Rittal SK 3212.xxx User manual

Montageanleitung
Assembly instructions
Notice de montage
Montage-instructie
Montageanvisning
Istruzioni di montaggio
Instrucciones de montaje
R
Wärmetauscher
heat exchanger
thermique air/eau
warmtewisselaars
värmeväxlare
aria/acqua
de calor aire/agua
SK 3247.000
Rittal
SK
Luft/Wasser-
Air/water
Echangeur
Lucht/water-
Luft/vatten
Scambiatore di calore
Intercambiador
SK 3212.xxx
SK 3214.100
SK 3215.100
SK 3216.xxx
SK 3217.100
SK 3218.100
SK 3218.104
SK 3219.100
SK 3249.100
SK 3249.104
Kühltechnik
Umweltorientierte

80
500
200
1
/2w
18
75
100
➁
➀
420
200
500
150
Ø 7
420
500
170 50
30
133
150
150
160
200
130
145
160
34
4 x
80
200
950
100
20
77
➁➀
200
(4 x)
140
11
920
175
170 15
475
315 22
126
98
19 920
950
164
140
Ø 7 (6 x)
Befestigungsbohrungen Einbau
Fastening holes for internal mounting
Perçages pour montage encastré
Bevestigingsgaten voor inbouw
Montagehålbild, inbyggnad
Fori di fissaggio per installazione incassata
Taladros de fijación para montaje interior
取付穴 全埋め込み取付け
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付け
SK 3214.100
2
SK 3215.100
➀Kondensatablauf
➀Condensate discharge
➀Ecoulement d’eau de condensation
➀Condensafvoer
➀Kondensavlopp
➀Dispositivo di scarico condensa
➀Salida del agua de codensación
➀凝縮水排出器
➁Kühlwasser-Anschluß 1/2˝
➁Cooling water connection 1/2˝
➁ Branchement eau de refroidissement 1/2˝
➁ Aansluiten koelwater 1/2˝
➁ Kylvattenanslutning 1/2˝
➁ Allacciamento liquido frigorigeno 1/2˝
➁ Acometida de 1/2˝ del agua de refrigeración
➁給水部 1/2 インチ
Ø 7
Ø 7

3
3
250
100
450
1400
80
➁
➀
450
350
410
15
33.5
440
711.5
180
455 455
1400
455
433.5
Ø 8
420
SK 3216.100
➀Kondensatablauf
➀Condensate discharge
➀Ecoulement d’eau de condensation
➀Condensafvoer
➀Kondensavlopp
➀Dispositivo di scarico condensa
➀Salida del agua de codensación
➀凝縮水排出器
➁Kühlwasser-Anschluß 1/2˝
➁Cooling water connection 1/2˝
➁ Branchement eau de refroidissement 1/2˝
➁ Aansluiten koelwater 1/2˝
➁ Kylvattenanslutning 1/2˝
➁ Allacciamento liquido frigorigeno 1/2˝
➁ Acometida de 1/2˝ del agua de refrigeración
➁給水部 1/2 インチ
Befestigungsbohrungen Einbau
Fastening holes for internal mounting
Perçages pour montage encastré
Bevestigingsgaten voor inbouw
Montagehålbild, inbyggnad
Fori di fissaggio per installazione incassata
Taladros de fijación para montaje interior
取付穴 全埋め込み取付け
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付け

4
36
17
600
400
103.5
400
35
73
1
Montageausschnitt Dachaufbau
Mounting cut-out for roof mounting
Découpe pour montage sur toit
Montage-uitsparingen voor dakopbouw
Hål för takmontage
Feritoia per struttura tetto
Escotadura de montaje para montaje en el techo
取付用カットアウト ルーフ型
Ø 230
238.5
138.5
258
42
493
(591)
69.5
150.5
391
280
436 115
Ø 8 (4 x)
SK 3219.100
Wasser-Anschluß und Kondensatablauf 1/2˝
Water connection and condensate discharge 1/2˝
Branchement d’eau et écoulement de condensat 1/2˝
Aansluiten water- en condensafvoer1/2˝
Vattenanslutning och kondensavlopp 1/2˝
Allacciamento idrico e scarico condensa 1/2˝
Acometida del agua y salida del agua de condensación 1/2˝
給水部および凝縮水排出器 1/2 インチ
/2w

5
300 451
310
310
310
30
1800
300
11
SK 3216.480 451
Ø 8 (10 x)
433.5
350
417
442.5
230
145
442.5 442.5 442.5
530
30
15
417
350
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付け
/2w
/2w

6
300
150
60
➁
➀
85
18
55
300
276
102
150
Ø 7 (4 x)
300
276
232
41
150
125
102
Ø 7 (4 x)
Befestigungsbohrungen Einbau
Fastening holes for internal mounting
Perçages pour montage encastré
Bevestigingsgaten voor inbouw
Montagehålbild, inbyggnad
Fori di fissaggio per installazione incassata
Taladros de fijación para montaje interior
取付穴 全埋め込み取付け
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付け
SK 3212.xxx
➀Kondensatablauf
➀Condensate discharge
➀Ecoulement d’eau de condensation
➀Condensafvoer
➀Kondensavlopp
➀Dispositivo di scarico condensa
➀Salida del agua de codensación
➀凝縮水排出器
➁Kühlwasser-Anschluß 3/8˝
➁Cooling water connection 3/8˝
➁ Branchement eau de refroidissement 3/8˝
➁ Aansluiten koelwater 3/8˝
➁ Kylvattenanslutning 3/8˝
➁ Allacciamento liquido frigorigeno 3/8˝
➁ Acometida de 3/8˝ del agua de refrigeración
➁給水部 3/8 インチ

