S.& A.S. OMEGA-ATS User manual

OFFICE: BOUTROS BLDG., 1ST BSMT, CHEIKH‐GHABI, BEIRUT 2068 7808
TEL: 961‐1‐216994 (2 LINES), FAX: 961‐1‐339600
HEADQUARTERS AND FACTORY: S. & A. S. BLDG, SEASIDE ROAD, JIEH CHOUF
TEL: 961‐7‐996333 (2 LINES), FAX: 961‐7‐996116
WW.SASCONTROLLERS.COM
USER’S MANUAL
FOR S/W V2.00.4 & ONWARDS
FOR S/W V3.00.4 & ONWARDS
2229
AUTOMATIC TRANSFER SWITCH CONTROLLER
OMEGA-ATS/ATSO
V1.2b


3. TECHNICAL
SPECIFICATION
S
3. TECHNICAL SPECIFICATIONS
2. FRONT
PANEL
DESCRIPTION
2.1 MEASURED AND DISPLAYED MEASUREMENTS
2.1.1 DISPLAYED PAGES
2.1.2 SYMBOLS DESCRIPTIONS
2.2 FRONT PANEL LEDS
2.3 DETECTED AND SIGNALED FAULTS
2.3.1 GENSET STATUSES
2.3.2 GENSET FAULTS
2.3.3 UTILILTY STATUSES
2.3.4 UTILITY FAULT
2.4 MENU DESCRIPTION
2.4.1 PASSWORD
2.4.2 ACCESSING THE MENU
2.4.3 SUBMENUS
2.4.4 CONFIGURATION SUBMENU
2.4.5 GENSET SUBMENU
2.4.6 UTILITY SUBMENU
2.4.7 MODBUS SUBMENU
2.4.8 ETHERNET SUBMENU
2.4.9 LCD DISPLAY SUBMENU
2.4.10 SD CARD SUBMENU
2.4.11 MENU MAPPING WITH PREVIOUS VERSION
2.5 PARAMETER DESCRIPTION
2.6 MODBUS REGISTERS
2.7 TERMINAL DESCRIPTION
4. FIRMWARE
UPGRADE
4.1 FIRMWARE UPGRADE USING PC
4.1.1 INSTALLING THE OMEGA USB DRIVER
4.1.2 NSTALLING THE FIRMWARE UPGRADE SOFTWARE
4.1.3 FIRMWARE UPGRADE PROCESS
4.2 FIRMWARE UPGRADE USING GOOGLE PLAY STORE ON
SMART PHONE
4.2.1 INSTALLING THE SASPTOOL FIRMWARE
APPLICATION ON THE MOBILE
4.2.2. FIRMWARE UPGRADE PROCESS
4.3 ONLINE FIRMWARE UPGRADE
1. GENERAL
DESCRIPTION
1.1 INTRODUCTION
1.2 FEATURES
1.3 OPERATION

5.1 DATA SAMPLING AND RETRIEVAL
5. SD CARD
RETRIEVAL
6.
DIMENSIONS
6. DIMENSIONS
7. APPENDIX A
7.
APPENDIX A

1. GENERAL DESCRIPTION
1.1 INTRODUCTION
This module controls up to three power sources: mains and two generators (MGG). It is also possible
to configure it to control mains and one generator (MG) or just two generators (GG). It features
isolated measurement of the voltages and frequency on all three sources as well as the current on the
load side. It has four operating modes selectable by the user: OFF, AUTO, MAINS, G1 or G2.
This module can be configured to be used as ATS or ATSO.
The user interface consists of a Graphical LCD display. A mode push button is provided to select the
operating mode and four push buttons are used to access a menu of parameters. The menu gives
access to all timers, set points and other parameters relevant to the control and protection of the
installation.
This module comes with RS485, USB and Ethernet communication ports. It also features a 4GB
MicroSD card for data and event logging. Data and event retrieval is done by either USB port or
Internet through a dedicated website.
The firmware could be easily upgraded on site via the USB interface using a desktop application or
any smart phone with a free Android app.
1.2 FEATURES
Microcontroller based design
Measurement and display of the voltages and frequency on the three power sources
Measurement and display of the current on the load side
Measurement and display of the power on the load side
All three supplies are monitored for over/under voltage, phase presence and sequence
All three supplies are monitored for over/under frequency
Load side is monitored for over current when it is not supplied by the Mains
Display of Software version, the internet connection status, the date and time
Alternate function to keep the running hours of the Gensets similar (For ATS)
Automatic switching between the two Gensets based on the load (For ATSO)
Weekly exerciser function
Ability to control contactor, motorized circuit breakers and motorized changeover switches
Easy to fit DIN standard 184X139 panel mount housing
Connection is via locking plug and socket connectors
Front panel LEDs for inputs status
Menu to provide access to all timers, set points and other parameters
Over / Under frequency alarm and shut down
Over / Under voltage alarm and shut down
Over current alarm and shut down
Operation by push buttons
USB interface
Ethernet interface (optional)
Serial RS485 Modbus protocol (optional)
4GB Micro SD card for event and data logging (optional)
Internet communication: no software installation required
Galvanic isolation for all three suppliers AC inputs
Parameters can be edited and updated from any remote interface at any time even when an engine
is running
Menu accessible from front panel as well as from the internet.
1. GENERAL
DESCRIPTION

