
Installation and operation manual – remote control 7
4 CONFIGURATION OF THE OPERATING PARAMETERS
This Paragraph is reserved exclusively for the author-
ised Robur Technical Assistance Centre.
Incorrect conguration of the remote control may cause
the system to malfunction.
This operation is used to congure the remote control in such a
way that it is compatible with the boiler and the relative system
to which it is connected.
How to congure the operating parameters
1. Set the remote control to the OFF mode.
2. Press and hold down the and keys until PAr ap-
pears on the display.
3. To conrm access, press the key. The display shows the
parameter number instead of the time and the value asso-
ciated with the parameter instead of the temperature. The
parameter number ashes (Figure 4.1
p.7
).
Figure4.1Selection of the parameter to be modied
4. Turn the knob to select the parameter number to be
displayed. The display shows the value associated with the
parameter.
5. To change the value press the knob: the value associ-
ated with the parameter starts ashing (Figure 4.2
p.7
).
6. Turn the knob to change the displayed value.
If no key is pressed for a period of 30 seconds, the change
made is aborted and normal operation is restored.
7. Press the key to save the value.
8. To exit the conguration mode, press .
Figure4.2Changing the selected value (ashing)
The editable parameters are as follows:
▶
P00 Room temperature probe correction
Value to add/subtract (-5.0 °C ÷ +5.0 °C) to the displayed
room temperature to compensate for any errors.
▶
P01 Trip temperature for the room antifreeze function
Trip temperature for the room antifreeze function (0,1 ÷
10,0 °C).
Setting parameter P01 to 0,0 disables the room anti-
freeze function.
▶
P02 Thermal dierential (OFF)
Value to be added to the set room setpoint that deter-
mines the end of the heating request.
Example:
Tsetpoint = 20,0 °C
P02 = 0,5 °C
Tsetpoint + P02 = 20,0 + 0.5 = 20,5 °C
The heat demand ends when the Troom is greater than
20,5 °C.
▶
P03 Thermal dierential (ON)
Value to be subtracted from the set room setpoint that
determines the start of the heating request.
Example:
Tsetpoint = 20,0 °C
P03 = 0,5 °C
Tsetpoint - P03 = 20,0 - 0,5 = 19,5 °C
The heat demand starts when the Troom is less than 19,5
°C.
▶
P04 Thermoregulation type
0 = On / O
1 = Modulating on room temperature probe
2 = Modulating on outdoor temperature probe
3 = Modulating on outdoor and room temperature
probes
4 = Disabled
Table4.1Operating parameters
Parameter Description Value Default
P00 Room temperature probe correction -5 / +5 °C 0 °C
P01 Trip temperature for the room antifreeze function 0,1 / 10 °C
0,0 °C = OFF 5 °C
P02 Thermal dierential OFF 0,0 / +1 °C + 0,3 °C
P03 Thermal dierential ON -1,0 / 0,1 °C - 0,3 °C
P04 Thermoregulation type 0 - 4 0