7
520
298
272
240
475
230
120
127 33
208
Ø 7
298
240
475
520
Ø 7
298
520
50
135
93
➁
➀
SK 3217.100
➀Kondensatablauf
➀Condensate discharge
➀Ecoulement d’eau de condensation
➀Condensafvoer
➀Kondensavlopp
➀Dispositivo di scarico condensa
➀Salida del agua de codensación
➀凝縮水排出器
➁Kühlwasser-Anschluß 1/2˝
➁Cooling water connection 1/2˝
➁ Branchement eau de refroidissement 1/2˝
➁ Aansluiten koelwater 1/2˝
➁ Kylvattenanslutning 1/2˝
➁ Allacciamento liquido frigorigeno 1/2˝
➁ Acometida de 1/2˝ del agua de refrigeración
➁給水部 1/2 インチ
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付け
Befestigungsbohrungen Einbau
Fastening holes for internal mounting
Perçages pour montage encastré
Bevestigingsgaten voor inbouw
Montagehålbild, inbyggnad
Fori di fissaggio per installazione incassata
Taladros de fijación para montaje interior
取付穴 全埋め込み取付け

8
400
950
904
340
340
60
280
463
112
280
Ø 7
400
950
280
904
Ø7
400
950
200
➁
➀
SK 3218.xxx
➀Kondensatablauf
➀Condensate discharge
➀Ecoulement d’eau de condensation
➀Condensafvoer
➀Kondensavlopp
➀Dispositivo di scarico condensa
➀Salida del agua de codensación
➀凝縮水排出器
➁Kühlwasser-Anschluß 1/2˝
➁Cooling water connection 1/2˝
➁ Branchement eau de refroidissement 1/2˝
➁ Aansluiten koelwater 1/2˝
➁ Kylvattenanslutning 1/2˝
➁ Allacciamento liquido frigorigeno 1/2˝
➁ Acometida de 1/2˝ del agua de refrigeración
➁給水部 1/2 インチ
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付け
Befestigungsbohrungen Einbau
Fastening holes for internal mounting
Perçages pour montage encastré
Bevestigingsgaten voor inbouw
Montagehålbild, inbyggnad
Fori di fissaggio per installazione incassata
Taladros de fijación para montaje interior
取付穴 全埋め込み取付け

9
300
128 85 470
230
320
40
75
750
825
25
40
380
Ø8
350
380
Ø8
825
765
45
85
380
Ø13
825
➁
➀
1
/2″
105
SK 3247.000
➁Wassereintritt
➁Water inlet
➁Arrivée d’eau
➁Waterintrede
➁Vatteningång
➁Entrata acqua
➁Entrada del agua
➁吸水口
➀Wasseraustritt
➀Water outlet
➀Départ d’eau
➀Wateruittrede
➀Vattenutgång
➀Uscita acqua
➀Salida del agua
➀放水口
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付け
Befestigungsbohrungen Einbau
Fastening holes for internal mounting
Perçages pour montage encastré
Bevestigingsgaten voor inbouw
Montagehålbild, inbyggnad
Fori di fissaggio per installazione incassata
Taladros de fijación para montaje interior
取付穴 全埋め込み取付け

10
Ø8(4x)
53
264
280
397
95 310 87
23 23
400
210
226
(538)
➀
280
547
404
SK 3249. xxx
➀Luftaustritt
➀Air outlet
➀Départ d’air
➀Inblaaslucht
➀Luftutlopp
➀Uscita aria
➀Salida del aire
➀空気吹出口
Montageausbruch Anbau
Mounting cut-out for external mounting
Découpe pour montage en saillie
Montage-uitsparingen, aanbouw
Montagehålbild, påbyggnad
Feritoia per installazione sporgente
Escotadura de montaje para montaje exterior
取付用カットアウト 表面取付けAnbau