OMEGA v1.0/1.1
OMEGA v1.2
On-site Firmware Upgrade
Not Available
Available via USB
Remote Firmware Upgrade
Not Available
Available via Internet
Faults history
Not Available
Up to 100 faults if the SD card is mounted
Up to 15 faults if the SD Card is not
mounted
User interface
16-char alphanumeric LCD
displays with 5 push buttons
to select between operating modes
New Graphical LCD Display with:
-Easy access to all measurements in
one page
-Easy access to the menu
-One dedicated push button to
select between modes
-Four push buttons to navigate
between displayed pages
Ethernet Interface
Not Available
Optional
Modbus Port
Not Available
Optional
SD Card
Not Available
Optional
Events/Time Logs
Not Available
Available if the SD card is mounted
1.3 OPERATION
Four operating modes are provided. To switch from one mode to another, press the mode push button till
you reach the required operating mode and then wait for 2 seconds for the operating mode to be applied.
Following is description of the operating modes:
OFF: In this mode the module cuts power completely from the load.
AUTO: In MGG and MG installation,the module monitors the Utility supply. When the Utility fails or its
contactor fails to engage, the module counts a “Response” delaybefore starting the genset.
In GG installation, the module monitors the remote control input. When the remote control input becomes
active, the module counts a “Response” delay before starting the genset.
The genset is started only if it is in Ready mode.
In MGG and GG installation:
oFor ATS type: Following a mains failure, G1 or G2 is started depending on the “Alternate
hrs”after a “Response” delay. Load is engaged after the elapse of the “Warm-up” delay.
If “Alternate hrs”is set to a value of hours, the genset with the less number of run hours is
started.
If “Alternate hrs” is set to G1/G2, G1/G2 is started.
Once a genset is feeding the load, it keeps feeding it for the number of hours set in
“Alternate hrs”.
oFor ATSO type: Following a mains failure, G1 (the smaller genset) or G2 (the bigger genset)
is started depending on the “Req priority”after a “Response” delay. Load is engaged after
the elapse of the “Warm-up” delay.
If the “Req priority” is set to Ld, G2 is requested if the load prior to mains failure was above
the “G1 Max Load %”, Otherwise, G1 is requested. The value of the load supplied by the
Mains is retained for 5 minutes only. So if 5 minutes have elapsed from the mains failure, G2
is started always. This could occur when switching to AUTO mode from Mains or OFF
modes.
If the “Req priority” is set to G1/G2, G1/G2 is requested independently from Load.
If G1 is feeding the load and the current goes above the “G1 Max Load %” for a “G1 MaxLd
del”delay, G2 is requested. If G2 is feeding the load and the current goes below the “G2
Min Load %”for a “G2 MinLd del”delay, G1 is requested.
1. GENERAL
DESCRIPTION

When the Mains is re-established, the power is switched back with a dead transfer time “Transfer”
after a restoration delay “Mains Rest.”and the genset is shut down after the elapse of the “Cooling”
time. For MGG and GG installation, in case the requested genset fails to start or its contactor fails to
engage or it shuts down due to any fault, the other genset will automatically start and supply the load.
If the “Hold Start”is enabled, and in case the genset failed to start, the start signal remains on so that
when it restarts, it will feed the load after disengaging the running genset. When the “Hold Start” is
disabled, the start signal is removed. Manual reset is required to recover from this failure. Please refer
to section 2 for display description.
Mains: The module monitors the Mains supply. The load is fed exclusively from this supply if it is within the
acceptable limits. No gensets will be started if the Mains fails.
G1: In this mode, G2 is always in standby mode. G1 is started when it is in ready modeand the Mains fails.
G2: In this mode, G2 is always in standby mode. G1 is started when it is in ready modeand the Mains fails.
In case contactors are used for the transfer switch, each contactor is controlled by one dry contact. The
other dry contact is used as an alarm output (CxD.NO).
If motorized circuit breakers or changeover switches are used, each motorized breaker/ switch is controlled
by two relays. The first has one normally open dry contact (CxENG) and is used to engage the motorized
circuit by giving a pulse of 2 seconds, the second is controlled by a contact that has a common (CxC),
normally open (CxD.NO) and normally closed (CxD.NC) contacts to disengage the motorized circuit breaker
by giving a pulse of 4 seconds.
Presettable in the menu. Refer to Section 2.4
Refer to Section 2.5
1. GENERAL
DESCRIPTION

2. FRONT PANEL DESCRIPTION
2.1 MEASURED AND DISPLAYED MEASUREMENTS
2.1.1 DISPLAYED PAGES
Graphical interface showing all power sources with their contactors states, voltages, frequencies,
currents and power in KW.
Display
Notes
The line-neutral and line-line voltages are all
measured. The voltage displayed is either
fixed on one voltage or allowed to scroll
automatically between all six voltages (RN,
SN, TN, RS, ST, and TR). The ESC push
button is used to switch between the two
display modes.
Statuses page that shows the status of each power source.
Display
Notes
Refer to section 2.3 for the available status
displayed
Separate page for each power source showing the status, contactor state, scrolling voltages,
frequency, currents and power in KW.
Display
Notes
The ESC push button is used to start/stop
the voltages scrolling.
Long press on the Select push button for 3
seconds resets the occurring fault.
Page showing the running hours for each generator and The Omega operating mode currently
selected.
Display
Summary page showing the Omega type, installation type, serial number, H/W version, S/W version,
revision number, date and time.
Display
2. FRONT
PANEL
DESCRIPTION

