
9
|
8|
8013901 I Instructions for use for SPA treatment table SONORA | REV 9 | Revision status 23/07/2020 8013901 I Instructions for use for SPA treatment table SONORA | REV 9 | Revision status 23/07/2020
The manufacturer cannot be made responsible for damage that is caused through use
that deviates from the intended use or failure to comply with the safety instructions and
warnings.
Danger from electrical energy
Danger due to electrical energy can occur through: performing incorrect repairs on the electri-
cal components, using “NON-ORIGINAL PARTS” in the transformer area, failure to remove the
mains plug for maintenance tasks and repair work, running over, damaging the mains cable.
Maintenance tasks and repair work must only be performed by specialists authorized by the
manufacturer.
When the table is not in use, always switch off the ON/OFF switch under the table and pull the
mains plug. The table must not be electrically adjusted, under any circumstances, as long as
people are within the movement range of the table.
Interference with other electrical devices can occur under certain circumstances.
Protective devices
Safeguards and cladding elements are installed for the protection of the user and operator.
They must not be removed, changed or bypassed.
HAVE IDENTIFIED DEFECTS RECTIFIED IMMEDIATELY!
Daily function checks
Prior to each use the checks listed below must be executed:
1. All electrically adjustable sections, such as back, leg and height adjustment, must be
checked for functionality via the manual control.
2. General visual inspection
IF THIS REQUIREMENT IS NOT SATISFIED, THE GUARANTEE WILL LAPSE AND WE
CANNOT ACCEPT LIABILITY!
GENERAL INFORMATION
Initial check for faults
If a motor does not stop despite "releasing" the function button, or if the function of the manual
switch should have to be switched off in other (emergency) cases, the complete power supply
can be interrupted by third parties (e.g. personnel) with the ON/OFF switch (locking device)
under the treatment table. This locking device cannot be actuated by the customer/patient
during intended use. Alternatively, the mains plug can also be pulled out.
Accessibility of the mains plug
The mains plug is used for disconnection from the mains. The accessibility of the mains plug
must always be ensured for disconnecting from the mains network in an emergency.
Proper status of the mains connection line
If you should determine that the power cable or any other cable is damaged, unplug the power
plug and arrange for the faulty cable to be replaced by a qualified electrician.
Stumbling hazard
Do not run over the mains cable (danger of crushing, electrical hazard) or the manual switch
cable (danger of crushing, malfunction). Lay the mains cable so that it is trip-proof. The mains
cable must not be laid taut.
Electrical hazard
The mains cable and cable for the foot switch must not get into the moving parts; danger of
crushing and/or danger of electrical shock.
Set-up Diagram | Space Requirements
It is essential to ensure that the table is positioned far enough away from the wall that it does
not collide anywhere and is easily accessible.