENERGIES
RS485
(Sec 3.2.1.11)
ENERGY ON
RESET COUNT
(Sec 3.2.1.12)
ENERGY DIGIT
RGB
COLOR
CODE
(Sec 3.2.9)
(Sec 3.2.4.2)
RELAY
OUTPUT 2
ANALOG OUTPUT 2
(Sec 3.2.4.4)
(Acc. To Table 7.1)
A
C
POWER QUALITY
SETTINGS
(Sec 3.2.6)
DATALOG
OPTIONS
(Sec 3.2.5)
EVENT BASED
(Sec 3.2.5.1)
TIME BASED
(Sec 3.2.5.2)
LOAD PROFILE
(Sec 3.2.5.3)
SAG
(Sec 3.2.6.1)
THRESHOLD
SWELL
(Sec 3.2.6.2)
THRESHOLD
OVERCURRENT
(Sec 3.2.6.3)
HYSTERESIS
SAG & SWELL
(Sec 3.2.6.4)
THRESHOLD
(Sec 3.2.6.5)
OVERCURRENT
HYSTERESIS
DATE &
TIME
(Sec 3.2.7)
PARAMETERS
ETHERNET
(Sec 3.2.2.2)
PARAMETERS
A
A
B
FREQUENCY
(Sec 3.2.1.6)
SYSTEM
RATE
(Sec 3.2.1.13)
ENERGY UPDATE
VERSION
(Sec 3.2.1.14)
METER
POLES
(Sec 3.2.1.10)
NUMBER OF
RESET TIME LOG
RESET LP LOG
RESET SAG LOG
A
D
FACTORY
RESET
(Sec 3.2.10)
*NOTE: ETHERNET Parameters (Sec 3.2.2.2) are available only if Ethernet card (add on) is inserted.
RESET SWELL LOG
RESET OvI LOG
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
#
*NOTE: ETHERNET Parameters marked # are available only for RM3440iDL
10

(Acc. To Table 2)
(Sec 3.2.4.1.2.1)
PARAMETER
SELECTION
CONFIGURATION
SELECTION (Hi-E
(Sec 3.2.4.1.2.5)
TRIP POINT
10% to 100%/120%
(Sec 3.2.4.1.2.6)
HYSTERESIS
0.5% to 50%
(Sec 3.2.4.1.2.7)
ENERGIZING
DELAY 1s to 10s
(Sec 3.2.4.1.2.8)
1 s to 10s
(Sec 3.2.4.1.2.9)
DE-ENERGIZING
DELAY
(Sec 3.2.4.1.1)
LIMIT
OUTPUT
(Sec 3.2.4.1.2)
PARAMETER
SELECTION
(Sec 3.2.4.1.1.1)
PULSE RATE
(Pulse Divisor Rate)
1, 10, 100, 1000
PULSE RATE
R
(Sec 3.2.4.1.1.3)
PULSE
DURATION
60,100,200
(Sec 3.2.4.1.1.2)
PULSE
OUTPUT
Output Options Parameters
If
PARAMETER
=37/38/39/40/41
Hi-DE,Lo-En,Lo-DE)
CONFIGURATION
SELECTION
(Sec 3.2.4.1.2.2)
TRIP POINT
10 to 9999999
(Sec 3.2.4.1.2.3)
ON DELAY
1 to 9999 s
(Sec 3.2.4.1.2.4)
(En,De-En)
(Sec 3.2.4.1.3)
RTC
OUTPUT
(Sec 3.2.4.1.4)
TIMER
OUTPUT
CONFIGURATION
SELECTION
(Sec 3.2.4.1.3.2)
ON DELAY
(Sec 3.2.4.1.3.3)
OFF DELAY
1 to 9999 s
(Sec 3.2.4.1.3.4)
(En,De-En)
(Sec 3.2.4.1.3.1)
NO OF CYCLES
(0 TO 9999)
1 to 9999 s
CONFIGURATION
SELECTION
(Sec 3.2.4.1.4.2)
ON TIME
(Sec 3.2.4.1.4.3)
(Sec 3.2.4.1.4.4)
(En,De-En)
(Sec 3.2.4.1.4.1)
WEEKDAYS
00:00 to 23:59
SELECTION
OFF TIME
00:00 to 23:59
A
C
Rs485 ADDRESS
(Sec 3.2.2.1.1)
RS485 PARITY
(Sec 3.2.2.1.3)
RS485
BAUD RATE
RS485
(Sec 3.2.2.1.2)
BAUD RATE
IP ADDRESS
(Sec 3.2.2.2.1)
DEFAULT
(Sec 3.2.2.2.3)
SUBNET MASK
(Sec 3.2.2.2.2)
SERVER PORT
(Sec 3.2.2.2.4)
B
AA
B
GATEWAY
Modbus
Parameters
Ethernet
Parameters
ON/OFF STATUS
(Sec 3.2.5.2.1)
PARAMETERS
(Sec 3.2.5.2.3)
TIME
(Sec 3.2.5.2.2)
INTERVAL
B
D
Time Datalog
Parameters
#
#
#
#
##
#
#
#
#
#
#
#
Yes
No
#
#
#
#
*NOTE: ETHERNET Parameters marked # are available only for RM3440iDL.
11

