EPA 2000 BREAKOUT CABLE CONNECTIONS
• THE A/C CURRENT PROBES ARE A CLAMP-ON TYPE
THAT CAN BE ATTACHED TO A/C CONDUCTORS
QUICKLY AND SAFELY.
• CURRENT PROBES SHOULD BE CONNECTED TO THE
ACCESSIBLE PHASE CONDUCTORS, NEUTRAL (WHITE)
CONDUCTOR, AND GROUND (GREEN) CONDUCTOR.
• CONNECT ONE PROBE PER CONDUCTOR.
• ENSURE THAT THE A/C CURRENT PROBE IS SECURELY
CLAMPED AROUND THE CONDUCTOR AND THAT THE
CURRENT PROBE JAW IS SECURELY CLOSED.
• CONTACT RXMS @ 603-666-6606 X 201
IMMEDIATELY IF THE SUPPLIED CURRENT PROBES DO
NOT FIT AROUND THE INDIVIDUAL CONDUCTORS.
• THE CURRENT PROBES ARE POLARIZED AND THEY
MUST BE CONNECTED IN THE PROPER DIRECTION
FOR AN ACCURATE ANALYSIS.
• ARROWS ON THE CURRENT PROBE POINT FROM THE
SOURCE (PLUG - MALE SIDE, UTILITY OR LINE) TO
THE LOAD (FEMALE SIDE OF THE A/C ADAPTER,
OR THE EQUIPMENT BEING MONITORED).
• IDEALLY, A CURRENT PROBE SHOULD BE CONNECTED
FOR EACH VOLTAGE LEAD THAT IS CONNECTED.
• ENSURE THAT THE CURRENT PROBE IS CONNECTED
TO THE SAME CONDUCTOR AS THE VOLTAGE LEAD
FOR THAT PHASE.