11
Tab. 2.1 Technische Daten
Tab. 2.1 Technical data
Tab. 2.1 Données techniques
Tab. 2.1 Technische gegevens
Tab. 2.1 Tekniska data
Tab. 2.1 Caratteristiche tecniche
Tab. 2.1 Datos técnicos
図2.1 仕様
Bemessungsbetriebs-
spannung
Bemessungs-
strom
Vor-
sicherung
T
Einschalt-
dauer
Nutzkühlleistung Kühlmedium:
Wasser
(s. Spezifikation)
Wasservorlauf-
temperatur
Umgebungs-
temperatur-
bereich
Betriebs-
druck
Geräusch-
pegel
Schutzart
Innenkreislauf
Außenkreislauf
Abmessungen
(B x H x T)
mm
Gewicht Farbton
Operating
voltage
Rated
current
Pre-fuse
T
Duty cycle Useful cooling
output
Refrigerant:
Water
(see specification)
Water inlet
temperature
Ambient
temperature
Operating
pressure
Noise
level
Protection categ.
Internal circuit
External circuit
Dimensions
(W x H x D)
mm
Weight Colour
Tension
nominale
Courant
nominal
Dispositif
de sécurité
T
Durée de
mise en
circuit
Puissance
frigorifique en
régime permanent
Fluide frigorigène:
de l’eau (voir les
spécifications)
Température de
l’eau à l’entrée
Température
ambiante
Pression
de régime
Niveau
sonore
Ind. de protect.
Circuit intérieur
Circuit extérieur
Dimensions
(L x H x P)
mm
Poids Teinte
Bedrijfs-
spanning
Nominale
stroom
Voor-
zekering,
traag T
Inschakel-
duur
Nuttig
koelvermogen
Koelmedium:
Water
(zie specificatie)
Waterinlaat-
temperatuur
Omgevings-
temperatuur-
bereik
Bedrijfs-
druk
Geluidsnivo Beschermklasse
Inwendig circuit
Uitwend. circuit
Afmetingen
(B x H x D)
mm
Gewicht Kleur
Märkspänning Märkström Försäkring
T
Inkopp-
lingstid
Effektiv
kyleffekt
Kylmedel:
Vatten
(se specifikation)
Tillvatten-
temperatur
Omgivnings-
temperatur
Vattentryck Ljudnivå Kapslingsklass
Inre kretslopp
Yttre kretslopp
Mått
(B x H x D)
mm
Vikt Färgton
Tensione
nominale
Corrente
nominale
Fusibile
ritardato T
Intermit-
tenza
Potenza
frigorifera utile
Mezzo frigorifero:
Acqua
(vedi specifica)
Temperatura
di ingresso
dell’acqua
Campo di
temperatura
d’impiego
Pressione
di
esercizio
Livello di
rumorosità
Grado di protez.
Circuito interno
Circuito esterno
Dimensioni
(L x A x P)
mm
Peso Colore
Tensión
de servicio
Intensidad
nominal
Fusible T Duración
de
conexión
Potencia
frigorífica útil
Agente refrigerante:
Agua
(ver especificación)
Temperatura
del agua de
entrada
Campo de
temperatura
ambiente
Presión
máxima
admisible
Nivel
de ruido
Protección
Circuito interior
Circuito exterior
Dimensiones
(anch. x alt.
x prof.) mm
Peso Color
定格電圧 定格電流 バック
アップ
ヒューズ
デュー
ティサイ
クル
有効冷却能力 冷却材:水
( 冷却材仕様
参照)
注入時水温 外部温度
範囲
動作圧 騒音
レベル
保護等級
内部回路
外部回路
外形寸法
(幅 x 高さ x 奥
行)mm
質量
カラー
L35 W10, 200 l/h
L35 W10, 400 l/h EN 60 529
SK 3212.024
24 V DC, 1,20 A 2,0 A
100% 300 W (200 l/h) > +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 42 dB (A) IP 55 150 x 300 x 80 3 kg RAL
7035
SK 3214.100
230 V,
50/60 Hz
0,17 A/
0,18 A
2,0 A/
2,0 A 100 % 600 W (200 l/h)
650 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 42 dB (A) IP 55 200 x 500 x 100 7 kg RAL
7035
SK 3217.100
230 V,
50/60 Hz
0,60 A/
0,55 A
4,0 A/
4,0 A 100 % 1000 W (200 l/h)
1100 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 44 dB (A) IP 55 298 x 520 x 135 9,5 kg RAL
7035
SK 3215.100
230 V,
50/60 Hz
0,38 A/
4,0 A
4,0 A/
4,0 A 100 % 1250 W (200 l/h)
1300 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 53 dB (A) IP 55 200 x 950 x 100 13 kg RAL
7035
SK 3247.000
230 V,
50/60 Hz
0,43 A/
0,50 A
4,0 A/
4,0 A 100 % 1540 W (200 l/h)
1700 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 51 dB (A) IP 55 380 x 825 x 105 17 kg RAL
7035
SK 3218.104
230 V,
50/60 Hz
0,42 A/
0,48 A
4,0 A/
4,0 A 100 % 2250 W (200 l/h)
2650 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 42 dB (A) IP 55 400 x 950 x 200 19 kg RAL
7035
SK 3218.100
230 V,
50/60 Hz
0,42 A/
0,48 A
4,0 A/
4, 0 A 100 % 3000 W (200 l/h)
3500 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 42 dB (A) IP 55 400 x 950 x 200 21 kg RAL
7035
SK 3216.100
230 V,
50/60 Hz
0,98 A/
1,10 A
4,0 A/
4,0 A 100 % 5000 W (400 l/h) > +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 61 dB (A) IP 55 450 x 1400 x 250 56 kg RAL
7035
SK 3216.480
400 V, 3~, 50/60 Hz
480 V, 3~, 60 Hz
1,4 A/1,6 A
1,2 A
4,0 A/
4,0 A 100% 7000 W (500 l/h) > +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 70 dB (A) IP 55 450 x 1800 x 300 79 kg RAL
7035
SK 3249.104
230 V,
50/60 Hz
0,91 A /
0,94 A
4,0 A/
4,0 A 100 % 1700 W (200 l/h)
1900 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 47 dB (A) IP 55 547 x 280 x 404 19 kg RAL
7035
SK 3249.100
230 V,
50/60 Hz
0,91 A /
0,94 A
4,0 A/
4,0 A 100 % 2250 W (200 l/h)
2500 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 47 dB (A) IP 55 547 x 280 x 404 21 kg RAL
7035
SK 3219.100
230 V,
50/60 Hz
1,2 A /
1,8 A
4,0 A/
4, 0 A 100 % 3330 W (200 l/h)
4000 W (400 l/h)
> +1°C –
+30°C
+1°C –
+70°C 1 – 10 bar 56 dB (A) IP 55 600 x 400 x 400 38 kg RAL
7035
D
GB
F
NL
S
I
E
J