3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-up screens, by
default password is “0000”.
Password protection is enabled by selecting any four digit number.
3. Programming
The following sections comprise step by step procedures for conguring the instrument for
individual user requirements. To access the set-up screens touch on the “ SETUP ” icon in
Main Menu. This will take the User into the Password Protection Entry Stage(Section 3.1).
After touching “ SETUP” icon Password protection screen is
displayed. Screen consists of 0 to 9 digit input keypad for entering the
password very similar to any calculator in touchscreen mobile.“Enter
Password” is displayed on screen at start so that user can enter
password using displayed keypad.
Touching “ key” will display 1 in display area, similarly user can
enter remaining 3 digits.
For deleting any digit while entering password, user can touch “ key”.
After entering the complete password user needs to conrm password by touching “ key’’.
DEL
ENTER
ENTER
1
If Entered password is correct then “Password Accepted” is displayed on screen & user will on
screen & user will enter into setup menu.
Password conrmed.
If Entered password is wrong then “Password Rejected” is displayed on screen & user need to
re-enter the password After wrong password is entered, user needs to touch “ key ” for
trying another password.
Password Incorrect.
12

Change Password Option is the second last option in list of “SETUP”
submenu, so can be accessed by a simple touch on “ Change
Password” button.
In this screen user rst needs to enter the current password.
3.1.1 Change Password
After input of correct password,“PASSWORD ACCEPTED”is
displayed & now user can enter the new 4 digit password.
After entering new password user needs to touch “ key” to
conrm.
After conrming “PASSWORD CHANGED” is displayed on screen,
which ensures successful changing of the password.
New Password conrmed.
3.2 Menu selection.
After entering in the SUBMENU 6 - SETUP, user will be asked to enter password & after
input of correct password list of following parameters will be displayed on screen :-
ENTER
13

Touching on SYSTEM PARAMETER will open the system parameters list screen.Then these
screens from particular parameter may be scrolled through one at a time in incremental order
by touching the “ key” and in decremental order by touching “ key” on given touch
screen.
3.2.1 System Parameters Selection
After entering in the “SYSTEM PARAMETERS”, List of following parameters will be displayed :-
3.2.1.1 SYSTEM TYPE
3.2.1.2 PT PRIMARY
3.2.1.3 PT SECONDARY
3.2.1.4 CT PRIMARY
3.2.1.5 CT SECONDARY
3.2.1.7 DEMAND INTEGRATION TIME
3.2.1.8 AUTO SCROLL
3.2.1.9 LOW CURRENT NOISE CUTOFF
3.2.3 RESET PARAMETERS
3.2.4 OUTPUT OPTIONS
3.2.1.11 ENERGY RESOLUTION
3.2.1.12 ENERGY DIGIT RESET COUNT
3.2.5 DATALOGGING OPTIONS
3.2.6 POWER QUALITY SETTINGS
3.2.7 DATE & TIME SETTINGS
3.2.10 FACTORY RESET
3.2.8 BRIGHTNESS & CONTRAST
3.2.9 RGB COLOR CODE
3.2.1.6 SYSTEM FREQUENCY
3.2.1.10 NUMBER OF POLES
3.2.1.13 ENERGY UPDATE RATE
3.2.1.14 METER VERSION
3.2.1 SYSTEM PARAMETERS
3.2.2 COMMUNICATION PARAMETERS
14

3.2.1.2 Potential Transformer Primary Value
The nominal full scale voltage will be displayed as Line to Line Voltages for 3 Phase 3 wire and
3 Phase 4 wire and 1 Phase 2 wire for Single Phase.
This screen can be accessed only from system parameters list menu.
Here again 0 to 9 digit input keypad is provided to set value of PT
Primary, & user can conrm this value with a simple touch “ key”.
“ key” is used to multiply value by 1000.
In case presently displayed Potential Transformer Primary value
together with the Current Transformer Primary value, previously set,
would result in a maximum power of greater than 666.6 MVA per
phase,”Invalid value” will be displayed. Then the valid range will be
displayed.
Valid range of PT primary setting value is
100V L-L to 692.8KV L-L.
If value outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter.
Note : Changing PT Primary would erase the Sag and Swell data of
PQ events.
3.2.1.1 System Type
This screen is used to set the system type.
Two types: 3 phase 3 wire & 3 phase 4 wire system are displayed on
screen (for RM3440i). Touching radio button in front of particular type
will select that type.
Touch on “ key” will conrm the system type.
Touching the “ key” will keep the old selected setting and will
return to previous menu.
Note : If system type is changed, relay parameter selection & analog output selection will be set
to NONE and all the PQ event data (sag/ swell/ overcurrent) would be erased.
SYSTEM TYPE
3-PHASE 4 WIRE
FOR 3 PHASE STAR CONNECTED LOAD
3-PHASE 3 WIRE
FOR 3 PHASE DELTA CONNECTED LOAD
OK BACK
OK
BACK
VALID RANGE IS : 100.0 TO 692800
K
ENTER
15

