SafeCom T-Former Series User manual

Power
Safecom T-Former Series
Stabilized sine voltage technology (Patent P)
Modular UPS & Non –standby Power Supplies
Safecom TFPS Series
Installation Manual
JUN-2011
SAFECOM Patent.P
1

Table of Contents
Page 3: About T-former Technology & advantages.
Page 4: Safety Instructions:
Page 5 : overview.
Page 6: Specification.
Page 7 : Technology.
Page 8 : Inside view.
Page 9 : Voltage configuration
Page 10: Bottom view –Connecting panel.
Page 11: Back View bracket open & Mounting template.
Page 12: back View bracket locked.
Page 13 : Safecom T-former P.S ordering information.
Page 14 : Connecting Power Cable to T-former AC OUTPUT.
Page 15 : Troubleshooting and Repair
2

T-Former (patent P) - High efficiency Power supply
•Lower Operating Costs - Saves at least 5% energy compared to Ferro systems
•Lower Capital Cost per unit - compared to traditional Ferro-resonant devices.
•Longer Life -Unique technology enables almost unlimited lifetime.
•No Noise, No Vibration - No environmental disturbance when installed on or near
buildings
•Slow Start prevents fall of current breakers after power-out or during ignition.
•Automatic overload protection.
EFFICIENCY : T-Former Vs traditional Ferro
20
30
40
50
60
70
80
90
100
010 20 30 40 50 60 70 80 90 100
Efficiency (%)
Load Pout (%)
T-former P.S
Common Ferro
pure sine wave stabilizer technology
3

Safety Instructions
Review the installation manual before proceeding.
If there is any questions regarding safe installation or operation &
performance please contact us support@safecom.tv .
Prior to any handling, the power supply is required to be disconnected
from the Mains.
Only an experienced and authorized technician or electrician who is
qualified to work on the electrical grid while taking necessary
precautions that comply with the electrical code will do handling.
Before Installation:
Make sure that P.S input voltage configuration matches the standard
utility voltage level
Make sure that P.S output voltage configuration matches the CATV
voltage requirements.
Recheck circuit breaker and earth leakage circuit breaker (ELCB).
Connect grounding cable between P.S grounding to utility grounding
point.
Safety:
Prior to installation or removal recheck that utility circuit breaker is OFF
and no voltage at the P.S.
Only licensed electrician is required to install P.S.
Ensure all cable dry and wet protected.
4

Overview:
T-Former is pure stabilizer sine wave P.S with the highest- efficiency, and most
reliable technology, specifically developed for the advanced operation of line
amplifiers in CATV distribution systems. With around double the lifetime of
legacy Ferro-resonant products, delivering energy savings of at least 5% energy
compared to standard systems. Its modular optional design enables upgrade
of the T-Former to UPS by adding compatible ONLINE DC-AC inverter
/Charger . That helps operators reduce network expenditure at capital as well
as operational levels.
Thanks to its patent-pending sine wave
stabilizer technology, the T-Former's
advanced electronic controller
automatically monitors and compensates
for any changes to line voltage -
eliminating negative Inrush current side
effects resulting from utility power
recovery. In addition, the T-Former
operates in complete silence - solving
noise and vibration problems inherent in
existing products. This is increasingly
important in highly populated areas
where power supply devices are often
mounted nearby the buildings. T-Former
is designed to work at a wide range of
temperatures and humidity without
maintenance, at full power capacity.
Safecom's T-Formers undergo rigorous
quality testing - with fully 100% of the
units repeatedly tested.
5