14
English
4. Electrical connection
The connection voltage and frequency must cor-
respond to the rated values quoted on the data
plate. The unit must be connected to the mains
via a disconnection device which ensures at least
3 mm contact opening in the deactivated state.
No additional temperature control must be con-
nected to the supply side of the unit. Line protec-
tion should be provided by means of the pre-fuse
specified on the name plate. Please observe the
relevant regulations when installing!
The mains connection is made at the connec-
tion terminal (see fig. on page 32).
5. Cooling water
connection
The cooling water connection must be made with
pressure resistant flexible hoses which should be
secured with clips.
(Note the direction of flow and check for
absence of leaks!)
The units have no separate air-bleed. With
pressure-sealed systems, corresponding air-
bleed facilities are to be installed on the water
side.
Protect the water circuit from contamination and
excess pressure (10 bar max.).
Please observe the relevant regulations when
installing!
6. Refrigeration and
control behaviour
The fan of the air circuit operates continuously,
thus ensuring an even temperature distribution
within the enclosure. A solenoid valve controls the
cooling water flow in accordance with the preset
temperature. Setting range +20°C to +60°C.
Presetting of the enclosure temperature is made,
6.1 for SK 3214.100 / SK 3215.100 /
SK 3216.xxx / SK 3217.100 / SK 3218.xxx
via the thermostat on the rear of the unit.
6.2 for SK 3247.000 at the setting knob of the
built-in thermostat. To do this, remove the
hood of the unit.
6.3 for SK 3219.100 / SK 3249.xxx at the
potentiometer P1 of the control board.
To do this, remove the hood of the unit and
the board cover.
6.4 SK 3212.xxx has no control unit.
7. Leaks and temperature
monitoring
7.1 Temperature monitoring
Should the temperature inside the enclosure rise
by more than
10 K in the models SK 3247.000 / SK 3214.100 /
SK 3215.100 / SK 3216.xxx /
SK 3217.100 / SK 3218.xxx
7 K in the models SK 3219.100 / SK 3249.xxx
above the set-point value, then the potential-free
changeover contact will switch. This contact is
routed to the outside via a separate cable for
model SK 3247.000, via a separate plug for
model SK 3219.100 / SK 3249.xxx.
For SK 3214.100 / SK 3215.100 / SK 3216.xxx /
SK 3217.100 / SK 3218.xxx the connection of
the potential-free contact is made via the plug-in
terminal strip on the rear of the unit.
7.2 Leak monitoring
(only in the case of SK 3219.100 / SK 3249.xxx)
In the event of a leakage developing in the
SK 3219.100 / SK 3249.xxx, or a pipe fracture
occurring in the water circuit
a) the cooling water supply will be cut
off immediately,
b) the potential-free changeover contact will
be switched, and
c) the fan will be switched off.
8. Maintenance
The air/water heat exchangers require no main-
tenance (see point 12.).
Check the function of the condensate draining
facility regularly.
9. Scope of supply
and warranty
9.1 SK 3247.000 / SK 3212.xxx / SK 3214.100 /
SK 3215.100 / SK 3216.xxx / SK 3217.100 /
SK 3218.xxx
1 air/water heat exchanger, ready for connection
1 sealing tape
4 fastening bolts
(internal installation of unit 3247.000)
4 threaded pins M6 x 30
(internal installation of unit)
4 flat-headed screws M6*
4 fixing rings*
4 nuts M6
4 washers A 6.4
4 protective caps
1 set of assembly and operating instructions
1 drilling template
* Only for SK 3214.100 / SK 3215.100 /
SK 3216.xxx / SK 3217.100 / SK 3218.xxx
instead of the threaded pins.
9.2 SK 3219.100 / SK 3249.xxx
1 air/water heat exchanger, ready for connection
1 sealing plate
4 double-ended threaded bolts
4 nuts M6
4 serrated washers J 6.4
1 set of assembly and operating instructions
1 drilling template
1 angled hose fitting
1 threaded bush
2 connectors
1 eyebolt (SK 3219.100)
Guarantee:
This unit is covered by a 1-year guarantee from
the date of supply, subject to correct usage.
Within this period, the returned unit will be
repaired in the factory or replaced free of charge.
The unit is to be used for the cooling of enclosures
only. If it is connected or handled improperly the
manufacturer’s guarantee does not apply and in
this case we are not liable for any damage
caused.
Contents
1. Application
2. Technical data
3. Assembly
4. Electrical connection
5. Cooling water connection
6. Refrigeration and control behaviour
7. Leaks and temperature monitoring
8. Maintenance
9. Scope of supply and warranty
10. Notes on discharge of condensate
11. Safety instructions
12. Notes on water quality
13. Spares list
1. Application
Air/water heat exchangers are designed and
built to dissipate heat from enclosures, by cool-
ing the air inside the enclosure and protecting
temperature sensitive components. Air/water
heat exchangers are particularly suitable for the
temperature range of +40°C to +70°C, where for
system related reasons, comparable units such
as air/air heat exchangers, enclosure cooling
units or fan units with filters cannot be used to
dissipate heat effectively and economically.
2. Technical data
(see table 2.1).
3. Assembly
Please use the enclosed drilling template to cut
out the component apertures.
3.1 SK 3247.000
The unit can be mounted
a) on the enclosure
see fig. on page 30
b) inside the enclosure
see fig. on page 30
Cut the enclosed seal to length and stick to the
appliance as shown in fig. 3.2, page 31.
3.2 SK 3219.100 / SK 3249.xxx
The unit should be mounted on the top cover
of the enclosure in accordance with fig. on
page 31.
3.3
SK 3212.230 / SK 3214.100 / SK 3215.100 /
SK 3216.xxx / SK 3217.100 / SK 3218.xxx
External installation of the unit (Fig. page 30):
Screw the four fastening bolts ➀, together with
the washer ➁and nut ➂, to the mounting level
➃of the enclosure. Push the heat exchanger ➄
into position and secure with four screws ➅.
Internal installation of the unit (Fig. page 30):
Insert four fastening bolts ➀into the appliance
from behind. Slide the fixing ring ➆onto the
fastening bolts as a mounting aid. Screw the
appliance, together with the washer ➁and nut
➂, to the mounting level of the enclosure from
the outside. Push the protective cap ➇onto the
nut.