Micro SD card page showing the SD card status, data consumption and last format date.
Display
Ethernet page showing the Site ID, the Ethernet S/W version, revision number and the
communication state.
Display
The UP and Down push buttons are used to scroll between the above pages. To access the parameters
menu, Press and release the Select push button.
2.1.2 SYMBOLS DESCRIPTIONS
Symbol
Description
Generator is off.
When blinking, it indicates that the generator is requested to start/stop or it is
running with an anomaly or/and no valid OK feedback.
When On, it indicates that the generator supply is within the acceptable limits,
the phases are all present and in the right sequence, and the OK signal is
active.
Mains power source is absent.
When blinking, it indicates that the Mains power source is detected but with
no valid measurements or/and wrong phase sequence.
When On, it indicates that the Mains supply is within the acceptable limits, the
phases are all present and in the right sequence.
Generator is in a faulty status with no start order, Fault reset is needed.
Generator Failed to start and the start order is active (hold start is enabled).
Order to disengage contactor is given.
Order to engage contactor is given.
The exclamation mark blinks to indicate that Order to disengage contactor is
given but the contactor feedback is active.
The exclamation mark blinks to indicate that Order to engage contactor is
given but the contactor feedback is inactive.
2. FRONT
PANEL
DESCRIPTION

2.2 FRONT PANEL LEDS
Five Leds used to indicate the operating mode.
Seven input Leds used to indicate the status of the inputs.
2.3 DETECTED AND SIGNALED FAULTS
2.3.1 GENSET STATUSES
Status
Display
Abbreviation
Standby ( Not ready)
Standby
Standby
Ready
Ready
Ready
Counting Response delay to give start order
Response
RSP
Start order is given (ST.Gx engaged)
Starting
Starting
Gx OK signal active with No AC signals from genset
OK-WaitingAC
OK-NoAC
Counting Warm-up delay to engage load
Warm Up
WUp
Engaging load (CGx Engaged) with No CGx F/B detected yet
Engaging
Engaging
Load engaged (CGx Engaged with CGx F/B detected) with No CG F/B
detected yet
Engaged
Engaged
Feeding the load (CGx Engaged with CGx F/B & CG F/B detected )
Feeding Load
Feeding
Disengaging the load (CGx Disengaged) with CGx and/or CG F/B still
detected
Disengaging
Diseng.
Counting Cooling delay to disengage start order
Cooling
COL
Shutting down ( Start order released)
Shutting
SDN
2.3.2 GENSET FAULTS
Fault
Display
Abbreviation
Start Fail caused by absence of Gx OK signal
StFail-NoOK
StF.NoOK
Start Fail caused by Failure of G contactor
StFail-CG-F
StF.CG-F
Start Fail caused by Failure of Gx contactor
StFailCGx-F
StF.CGxF
Start Fail caused by Absence of AC signals
StFail-NoAC
StF.NoAC
Start Fail caused by High voltage
StFail-HiV.
StF.HiV
Start Fail caused by Low voltage
StFail-LoV.
StF.LoV
Start Fail caused by High frequency
StFail-HiF.
StF.HiF
Start Fail caused by Low frequency
StFail-LoF.
StF.LoF
Start Fail caused by wrong phase sequence
StFail-Seq-F
StF.Seq
Start Fail caused by G contactor jam
StFail-CGJam
StF.CG-J
Start Fail caused by Mains contactor jam
StFail-CMJam
StF.CM-J
Start Fail caused by the other generator contactor jam
StFail-CGyJam
StF.CGyJ
Start Fail caused by the expire of start failure delay
StFail-Time
StF.Time
Gx OK Signal lost after generator has turned on
OK Failure
OK Fail
Global contactor failure
CG Fail
CG Fail
CGx Contactor failure
CGx Fail
CGx Fail
One of the three-phase voltages goes above the over voltage limits set
by OVolt(L-N) for a delay of OVolt del.
Hi Voltage
Hi Volt.
One of the three-phase voltages goes below the under voltage limits
set by UVolt(L-N) for a delay of UVolt del.
Lo Voltage
Lo Volt.
The frequency goes above the value set in Over Freq. for a delay of
OFreq del.
Hi Freq.
Hi Freq.
The frequency goes below the value set in Under Freq. for a delay of
UFreq del.
Lo Freq.
Lo Freq.
The phases are reversed
Wrong Seq.
Seq.Fail
The load exceeds the value set by Overload % for a delay of Overld del
Over Load
Over Ld.
2. FRONT
PANEL
DESCRIPTION