Model
SC-DTFPS 1050-60EO/I
Electrical
Input Voltage Taps (Vac)
230±15% EUROPE
Input Frequency (Hz)
50/60
Input Current (A)
< 5.5A
Input inrush current
< 10 A In single pulse of 5ms
Input Power Factor
0.95 at full load
Output Voltage Taps (Vac)
60, 66, 72V -25A (87V -25A )
Total Output Current (A)
25A (15A max each port)
Short circuit time response (ms)
<10
Recovery safety time delay (sec)
> 3
Output Power (VA)
1050
Load Regulation (%)
< 2%
Output Protection Fuse
T15A
Efficiency (%)
95% at full load
Mechanical
Dimensions ( L , W , H ) mm
375 x 220 x 215
Weight (Kg/lbs)
20 kg
Housing Finish
White zinc / epoxy plating
Environment
Operating Temperature
-20ºC ÷+60ºC
Storage Temperature
-20ºC ÷+70ºC
Humidity
0 ÷100% non condensing
Standard Features
Power Mains Cable
√
Mains Transients Protection
√
Quick Connection Output Coax socket
√
Output Fuse
√
Output Voltage Test Points
√
Output Current Measurement Loop
√
Power Indication Green LED
√
Optional Features
Output Screw Terminals
√
DC/AC inverter for UPS
√
6

•Technology
•The TFPS series, non-standby with the modular UPS option utilizes novel and
patented P AC-AC variable ratio transformation, providing ultimate voltage
regulation and pure sine voltage output at all loads. Input and output
voltages are completely isolated. Line conditioning allows for changing gears
at 0 time (“zero crossing”).This smooth online transformation between gears
provides clean AC pure sine voltage without any RF noise.
•An additional feature of the T-Former Novel P.S. is its Soft Startup, addressing
the most serious problem of Ferro-based P.S: the inrush current. This
innovative solution controls the current level during start up and preventing any
possibility of circuit breaker down during startup or utility power interruption.
•In addition electronic over load protection protecting and the network and
minimize fuse blow when momentary sort circuit occurred
•Safecom T-Former P.S has the most efficient technology with almost 95% efficacy at
wide range of load. It saves electricity and keeps cold temperature of transformer
and electronic parts make P.S most reliable for un-limited life time
•No like noise and vibrating Ferro P.S the new T-former P.S is completely silence with
no noise and vibration enabling to install nearby premises houses or very quite
places without interfere the residential area.
Block Diagram T-Former P.S
Multi Outputs
60, 66 , 72 / 87Vac
15A
Utility power
120 V 60Hz
230 V 50Hz
Multi outputs
transformer
Outputs
Control
Board
Start
Control
Board
7

Inside view : T-former outdoor 87V -15A
8

Voltage configuration
Safecom TF-PS serial offer input & output voltage level flexibly. Technician can
easily configure the optimal input voltage level and recommended output
voltage level for supplying power to the network.
1) Ensure utility power is OFF when changing voltage configuration at input &
output.
2) Changing is setting is by moving input & output cables from one port to
another. Cable seizure is by very strong spring. To release seizure simply need to
press the lower point by screw driver.
3) This configuration insure reliable connection for life without any possibly of lost
connection.
9

Bottom view
Output
Testing point
Clamp Meter
current test
Power output
Quick type RF
connector
Output
indicator
LED Green
/Red
Ground
Connector
10

Installing an TFPS –Outdoor
The SC-TFPS outdoor series non-standby power supplies are designed to mount by
separate bracket on a wall or pole.
When installing an TF-PS on a pole an approved mounting strap must go through
the mounting slots of the back bracket. When installing on the wall use two >8
mm screws to band the bracket on the wall.
After bracket is will well banded on the wall hang PS on the bracket and tight the
screw at the bottom of P.S for locking P.S.
Back View
Hanging Bracket Closed Cabinet Installed with special bracket
for hanging or shelf-lain mounting
Hanging
Bracket
Mounting
slot
Mounting
slot
Screw hole
Locking
Screw
Hanging Bracket
Banded by
mounting strap
Hanging Bracket
Banded by screws
to the wall
11