INVALID VALUE
PT SECONDARY
The Valid range of instrument is from 100 to 600V.
If value outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter.
Note : Changing PT Secondary would erase the Sag and Swell data
of PQ events.
3.2.1.3 Potential Transformer secondary Value
The value must be set to the nominal full scale secondary voltage which will be obtained from
the the Transformer when the potential transformer(PT)primary is supplied with the voltage
dened in 3.2.1.2 potential transformer primary voltage. The ratio of full scale primary to full
scale secondary is dened as the transformer ratio.
This screen can be accessed only from system parameters list menu. Here again 0 to 9 digit
input keypad is provided to set value of PT Secondary, & user can conrm this value with a
simple touch on “ key”.
ENTER
3.2.1.4 Current Transformer Primary Value
The nominal Full Scale Current that will be displayed as the Line currents. This screen enables
the user to display the Line currents inclusive of any transformer ratios, the values displayed
representthe Current in Amps.
This screen can be accessed only from system parameters list menu.
Here again 0 to 9 digit input keypad is provided to set value of CT
Primary & user can conrm this value with a simple touch on “ key”
and “ key” is used to multiply value by 1000. In case presently
displayed Current Transformer Primary Value together with the
Potential Transformer Primary Value results in a maximum power of
greater than 666.6 MVA, “invalid value” will be displayed. Example: If
primary value of PT is set as 692.8kV L-L (max value) then primary
value of Current is restricted to 1157A.
ENTER CT PRIMARY VALUE
ENTER
K
CT PRIMARY
16

3.2.1.5 Current Transformer Secondary Value
This screen is used to set the secondary value for Current
Transformer. Two options: 1 AMPERE & 5 AMPERE are displayed on
screen. Touching radio button in front of particular option will select
that option.
Touch on “ key” will conrm the setting. Touching the “
key” will keep the old selected setting and will return to previous
menu.
Note : Changing CT Secondary would erase the Overcurrent data of
PQ events.
OK
OK BACK
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
CT SECONDARY
1 AMPERE
5 AMPERE
OK BACK
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and 120% of
nominal voltage, i.e, 462.96 MVA nominal power per phase.
Valid range of CT primary setting value is from 1 to 9999. If value
outside the range is entered, It will display “INVALID VALUE” followed
by correct range of parameter.
Note : Changing CT Primary would erase the Overcurrent data of PQ
events.
INVALID VALUE
3.2.1.6 System Frequency
OK
OK
BACK
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
CT SECONDARY
1 AMPERE
5 AMPERE
OK BACK
This screen is used to set the frequency of the input.
Two options : 50 & 60 Hz are displayed on screen.
Touching radio button in front of particular option will select that
option.
Touch on “ key” will confirm the setting. Touching the
“ key” will keep the old selected setting and will return to
previous screen.
CT PRIMARY
17

LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2 VV
V
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2 VV
V
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2 VV
V
V
0.000
0.000
CT SECONDARY
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2 VV
V
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2 VV
V
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2 VV
V
V
0.000
0.000
AUTO - SCROLL
ALL
VOLTAGE
POWER
NONE
SYSTEM
CURRENT
ENERGY
OK BACK
3.2.1.7 Demand Integration Time
This screen is used to set the period over which current and power
readings are to be integrated.
Four options: 8, 15, 20, 30 Minutes are displayed on screen.
Touching radio button in front of particular option will select that
option.
Touch on “ key” will conrm the setting.
Touching the “ key” will keep the old selected setting and will
return to previous menu.
OK
OK
OK
OK
OK
BACK
BACK
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2 0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2 0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2 0.000
0.000
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2 0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2 0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2 0.000
0.000
DEMAND INTEGRATION TIME
8 MINUTES
15 MINUTES
20 MINUTES
30 MINUTES
MAINMAINMAINMAINMAINMAIN
OK BACK
3.2.1.8 Auto Scrolling
This screen allows user to enable screen scrolling. Seven options :
ALL, SYSTEM, VOLTAGE, CURRENT, POWER, ENERGY & NONE
are displayed on screen. Touching radio button in front of particular
option will select that option. Selecting particular option means, only
screens which are under that submenu will be scrolled automatically.
Selecting NONE will disable Auto-Scroll.
Touch on “ key” will conrm the setting.
Touching the “ key” will keep the old selected setting and will return to previous menu.
While in Auto-scrolling mode, touch sense for entire screen will be disabled except for the top
right most corner where “A” symbol would be displayed stating that meter is in Auto-scroll mode.
Touching on “A” will show two options “ON” and “OFF”. Touching on “ON” will continue auto
scrolling & touching on “OFF” will stop auto-scrolling & return to normal mode.
18
This manual suits for next models
1
Table of contents