2.3.3 UTILITY STATUSES
Status
Display
Abbreviation
Standby (not ready)
Standby
Standby
Ready
Ready
Ready
Utility Absent
Absent
Absent
Counting Restoring delay
Restoring
Rest.
Engaging load (CM engaged with No CM F/B detected yet)
Engaging
Engaging
Feeding the load (CM engaged with CM F/B detected )
Feeding Load
Feeding
Disengaging load CM Disengaged) with CM still detected
Disengaging
Diseng.
2.3.4 UTILITY FAULTS
Fault
Display
Abbreviation
Utility contactor failure
C-U Fail
CU Fail
One of the three-phase voltages goes above the over voltage limits set
by OVolt(L-N) for a delay of OVolt del.
Hi Voltage
Hi Volt.
One of the three-phase voltages goes below the under voltage limits
set by UVolt(L-N) for a delay of UVolt del.
Lo Voltage
Lo Volt.
The frequency goes above the value set in Over Freq. for a delay of
OFreq del.
Hi Freq.
Hi Freq.
The frequency goes below the value set in Under Freq. for a delay of
UFreq del.
Lo Freq.
Lo Freq.
The phases are reversed
Wrong Seq.
Seq.Fail
2. FRONT
PANEL
DESCRIPTION

2.4 MENU DESCRIPTION
2.4.1 PASSWORD
A password is required for accessing the menu. The password consists of 4 digits. Two passwords can access
the menu. The first is provided by S. & A.S. Co. Ltd. and is referred to as client password. This password can
only be changed by S. & A.S. Co. Ltd. The second password is referred to as the user password. The user
password can be modified in the menu. The client password accesses all the items in the menu whereas the
user password is denied access to some of the menu items.
2.4.2 ACCESSING THE MENU
Follow the steps described below to access the menu:
1. Press the Select push button once. You will be prompted to enter a four-digit code. The default
password is 0000.
2. Use the UP and DOWN push buttons to scroll to the desired number.
3. Press the Select push button. "*" replaces the first digit.
4. Repeat steps 2 and 3 until all four digits are entered.
5. If the entered password is valid, the user will have access to the menu below for 10 minutes without
the need to re-enter the password for every menu access.
While in the menu, if no push buttons are pressed for 25 seconds or if the ESC button is pressed, the
system will automatically exit the menu.
While editing a parameter in the menu, if no push buttons are pressed for 10 seconds or if the ESC
button is pressed, the system will automatically exit the edit mode.
While in the menu, The UP/DOWN push buttons are used to scroll up/down the submenus or the
parameters list. The Select push button accesses the submenu or edits the parameter.
While editing a parameter in the menu, The UP/DOWN push buttons are used to
increment/decrement the parameter value. The Select push button saves the changes done on the
parameter edited.
2.4.3 SUBMENUS
What you see on the display
Description
Visibility Condition
Configuration
Configuration sub menu
N/A
Genset
Generator sub menu
N/A
Utility
Utility sub menu
For MGG & MG installation type
Modbus
Modbus sub menu
Modbus Hardware Available
Ethernet
Ethernet sub menu
Ethernet Hardware Available
LCD Display
LCD Display sub menu
N/A
SD Card
SD Card sub menu
SD Card Hardware Available
View Faults
View faults
At least one fault exists
Erase Faults
Erase faults
At least one fault exists
2. FRONT
PANEL
DESCRIPTION

2.4.4 CONFIGURATION SUBMENU
What you see on the
display
Description
Visibility Condition
Range
Default
Value
Omega Type
Omega Type
Client P/W
ATS: for 2 gensets of the same
rating
ATSO: for 2 gensets of different
rating
N/A
ATS Type
ATS Type
Client P/W
Cont: for contactor outputs
MCB: for motorized circuit breakers
MCO: for motorized changeover
switches
Cont
Inst. Type
Installation Type
Client P/W
MGG: 1 Mains and 2 gensets
MG: 1 Mains and 1 genset
GG: 2 gensets
MGG
Company
Company Name
Client P/W
12 Characters long
S.& A.S. LTD
User P/W
User password
N/A
0000 to 9999
N/A
Date
Date
N/A
N/A
N/A
Time
Time
N/A
N/A
N/A
2.4.5 GENSET SUBMENU
What you see on
the display
Description
Visibility Condition
Range
Default
Value
Response
Response delay
N/A
0 to 999 sec
5 sec
Flt bypass
Fault bypass delay
N/A
0 to 999 sec
15 sec
Warm-up
Warming up delay
N/A
0 to (Start Fail - Transfer dead time -
10) sec
10 sec
Off delay
Off delay
“Inst. Type” set to GG
0 to 999 sec
10 sec
Transfer
Transfer dead time
delay
N/A
0 to (Start Fail –Warm up - 10) sec
0 sec
Cooling
Cooling down delay
N/A
0 to 999 sec
30 sec
Over Freq
Over frequency
N/A
N, 10 Hz to 70 Hz
55 Hz
OFreq del.
Over frequency delay
N/A
0 to 999 sec
2 sec
Under Freq
Under frequency
N/A
N, 10 Hz to 70 Hz
45 Hz
UFreq del.
Under frequency
delay
N/A
0 to 999 sec
2 sec
OVolt(L-N)
Over voltage (Line-
Neutral)
N/A
N, 1 to 260 V
240 V
OVolt del.
Over voltage delay
N/A
0 to 999 sec
3 sec
UVolt(L-N)
Under voltage (Line-
Neutral)
N/A
N, 1 to 260 V
180 V
UVolt del.
Under voltage delay
N/A
0 to 999 sec
5 sec
G-Seq Test
Generator phase
sequence test
N/A
N: Phase sequence test disabled
Y: Phase sequence test enabled
N
Start Fail
Start fail delay
N/A
(Warm up +Transfer dead time+10)
to 999 sec
45 sec
Hold Start
Hold Start feature
Client P/W
N: Start order released after start
failure
Y: Start order held after start failure
Y
2. FRONT
PANEL
DESCRIPTION