Back view TF-PS Bracket locked
12

SC TFPS
“M” : Monitoring
“I” : indoor housing
“O” :outdoor housing
“E” :Europe standard 230V +/- 15% 50Hz
“U” :USA standard 120V +/- 15% 60Hz
“2200” : 2200 VA (rms)
“1800” : 1800 VA (rms)
“1300” : 1300 VA (rms)
“1080” : 1080 VA (rms)
“ 300” : 300 VA (rms)
“D” : Dual output port.
“S” : Single output port.
“M” : Mini P.S.
“60” : 60V CATV voltage standard.
“90” : 87V CATV voltage standard.
Safecom T-former P.S ordering information
Model
Output
Port
Output
Voltage
Output
Current [A]
Input
Voltage[V]
Frequency
[Hz]
Housing
Monitoring
SC S TFPS 1080 60UI
Single
66,72
15
110,120
45 ÷65
Indoor
-
SC S TFPS 1080 60UO
Single
66,72
15
110,120
45 ÷65
Outdoor
-
SC D TFPS 1800 60UI
Dual
66,72
25
110,120
45 ÷65
indoor
-
SC D TFPS 1800 60UO
Dual
66,72
25
110,120
45 ÷65
outdoor
-
SC S TFPS 1300 90UI
Single
60,75,87
15
110,120
45 ÷65
Indoor
-
SC STFPS 1300 90UO
Single
60,75,87
15
110,120
45 ÷65
Outdoor
-
SC D TFPS 2200 90UI
Dual
60,75,87
25
110,120
45 ÷65
indoor
-
SC D TFPS 2200 90UO
Dual
60,75,87
25
110,120
45 ÷65
outdoor
-
SC D TFPS 2200 90UOM
Dual
60,75,87
25
110,120
45 ÷65
outdoor
SC S TFPS 1080 60EI
Single
66,72
15
220,230,240
45 ÷65
Indoor
-
SC S TFPS 1080 60EO
Single
66,72
15
220,230,240
45 ÷65
Outdoor
-
SC D TFPS 1800 60EI
Dual
66,72
25
220,230,240
45 ÷65
indoor
-
SC D TFPS 1800 60EO
Dual
66,72
25
220,230,240
45 ÷65
outdoor
-
SC S TFPS 1300 90EI
Single
60,75,87
15
220,230,240
45 ÷65
Indoor
-
SC STFPS 1300 90EO
Single
60,75,87
15
220,230,240
45 ÷65
Outdoor
-
SC D TFPS 2200 90EI
Dual
60,75,87
25
220,230,240
45 ÷65
indoor
-
SC D TFPS 2200 90EO
Dual
60,75,87
25
220,230,240
45 ÷65
outdoor
-
SC D TFPS 2200 90EOM
Dual
60,75,87
25
220,230,240
45 ÷65
outdoor
13

Connecting Power Cable to
T-former AC OUTPUT
All Safecom power supplies model has high current output quick
type connector without seizure screw.
Simply plug in connector at the front panel.
Connection is made quickly and reliably from outside.
Beryllium, cooper contact.
10 mm
Note : The center conductor may be cut
clean to allow for complete fit.
The length of the center conductor must be
10 mm.
14

Troubleshooting and Repair
The T-former P.S designed to be the most reliable P.S that can be use for
unlimited time at most harass environmental such as heating and humidity
even at maximum load.
Power supply has slow start circuit and overload protection to prevent the
most common failure at the network such as inrush current that switch OFF
circuit breaker, or fuse blow cause by overload or sort circuit.
This guide explain the few rare symptoms possible.
15
Solution
Reason
Symptom
The network must
monitored and the failure
cause must be removed
1) P.S. was shut down
due to overload current
short-circuit or a burnt
fuses..
No Voltage at output
RED LED “ON”
Replace fuses and
restart.
2) Fuse blow
Turn on Circuit breaker.
Circuit breaker down /
No Power at the Main
No voltage at output
LED “OFF”
Check polarity of output
connection.
Neutral wire must be
connected to the
connector marked “0”.
The fuse blows out upon
activation of the power
supply
Reduce the load under
15A .
Overload protection
>15A activated
Output voltage exists but
the LED is still Red.
Other manuals for T-Former Series
1
Table of contents
Popular UPS manuals by other brands

PS Audio
PS Audio POWERPACK 1500 MKII Owner reference guide

Kohler
Kohler PowerWAVE 8000DPA RI (S2) Series user manual

Toshiba
Toshiba G9000 SERIES Installation and operation manual

Conceptronic
Conceptronic ZEUS03EP Multi Language Quick Guide

LEGRAND
LEGRAND DAKER DK Plus Series installation manual

Panduit
Panduit SmartZone user manual