15
1
/2˝
10. Notes on discharge
of condensate
A drain hose must be fitted to the 1/2˝ flanged
socket protruding from the unit, to discharge any
condensate water accumulating.
For SK 3219.100 / SK 3249.xxx connect drain
hoses with elbow sockets (do not kink!) and direct
immediately downwards to avoid reflux and over-
flow of the condensate into the inside of the unit.
Fig. 10.1 Condensate discharge
SK 3219.100 / SK 3249.xxx
In order to ensure the safe discharge of conden-
sate, the following points must be observed:
●Discharge hose must be routed free from kinks!
●Do not reduce the hose cross-section!
●Always install the drainage hose with a
downward slope!
In order to prevent increased development of con-
densate and also in the interest of energy savings,
the cooling water temperature should be matched
to the required cooling output (see performance
diagrams).
11. Safety instructions
●When installing the device, the condensate
discharge must be routed out of the enclosure!
●In order to avoid frost damage, the minimum
permissible water temperature of +1°C must
not be undercut at any point in the water cycle!
●It is essential to obtain the manufacturer’s
permission before adding anti-freeze!
●During storage and transportation below
freezing point, the water cycle should be
drained completely using compressed air!
●Only set the thermostat as low as is strictly
necessary, because of undercutting the dew
point with a falling water inlet temperature
(condensation)!
●It is very important that the enclosure is sealed
on all sides (IP 54), particularly the cable entry
(condensation)!
12. Notes on water quality
For safe operation of the equipment, it is essential
to observe the VBG guidelines on cooling water
(VGB R 455 P).
Cooling water must not contain any limescale
deposits or loose debris; in other words, it should
have a low level of hardness, particularly a low
level of carbon hardness. For recooling within the
plant, the carbon hardness should not be too
high. On the other hand, however, the water
should not be so soft that it attacks the operating
materials. When recooling the cooling water, the
salt content should not be allowed to increase
excessively due to the evaporation of large
quantities of water, since electrical conductivity
increases as the concentration of dissolved sub-
stances rises, and the water thereby becomes
more corrosive. For this reason, not only is it
always necessary to add a corresponding quan-
tity of fresh water, but also to remove part of the
enriched water.
Gypsiferous water is unsuitable for cooling pur-
poses because it has a tendency to form boiler
scale, which is particularly difficult to remove.
Furthermore, cooling water should be free from
iron and manganese, because otherwise de-
posits may occur which settle in the pipes and
block them. At best, organic substances should
only be present in small quantities, because
otherwise sludge deposits and microbiological
contamination may occur.
12.1 Preparation and maintenance
of the water in recooling systems
Depending on the type of installation to be
cooled, certain requirements are placed on the
cooling water with respect to purity. According
to the level of contamination and the size and
design of the recooling systems, a suitable
process is used to prepare and/or maintain the
water. The most common types of contamination
and most frequently used techniques to elimin-
ate them in industrial cooling are:
Contamination of the water Procedure
Mechanical contamination
Filtering of water via
– Mesh filter
– Gravel filter
– Cartridge filter
– Precoated filter
Excessive hardness Water softening via ion exchange
Moderate content of mechanical contaminants
and hardeners Addition of stabilisers and/or dispersing
agents to the water
Moderate content of chemical contaminants Addition of passifiers and/or inhibitors
to the water
Biological contaminants, slime bacteria and algae Addition of biocides to the water
In order to ensure correct operation of a recooling
system which is operated with water on at least
one side, the properties of the added or system
Hydrological data
SK 3212.xxx / SK 3247.000 /
SK 3219.100 / SK 3249.100 /
SK 3214.100 / SK 3215.100 /
SK 3216.xxx / SK 3217.100 /
SK 3218.100
SK 3218.1041)
SK 3249.1041)
pH value 7 – 8.5 6 – 9
Carbonate hardness > 3 < 8 °dH 1 – 12 °dH
Free carbon dioxide 8 – 15 mg/dm31 – 100 mg/dm3
Accompanying carbonic acid 8 – 15 mg/dm3free
Aggressive carbonic acid 0 mg/dm30 – 400 mg/dm3
Sulphides free free
Oxygen < 10 mg/dm3< 10 mg/dm3
Chloride ions < 50 mg/dm3< 200 mg/dm3
Sulphate ions < 250 mg/dm3< 500 mg/dm3
Nitrates and nitrites < 10 mg/dm3< 100 mg/dm3
COD < 7 mg/dm3< 40 mg/dm3
Ammonia < 5 mg/dm3< 20 mg/dm3
Iron < 0.2 mg/dm3free
Manganese < 0.2 mg/dm3free
Conductivity < 2200 μS/cm < 4000 μS/cm
Residue on evaporation < 500 mg/dm3< 2000 mg/dm3
Potassium permanganate consumption < 25 mg/dm3< 40 mg/dm3
Suspended matter
< 3 mg/dm3
> 3 < 15 mg/dm3part current purification recommended
> 15 mg/dm3continuous purification recommended
water used should not deviate substantially
from the following list of hydrological data:
1) The complete absence of corrosion under experimental conditions suggests that solutions with a
significantly higher salt content and greater corrosion potential (such as seawater) may still be
tolerated.
13. Spares list
(see page 28)