What you see on
the display
Description
Visibility Condition
Range
Default
Value
Time Switch
Time Switch
operation
N/A
N: Operation disabled
Y: Operation enabled
N
Ready @
Gensets ready at time
“Time Switch” set to Y
N/A
8:00 AM
Stdby @
Gensets standby at
time
“Time Switch” set to Y
N/A
5:00 PM
All Days Ready
Gensets ready feature
N/A
N: Have to set the gensets ready
days
Y: Gensets ready all days of the
week
Y
Sunday
Gensets readiness on
Sunday
“All Days Ready” set to N
N: Genset not ready on Sunday
Y: Genset ready on Sunday
N
Monday
Gensets readiness on
Monday
“All Days Ready” set to N
N: Genset not ready on Monday
N
Tuesday
Gensets readiness on
Tuesday
“All Days Ready” set to N
Y: Genset ready on Tuesday
N
Wednesday
Gensets readiness on
Wednesday
“All Days Ready” set to N
N: Genset not ready on
Wednesday
N
Thursday
Gensets readiness on
Thursday
“All Days Ready” set to N
Y: Genset ready on Thursday
N
Friday
Gensets readiness on
Friday
“All Days Ready” set to N
N: Genset not ready on Friday
N
Saturday
Gensets readiness on
Saturday
“All Days Ready” set to N
Y: Genset ready on Saturday
N
Weekly Ex.
Weekly Exercising
N/A
N/Y
N
Alternate hrs
Alternate number of
hours
“Omega Type” set to ATS
G1: Highest priority to G1
G2: Highest priority to G2
1 to 99 hours
4 hours
Req Priority
Request Priority
“Omega Type” set to
ATSO
G1: Highest priority to G1
G2: Highest priority to G2
Ld (MGG only): Load dependent
priority
G2
G1 hours
G1 running hours
Client P/W
0 to 999999 hours
0 hours
G2 hours
G2 running hours
“Inst. Type” set to MGG or
GG
Client P/W
0 to 999999 hours
0 hours
R.C.
Remote control
configuration
N/A
Gensets Rdy: Gensets are ready
U Present: Simulate utility presence
v1.0 Compt.: Compatible with
Omega v1.0
U Present
NB Phases
Gensets connection
N/A
1PH: 1 phase
3PH: 3 phases
3PH
CT ratio /5
Current transformer
ratio
N/A
N, 1 to 9999
100
Overload %
Gensets Overload %
of the current
transformer
“Omega Type” set to ATS
0 to 100%
90%
Overld del
Gensets Overload
delay
“Omega Type” set to ATS
0 to 999 seconds
10
G1 Overload %
G1 Overload % of the
current transformer
“Omega Type” set to
ATSO
0 to 100%
90
G1 Overld del
G1 Overload delay
“Omega Type” set to
ATSO
0 to 999 seconds
10

2.4.6 UTILITY SUBMENU
What you see on
the display
Description
Visibility Condition
Range
Default
Value
Mains Rest.
Mains Restoration
delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
10 sec
Over Freq
Over frequency
“Inst. Type” set to MGG or
MG
N, 10 Hz to 70 Hz
55 Hz
OFreq del
Over frequency delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
2 sec
Under Freq
Under frequency
“Inst. Type” set to MGG or
MG
N, 10 Hz to 70 Hz
45
UFreq del
Under frequency
delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
2 sec
OVolt(L-N)
Over voltage (Line-
Neutral)
“Inst. Type” set to MGG or
MG
N, 1 to 260 V
240 V
OVolt del
Over voltage delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
3 sec
UVolt(L-N)
Under voltage (Line-
Neutral)
“Inst. Type” set to MGG or
MG
N, 1 to 260 V
180 V
UVolt del
Under voltage delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
5 sec
U-Seq Test
Utility phase sequence
test
“Inst. Type” set to MGG or
MG
N: Phase sequence test disabled
Y: Phase sequence test enabled
N
NB Phases
Utility connection
“Inst. Type” set to MGG or
MG
1PH: 1 phase
3PH: 3 phases
3PH
What you see on
the display
Description
Visibility Condition
Range
Default
Value
G2 Overload %
G2 Overload % of the
current transformer
“Omega Type” set to
ATSO
0 to 100%
90
G2 Overld del
G2 Overload delay
“Omega Type” set to
ATSO
0 to 999 seconds
10
G1 Max Load %
G1 Maximum Load %
of the current
transformer
“Omega Type” set to
ATSO
0 to 100%
50
G1 Maxld del
G1 Maximum load
delay
“Omega Type” set to
ATSO
0 sec to 99 min
10sec
G2 Min Load %
G2 Minimum Load %
of the current
transformer
“Omega Type” set to
ATSO
0 to 100%
30
G2 Minld del
G2 Minimum load
delay
“Omega Type” set to
ATSO
0 sec to 99 min
10sec
Recycle reset
Recycle after Utility
reset
N/A
N: No automatic reset is done after
a genset fault
Y: Automatic reset is done on faulty
genset when Mains is established
Y
Gx Mode
G1/G2 Mode
N/A
OnWUAbs: On When Utility is
Absent
AlwaysOn: Always On
OnWUAbs
2. FRONT
PANEL
DESCRIPTION