28
75
73
91
10
95
71
33
15
16
40
32
Ersatzteil-
liste Spares
list
Liste de
pièces
détachées
Lijst
reserve-
delen
Reserv-
delslista
Lista dei
pezzi di
ricambio
Lista de
piezas de
repuesto
スペア
パーツ
Bezeichnung Description Signification Benaming Beteckning Descrizione Descripción 製品名
10 Ventilator,
komplett Fan,
complete Ventilateur,
complète Ventilator,
kompleet Fläkt,
komplett Ventilatore,
completa Ventilador,
completo ファン、
一式
15 Zubehörbeutel Dispatch bag Pochette
d’accessoires Zakje toebehoren Tillbehörspåse Sacchetto
accessori Bolsa de
accesorios アクセサリー
バッグ
16 Abdichtplatte Sealing plate Plaque
d’étanchéité Afdichtplaat Tätningsplatta Piastra di tenuta Placa de
estanqueidad 密閉用プレート
32 Magnetventil,
komplett Solenoid valve,
complete Vanne électroma-
gnétique, complète Magneetventiel,
kompleet Magnetventil,
komplett Valvola elettromag-
netica, completa Electroválvula,
completa マグネットバルブ、
一式
33 Rückschlagventil Flap valve Clapet antiretour Terügstroomventiel Backventil Valvola di
non ritorno Válvula de
retención フラップバルブ
35 Zwei-Stufen-
Thermostat Two-stage
thermostat Thermostat
à deux paliers Tweestanden-
thermostaat Tvåstegs-
termostat Termostato
a due stadi Termostato
de dos estados 二段階式
サーモスタット
40 Steuerplatine
komplett Control PCB
complete Platine de com-
mande, complète Stuurstroomprint,
kompleet Styrkort,
komplett Piastra circuito
stampate, completa Pletina de mando
completa コントロールPCB、
一式
48 Lufteintrittsgitter Air inlet grille Grille d’entrée d’air Luchtinlaatrooster Luftingångsgaller Griglia d’entrata
dell’aria Rejilla de entrada
de aire 吸気グリッド
71 Temperaturfühler Temperature
sensor Sonde de
température Temperatuursensor Temperaturgivare Sonda di
temperatura Sonda térmica 温度センサー
73 Leckagesensor Leakage sensor Palpeur de fuite Lekkagesensor Läckagesensor Rivelatore
di perdite Sensor de fugas
de agua 漏水モニター
75 Haube,
komplett Cover,
complete Couvercle,
complète Afdekkap,
kompleet Huv,
komplett Calotta,
completa Cubierta
completa カバー、
一式
91 Wärmetauscher Heat exchanger Echangeur
thermique Warmtewisselaar Värmeväxlare Scambiatore
di calore Intercambiador
de calor ヒートエクスチェン
ジャー
95 Bodenwanne,
komplett Base tray,
complete Bac de rétention,
complète Bodemplaat,
kompleet Bottentråg,
komplett Vaschetta di racc.
cond., completa Bandeja de base
completa ベーストレイ、
一式
DE J
GB NL I
FS
Position
Item
Pos.
Pos.
Pos.
Pos.
Posición
項目
Bei Bestellung unbedingt angeben
Typ:
Fabrikations-Nr.:
Herstelldatum:
Ersatzteil-Nr.:
Absolutely necessary in case of order
Type:
Fabrication no.:
Manufacturing date:
Spare part no.:
SK 3219.100
スペアパーツご発注時に必ずご記入下さい。
クーラー型式:
製造番号:
製造日時:
スペアパーツ番号:

29
10
75
91
40
15
71
32
95
16
73
33
91
33 15
32
75
10
35
48
32
75
10
35
91
48
15
32
33
35
91
48
15
10
75
SK 3249.100 / SK 3249.104 SK 3247.000
SK 3212.230 / SK 3214.100 /
SK 3215.100 / SK 3217.100 SK 3216.xxx / SK 3218.100 / SK 3218.104
* nicht bei SK 3212.xxx /
not installed in SK 3212.xxx
*
*

30
1
4
3
4
2
6514283271
5
4
Geräteanbau
External mounting
Montage en saillie
Apparaatopbouw
Påbyggnad
Montaggio sporgente
Montaje exterior del aparato
表面取付け
Geräteeinbau
Internal mounting
Montage encastré
Apparaatinbouw
Inbyggnad
Montaggio incassato
Montaje interior del aparato
全埋め込み取付け
M 6 x 40
M 6
A 6.4
1/2″
1
20 x 10
M 6
A 6.4
M 6
SK 3247.000
SK 3212.xxx / SK 3214.100 / SK 3215.100 / SK 3216.xxx /
SK 3217.100 / SK 3218.xxx
SK 3247.000
SK 3212.xxx / SK 3214.100 / SK 3215.100 / SK 3217.100 / SK 3218.xxx
Geräteanbau
External mounting
Montage en saillie
Apparaatopbouw
Påbyggnad
Montaggio sporgente
Montaje exterior del aparato
表面取付け
SK 3215.100
/2w
3

31
1/2″
547
404
280
95 310 87
400
226
210
264
280
34
72
103
Geräteanbau
External mounting
Montage en saillie
Apparaatopbouw
Påbyggnad
Montaggio sporgente
Montaje exterior del aparato
表面取付け
Geräteeinbau
Internal mounting
Montage encastré
Apparaatinbouw
Inbyggnad
Montaggio incassato
Montaje interior del aparato
全埋め込み取付け
Abb. 3.2 Anbringung der Dichtung
Fig. 3.2 Attaching the seal
Fig. 3.2 Mise en place du joint
Afb. 3.2 Aanbrengen van de afdichting
Bild 3.2 Montage av tätning
Fig. 3.2 Applicazione della guarnizione
Fig. 3.2 Colocación de la junta
図3.2 パッキンの取付
SK 3249.xxx
SK 3212.xxx / SK 3214.100 / SK 3215.100 /
SK 3216.xxx / SK 3217.100 / SK 3218.xxx
SK 3212.xxx / SK 3214.100 / SK 3215.100 /
SK 3217.100 / SK 3218.xxx

32
NL1
M
1~
M1
K3
VE2 VE3
MA2 ST1 ST2 ST3 TS1 TS2 LS1 LS2
P1
D9 D8
ABC CBA
Y1
B2
B1
21 3
NPEL1
123
PE
PE
g/g 21
br
C1
PE 456
654
T1 T2 S3
12
A1
X10
X20
X3
X1: X2:
X1:
X11
M
1~
C1
M1
X10
L1 N
X11
X20
SK 3249.100 / SK 3249.104 / SK 3219.100
Anschlußplan
Wiring diagram
Schéma des connexions
Aansluitschema
Anslutningsdiagram
Schema di allacciamento
Esquema de conexiones
配線図
SK 3212.230
Anschlußplan
Wiring diagram
Schéma des connexions
Aansluitschema
Anslutningsdiagram
Schema di allacciamento
Esquema de conexiones
配線図
Netzanschluß
Mains connection
Raccordement au résau
Netaansluiting
Nätanslutning
Allacciamento rete
Conexión a la red
電源
Technische Daten siehe Typenschild
Technical data see name plate
Données techniques voirplaque signalétique
Technische gegevens zie typeplaatje
Tekniska data se typskylten
Caratteristiche tecniche vedi dati di targa
Datos técnicos verplaca de características
仕様については銘板参照
T
i
max.
Leck
Leak
Fuite
Lekkage
Läckage
Perdita
Fugas
漏電
024

33
L 12NPE3456
1~
sw2
sw
bl gn/gb
gn/gb
sw2
sw1
sw
sw1 sw2 gn/gb
br
sw1
sw3 sw1
sw2
<
14
11
12
31
32
34
F1.2F1.1
Y1
M1
C1
➁➂
➀
1~
32
X10 3
C1
F1.2
Y1
14
31
T
34
M1
45
X20
X10
L1 N
T
11
F1.1
M
3~
M1
L1 L2 L3 1 2 3 4 5
L1 (U1)
L2 (V1)
L3 (W1)
X12
X11
X10
F1.2
F1.1
14
11
31
Y1
32 34
T>
T>>
SK 3247.000
Wirkschaltplan
Detailed wiring diagram
Schéma des connexions détaillé
Vermogensdiagrammen
Effektdiagram
Schema di allacciamento
Esquema de conexiones
詳細配線図
➀Thermostat
Thermostat
Thermostat
Thermostaat
Termostat
Termostato
Termostato
サーモスタット
➁Ventilator
Fan
Ventilateur
Ventilator
Fläkt
Ventilatore
Ventilador
ファン
➂Magnetventil
Solenoid valve
Vanne électromagnétique
Magneetventiel
Magnetventil
Valvola elettromagnetica
Válvula electromagnética
マグネットバルブ
SK 3214.100 / SK 3215.100 / SK 3216.100 /
SK 3217.100 / SK 3218.100 / SK 3218.104
Anschlußplan
Wiring diagram
Schéma des connexions
Aansluitschema
Anslutningsdiagram
Schema di allacciamento
Esquema de conexiones
配線図
Technische Daten siehe Typenschild
Technical data see name plate
Données techniques voir plaque signalétique
Technische gegevens zie typeplaatje
Tekniska data se typskylten
Caratteristiche tecniche vedi dati di targa
Datos técnicos ver placa de características
仕様については銘板参照
SK 3216.480
Anschlußplan
Wiring diagram
Schéma des connexions
Aansluitschema
Anslutningsdiagram
Schema di allacciamento
Esquema de conexiones
配線図
Technische Daten siehe Typenschild
Technical data see name plate
Données techniques voir plaque signalétique
Technische gegevens zie typeplaatje
Tekniska data se typskylten
Caratteristiche tecniche vedi dati di targa
Datos técnicos ver placa de características
仕様については銘板参照
M
M