2.4.7 MODBUS SUBMENU
What you see on
the display
Description
Visibility Condition
Range
Default
Value
Modbus
Modbus feature
Modbus HW available
N: Modbus disabled
Y: Modbus enabled
Y
Slave ID
Slave node ID
“Modbus” set to Y
1 to 247
20
Baudrate
Baud rate
“Modbus” set to Y
9600
14400
19200
28800
38400
56000
57600
115200
9600
Parity
Parity
“Modbus” set to Y
None
Odd
Even
None
Stop Bits
Stop Bits
“Modbus” set to Y
1
1.5
2
1
Mode
Communication Mode
“Modbus” set to Y
RTU
ASC
RTU
2.4.8 ETHERNET SUBMENU
What you see on
the display
Description
Visibility Condition
Range
Default
Value
Ethernet
Ethernet feature
Ethernet HW available
N: Ethernet disabled
Y: Ethernet enabled
Y
DHCP
DHCP
“Ethernet” set to Y
N: DHCP disabled
Y:DHCP enabled
Y
SITEID
SITE ID
“Ethernet” set to Y
6 Characters long
XXXXXX
IP ADDRESS
IP ADDRESS
“Ethernet” set to Y “DHCP”
set to N
N/A
192.168.0.2
1
SUBNET MASK
SUBNET MASK
“Ethernet” set to Y “DHCP”
set to N
N/A
255.255.255
.0
GATEWAY
GATEWAY
“Ethernet” set to Y “DHCP”
set to N
N/A
192.168.0.1
P.ServerName
Primary server name
“Ethernet” set to Y
30 Characters long
www.sascon
trollers.com
S.ServerName
Secondary server
name
“Ethernet” set to Y
30 Characters long
www.sascon
trollers.com
2. FRONT
PANEL
DESCRIPTION

2.4.9 LCD DISPLAY SUBMENU
What you see on
the display
Description
Visibility Condition
Range
Default
Value
LCD Contrast
LCD Contrast
N/A
0 to 30
12
LCD Backlight
LCD Backlight
percentage
N/A
0 to 100 %
70 %
2.4.10 SD CARD SUBMENU
What you see on
the display
Description
Visibility Condition
Range
Default
Value
DSR
SD Data sampling rate
SD card available
N, 1 sec to 24 hours
20 sec
2.4.11 MENU MAPPING WITH PREVIOUS VERSIONS
OMEGA v1.0/1.1 PARAMETER NAME
OMEGA v1.2 PARAMETER NAME
OMEGA v1.2 SUBMENU
Response
Response
GENSET SUBMENU
Flt bypass
Flt bypass
GENSET SUBMENU
Warm-up
Warm-up
GENSET SUBMENU
Mains Rest.
Mains Rest.
GENSET SUBMENU
Cooling
Cooling
GENSET SUBMENU
U-OverFrq. Hz
Over Freq
UTILITY SUBMENU
U-OvrFrq dly
OFreq del.
UTILITY SUBMENU
U-UndrFrq. Hz
Under Freq
UTILITY SUBMENU
U-UndrFrqdly
UFreq del.
UTILITY SUBMENU
U-OverVolt. V
OVolt(L-N)
UTILITY SUBMENU
U-OvrVlt.dly
OVolt del.
UTILITY SUBMENU
U-UnderVolt. V
UVolt(L-N)
UTILITY SUBMENU
U-UndrVltdly
UVolt del.
UTILITY SUBMENU
G-OverFrq. Hz
Over Freq
GENSET SUBMENU
G-OvrFrq dly
OFreq del.
GENSET SUBMENU
G-UndrFrq. Hz
Under Freq
GENSET SUBMENU
G-UndrFrqdly
UFreq del.
GENSET SUBMENU
G-OverVolt. V
OVolt(L-N)
GENSET SUBMENU
G-OvrVlt.dly
OVolt del.
GENSET SUBMENU
G-UnderVolt. V
UVolt(L-N)
GENSET SUBMENU
G-UndrVltdly
UVolt del.
GENSET SUBMENU
CT ratio /5
CT ratio /5
GENSET SUBMENU
Overload %
Overload %
GENSET SUBMENU
Overld dly
Overld del
GENSET SUBMENU
Start Fail
Start Fail
GENSET SUBMENU
Xfr deadtim
Transfer
GENSET SUBMENU
Hold Start
Hold Start
GENSET SUBMENU
Time switch
Time Switch
GENSET SUBMENU
G1 hh:mmy hh:mmy
G1 Rdy@, G1 Stby@
GENSET SUBMENU
G2 hh:mmy hh:mmy
G2 Rdy@, G2 Stby@
GENSET SUBMENU
2. FRONT
PANEL
DESCRIPTION