34
Anschlußschema
A1 = Steuerplatine
B1 = Temperaturfühler
B2 = Leckagefühler
C1 = Betriebskondensator
F1 = Thermostat
F1.1 = Schaltkontakt
F1.2 = Störmeldekontakt
M1 = Ventilator
Y1 = Magnetventil
X1 = Klemmleiste
X10 = Stecker Netzanschluß (schwarz)
X11 = Stecker Sammelstörmeldung (braun)
X12 = Gerätesteckanschluß TW
X20 = Steckverbindung Ventilator
P1 = Sollwert-Potentiometer
Schrankinnentemperatur
ABC = Umschaltung der Betriebsart
Aansluitschema
A1 = Stuurstroomprint
B1 = Temperatuursensor
B2 = Lekkagesensor
C1 = Bedrijfskondensator
F1 = Thermostaat
F1.1 = Schakelaar
F1.2 = Storingsmelderkontakt
M1 = Ventilator
Y1 = Magneetventiel
X1 = Klemmenstrook
X10 = Stekker netaansluiting (zwart)
X11 = Stekker verzamelsfoormelding
(bruin)
X12 = Connectoraansluiting TW
X20 = Connector voor ventilator
P1 = Temperatuur in kast
ABC = Omschakeling van bedrijfsstand
Esquema
de conexiones
A1 =
Pletina de mando
B1 =
Sensor de temperatura
B2 =
Sensor de fugas
C1 =
Condensador de servicio
F1 = Termostato
F1.1 = Contacto de conexión
F1.2 = Contacto de aviso de averia
M1 =
Ventilador
Y1 = Válvula electromagnética
X1 = Regleta de bornes
X10 = Enchufe alimentación de red (negro)
X11 = Enchufe aviso de avería colectiva
(marrón)
X12 = Conexión de enchufe del aparato TW
X20 = Conexión ventilador
P1 = Valor teórico potenciómetro
temperatura interior armario
ABC =
Conmutación de la clase de servicio
D
NL
E
Wiring diagram
A1 = Control PCB
B1 = Temperature sensor
B2 = Leak sensor
C1 = Operating capacitor
F1 = Thermostat
F1.1 = Switch contact
F1.2 = Fault signal contact
M1 = Fan
Y1 = Solenoid valve
X1 = Terminal strip
X10 = Mains plug connector (black)
X11 = Collective fault signal plug (brown)
X12 = Unit plug connector TW
X20 = Plug connection fan
P1 = Set-point setter,
enclosure internal temperature
ABC = Changeover of operating mode
Anslutningsschema
A1 = Styrkort
B1 = Temperaturavkännare
B2 = Läckageavkännare
C1 = Driftkondensator
F1 = Termostat
F1.1 = Omkopplare
F1.2 = Felmeddelande
M1 = Fläkt
Y1 = Magnetventil
X1 = Klämlist
X10 = Kontakt nätanslutning (svart)
X11 = Kontakt störsignaler (brun)
X12 = Aggregatuttag TW
X20 = Anslutning fläkt
P1 = Apparatskåpets innertemperatur
ABC = Växling av funktion
配線図
A1 = 制御PCB
B1 = 温度センサー
B2 = 漏水センサー
C1 = 操作用コンデンサー
F1 = サーモスタット
F1.1 = スイッチ接点
F1.2 = エラー信号接点
M1 = ファン
Y1 = マグネットバルブ
X1 = ターミナルストリップ
X10 = 電源プラグ(黒)
X11 = 集合故障信号プラグ(茶)
X12 = ユニットプラグコネクタ TW
X20 = プラグ接続式ファン
P1 = 設定値ポテンシャルメータ
エンクロージャー内部温度用
ABC = 運転モード切替
GB
S
J
Schéma électrique
A1 = Platine de commande
B1 = Sonde de température
B2 = Sonde de niveau d’eau
C1 = Condensateur de régime
F1 = Thermostat
F1.1 = Contact de commutation
F1.2 = Contact de signalisation de défaút
M1 = Ventilateur
Y1 = Vanne électromagnétique
X1 = Bornier
X10 = Bornes de raccordement secteur (noir)
X11 = Bornes de raccordement des
indications de défaut (brun)
X12 = Connecteur enfichable TW
X20 = Fiche du ventilateur
P1 = Potentiomètre de réglage de la
température intérieure de l’armoire
ABC =
Commutation du mode
de fonctionnement
Schema allacciamenti
A1 = Piastra circuito stampate
B1 = Sonda di temperatura
B2 = Rivelatore (sonda) di predita
C1 = Condensatore d’esercizio
F1 = Termostato
F1.1 = Contatto degli interruttori
di distribuzione
F1.2 = Contatto di segnalazione guasti
M1 = Ventilatore
Y1 = Valvola elettromagnetica
X1 = Morsettiera
X10 =
Spina allacciamento rete (nero)
X11 =
Spina circuito de segnalazione
(marrone)
X12 = Allacciamento apparecchio TW
X20 = Connettore per ventilatore
P1 = Regolazione della temperatura interna
ABC = Commutazione del tipo esercizio
F
I
This manual suits for next models
10
Table of contents
Popular Heating System manuals by other brands

ELEKTRA
ELEKTRA FreezeTec installation manual

Watts
Watts Push'n'Go HKV-R Series Installation and operating manual

NuAire
NuAire ecosmart SQURBO XBOX Installation, operating and maintenance instructions

Innova
Innova HRP DOMO EXT Installation, use and maintenance manual

LG
LG MULTIV III Service manual

Tyco
Tyco Raychem ETL-10 installation manual

Oxygen
Oxygen X-Air V500E Installation and operation manual

ubbink
ubbink Ubiflux Vigor W225 installation instructions

Miller
Miller 907689 owner's manual

Vents
Vents VUT R 400 WH EC A17 user manual

Olimpia splendid
Olimpia splendid SITALI CXVM 280 Instructions for installation, use and maintenance manual

Trane
Trane IntelliPak SCWG 020 installation manual