2.5 PARAMETERS DESCRIPTION
The over/under frequency/voltage could be disabled by setting the corresponding parameter in the menu to
'N'.
When transferring load from one generator to another, the transfer dead time and the warm up delay are
counted. To avoid getting a fault on the generator, the sum of these delays should not exceed the start fail
delay of the generator. Thus, the “Start Fail”delay should never fall below (“Transfer” + “Warm-up”+10sec).
When “Hold Start”feature is enabled, the start signal is held on the generator after a start failure or an OK
failure fault occurs. Thus, when this fault no longer exists, the generator starts without user intervention.
When it is disabled, the start signal is removed and a manual reset of the fault is required to resume use of
the specific generator.
For ATS, the “Alternate hrs” parameter indicates the number of hours that a generator must run before the
other generator is requested. If set to G1, G1 is given priority and if set to G2, G2 is given priority.
The “Weekly Ex.”parameter enables/disables the weekly exerciser. When enabled, any generator that did
not operate between Sunday and Friday would be started on Saturday at 8:00 am for half an hour. If both
were not used during the whole week, they will be started on Saturday at 8:00AM in sequence and each for
half an hour.
The “Time Switch” manages the operating time of the genset daily. Two parameters control the daily time
switch: “Ready @” and “Stdby @”. “Ready @” sets the time at which the genset becomes ready. “Stdby @” sets
the time at which the genset goes to standby mode. If genset is required to be in ready mode all day then set
“Time Switch” to N.
The “All Days Ready”manages the operating time of the genset weekly. Under “All Days Ready”, if Y is
selected then the genset will be ready all week long. Otherwise, the genset will be ready only in days set to Y.
It will be in standby in days set to N.
As a result, the genset will be ready during the hours set by “Ready @” and “Stdby @” only on days set to Y
under Rdyday.
When “R.C.” is set to “Gensets Rdy”, when remote control is active and genset in ready mode, following a
mains failure, the genset is started. Otherwise, the genset is stopped.
When “R.C.” is set to “U Present”, when remote control is active and genset in ready mode, the genset is
stopped.
When “R.C.” is set to “v1.0 Compt.”, the remote control input will be at the place of CM F/B as in
Omega v1.0 & v1.1
OMEGA v1.0/1.1 PARAMETER NAME
OMEGA v1.2 PARAMETER NAME
OMEGA v1.2 SUBMENU
G1Alternat hrs
G1 Alt. hrs
GENSET SUBMENU
G2Alternat hrs
G2 Alt. hrs
GENSET SUBMENU
W.Exercise
Weekly Ex.
GENSET SUBMENU
ATS Type
ATS Type
CONFIGURATION SUBMENU
Installat.
Inst. Type
CONFIGURATION SUBMENU
LCD Contrast
LCD Contrast
LCD DISPLAY SUBMENU
Co.
Company
CONFIGURATION SUBMENU
Time
Time
CONFIGURATION SUBMENU
Date
Date
CONFIGURATION SUBMENU
User P/W
User P/W
CONFIGURATION SUBMENU
G1 hours
G1 hours
GENSET SUBMENU
G2 hours
G2 hours
GENSET SUBMENU
2. FRONT
PANEL
DESCRIPTION

2.6 MODBUS REGISTERS
Name
type
Address
Size
Access
Description
Omega Type
input register
30001
1
R
Omega Type
0 = ATS
1 = ATSO
Hardware Version
input register
30002
1
R
Hardware Version
Software Version
input register
30003
1
R
Software Version
Revision number
input register
30004
1
R
Revision number
Modbus Status
input register
30005
1
R
Modbus status: 0(normal), 1(malfunction)
Operating Mode
input register
30006
1
R
Operating Mode:
1 = Auto Mode
2 = Mains-Only Mode
3 = G1-Only Mode
4 = G2-Only Mode
Status
input register
30010 Utility
1
R
0 = Utility Standby
1 = Utility Ready
2 = Utility Absent
3 = Utility Counting restoring delay
4 = Utility Engaging
5 = Utility Feeding Load
6 = Utility Disengaging
7 = C-U Fail
8 = Utility High Voltage
9 = Utility Low Voltage
10 = Utility High Frequency
11 = Utility Low Frequency
12 = Utility Wrong Sequence
G1 Status
input register
30011
1
R
13 = Engine Standby
14 = Engine Ready
15 = Engine Counting response delay
16 = Engine Starting
17 = Engine OK-WaitingAC
18 = Engine Warming Up
19 = Engine Engaging load
20 = Engine Cooling down
21 = Engine Shutting down
22 = Engine's Contactor Engaged
23 = Engine Feeding Load
24 = Engine Disengaging load
25 = Engine OK Failure
26 = Engine - CG Fail
27 = Engine - CGx Fail
28 = Engine - High Voltage
29 = Engine - Low Voltage
30 = Engine - High Frequency
31 = Engine - Low Frequency
32 = Engine - Wrong Sequence
33 = Engine - Over Load
34 = Engine - Start Fail-NoOK
35 = Engine - Start Fail-CG-F
36 = Engine - Start FailCGx-F
37 = Engine - Start Fail-NoAC
38 = Engine - Start Fail-High Voltage
39 = Engine - Start Fail-Low Voltage
40 = Engine - Start Fail-High Frequency
41 = Engine - Start Fail-Low Frequency
42 = Engine - Start Fail-Seq-Fail
43 = Engine - Start Fail-CGJam
44 = Start Fail-CMJam
45 = Engine - Start Fail-CGyJam
46 = Engine - Start Fail-Time
G2 Status
input register
30012
1
R
Same as G1 Status
2. FRONT
PANEL
DESCRIPTION

Name
type
Address
Size
Access
Description
G1 Exercising status
input register
30014
1
R
0 = Not Exercising
1 = Exercising Needed
2 = Exercising requested
3 = Exercising stopped
G2 Exercising status
input register
30015
1
R
0 = Not Exercising
1 = Exercising Needed
2 = Exercising requested
3 = Exercising stopped
Utility RN voltage
input register
30016
1
R
Utility phase R-Neutral voltage in V
Utility SN voltage
input register
30017
1
R
Utility phase S-Neutral voltage in V
Utility TN voltage
input register
30018
1
R
Utility phase T-Neutral voltage in V
Utility RS voltage
input register
30019
1
R
Utility phase R to phase S voltage in V
Utility ST voltage
input register
30020
1
R
Utility phase S to phase T voltage in V
Utility TR voltage
input register
30021
1
R
Utility phase T to phase R voltage in V
G1 RN voltage
input register
30022
1
R
G1 phase R - Neutral voltage in V
G1 SN voltage
input register
30023
1
R
G1 phase S - Neutral voltage in V
G1 TN voltage
input register
30024
1
R
G1 phase T - Neutral voltage in V
G1 RS voltage
input register
30025
1
R
G1 phase R to phase S voltage in V
G1 ST voltage
input register
30026
1
R
G1 phase S to phase T voltage in V
G1 TR voltage
input register
30027
1
R
G1 phase T to phase R voltage in V
G2 RN voltage
input register
30028
1
R
G2 phase R - Neutral voltage in V
G2 SN voltage
input register
30029
1
R
G2 phase S - Neutral voltage in V
G2 TN voltage
input register
30030
1
R
G2 phase T - Neutral voltage in V
G2 RS voltage
input register
30031
1
R
G2 phase R to phase S voltage in V
G2 ST voltage
input register
30032
1
R
G2 phase S to phase T voltage in V
G2 TR voltage
input register
30033
1
R
G2 phase T to phase R voltage in V
Utility frequency
input register
30034
1
R
Utility frequency in Hz *10 format (i.e. if this register
value is 504 this means that the frequency is 50.4Hz)
G1 frequency
input register
30035
1
R
G1 frequency in Hz *10 format (i.e. if this register
value is 504 this means that the frequency is 50.4Hz)
G2 frequency
input register
30036
1
R
G2 frequency in Hz *10 format (i.e. if this register
value is 504 this means that the frequency is 50.4Hz)
RN current
input register
30037
1
R
Line R current in A *10 format (i.e. if this register
value is 125 this means that the current is 12.5A)
SN current
input register
30038
1
R
Line S current in A *10 format (i.e. if this register
value is 125 this means that the current is 12.5A)
TN current
input register
30039
1
R
Line T current in A *10 format (i.e. if this register
value is 125 this means that the current is 12.5A)
Power (KW)
input register
30040
1
R
Power in KW
Digital Inputs
input register
30041
1
R
Omega Digital Inputs
Each bit represents an input (first input is the LSB)
Bit0: IP1
Bit1: IP2
...
Bit6: IP7
Digital Outputs
input register
30042
1
R
Omega Digital Outputs
Each bit represents an output (first output is the LSB)
Bit0: OP1
Bit1: OP2
...
Bit7: OP8
Operating Mode
holding
register
40001
1
R/W
Operating Mode:
1 = Auto Mode
2 = Mains-Only Mode
3 = G1-Only Mode
4 = G2-Only Mode
G1 Hourmeter
holding
register
40002
2
R/W
G1 Hourmeter
G2 Hourmeter
holding
register
40004
2
R/W
G2 Hourmeter
Other manuals for OMEGA-ATS
1
This manual suits for next models
3
Table of contents
Other S.& A.S. Controllers manuals
Popular Controllers manuals by other brands

Aruba Networks
Aruba Networks 7030-MNT-19 installation guide

Axel Larsson
Axel Larsson AL 79-045U Installation, Maintenance and Operating Instruction Manual

Johnson Controls
Johnson Controls Metasys FEC Series installation guide

Danfoss
Danfoss EKD 316 manual

Siemens
Siemens Simatic S7-1500 manual

HighPoint
HighPoint RocketRAID 174x installation manual