SAI Canarias EA900RT G4 Series User manual

USER MANUAL
UPS ON LINE EA900RT G4 6-10 KVA (1/1)

Table of contents
Table of Contents
Important Safety Instructions....................................................................1
1 Product Description..............................................................................2
1.1
Electromagnetic Compatibility .....................................................................................2
1.2
Features......................................................................................................................3
1.3
Models ........................................................................................................................3
1.4
Appearance ................................................................................................................3
1.5
System Description .....................................................................................................6
1.6
UPS Working Mode.....................................................................................................7
1.7
Product Specifications.................................................................................................9
2 Installation ........................................................................................... 11
2.1
Unpacking and Inspection ......................................................................................... 11
2.2
Main cabinet installation............................................................................................ 11
2.3
Connect Input/Output Power .....................................................................................15
2.4
Connect External Batteries (Long Backup Model UPS) .............................................17
2.5
Connect Parallel Cables............................................................................................18
2.6
Connect Communication Cables ...............................................................................19
3 Controls and Indicators......................................................................21
4 Operation .............................................................................................27
4.1
Operation Mode ........................................................................................................27
4.2
Parallel Operation .....................................................................................................28
5 Communication ...................................................................................29
5.1
RS232 and USB Port ................................................................................................29
5.2
EPO Port...................................................................................................................29
5.3
Intelligent Cards (Optional)........................................................................................30
6 Maintenance ........................................................................................31
6.1
Battery Maintenance .................................................................................................31
6.2
Battery Disposal........................................................................................................31
6.3
Battery Replacement Procedures..............................................................................32
6.4
Precaution.................................................................................................................32
6.5
Checking UPS Status................................................................................................32
7 Troubleshooting ..................................................................................33
Annex A Parallel Setting ..........................................................................37
Annex B Battery Run Time ......................................................................37

Important safety instructions
1
Important Safety Instructions
Save these instructions
This manual contains important safety instructions. Read all safety and operating
instructions before operating the uninterruptible power systems (UPS). Adhere to all
warnings on the unit and in this manual. Follow all operating and user instructions. This
equipment can be operated by individuals without previous training.
This product designed for commercial/industrial use only. It is intended for use with lift
support and other designated “critical” devices. Maximum load must not exceed that shown
on the UPS rating label. The UPS is designed for data processing equipment. If uncertain,
consult your dealer or local representative.
This UPS is designed for use on a properly grounded (earthed), 220/230/240Vac, 50 or
60Hz supply. The factory default setting is 220Vac /50Hz. Installation instructions and
warning notices are in this manual.
The UPS 06 –10 kVA@220/230/240Vac is designed for use with a three-wire input
(L,N,G)(1/1) or a five-wire input (L1,L2,L3,N,G)
(
3/1
)
.
WARNING
The battery can present a risk of electrical shock and high short circuit current.
Following precautions should be observed before replacing the battery.
Wear rubber gloves and boots.
Remove rings, watches and other metal objects.
Use tools with insulated handles.
Do not lay tools or other metal objects on the batteries.
If the battery is damaged in any way or shows signs of leakage, contact your local
representative immediately.
Do not dispose of batteries in a fire. The batteries may explode.
Handle, transport and recycle batteries in accordance with local representative.
WARNING
Although the UPS has been designed and manufactured to ensure personal safety,
improper use can result in electrical shock or fire. To ensure safety, observe the
following precautions:
Turn off and unplug the UPS before cleaning it.
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
Never block or insert any objects into the ventilation holes or other openings of the UPS.
Do not place the UPS power cord where it might be damaged

Product description
2
1 Product Description
Congratulations on your choice of the UPS uninterruptible power system(UPS), the UPS
comes in nominal power ratings of 6-10kVA. It is designed to provide conditioned power to
computers and other sensitive electronic equipment.
This chapter gives a brief description of the UPS, including the UPS features, models,
appearance, operating principle and specification.
1.1 Electromagnetic Compatibility
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission.........IEC/EN 62040-2 Category C3
Radiated Emission............IEC/EN 62040-2 Category C3
*EMS
ESD..................................IEC/EN 61000-4-2 Level 4
RS....................................IEC/EN 61000-4-3 Level 3
EFT..................................IEC/EN 61000-4-4 Level 4
SURGE............................IEC/EN 61000-4-5 Level 4
Low Frequency Signals..............:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second
environment-installation restrictions or additional measures may be needed to
prevent disturbances.
NOTICE
:
This is a product for restricted sales distribution to informed partners. Installation restrictions
or additional measures may be needed to prevent radio interference.
Operated the UPS in an indoor enviroment only in an ambient temperature range of
0-40°C(32-104°F). Install it in a clean environment, free from moisture, flammable liquids,
gases and corrosive substance.
This UPS contains no user-serviceable parts except the internal battery pack. The
UPS“ ”push buttons do not electrically isolate internal parts. Under no circumstance
attempt to gain access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the panel indications are not in accordance with these
operating instructions or the UPS performance alters in use. Refer all faults to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the precautions. Keep unauthorized personnel away from the batteries. Proper
disposal of batteries is required. Refer to your local laws and regulations for disposal
requirement.
DO NOT CONNECT equipment that could overload the UPS or demand surge current from

Product description
3
the UPS, for example: electric drills, vacuum cleaners, hair dryer, motors and so on.
DO NOT CONNECT equipment that is life related, for example: medical equipment, elevator
and so on.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol
cleaners.
1.2 Features
The UPS features include:
Providing more high efficient AC power, compared with the previous generation
Full digital control technology based on DSP to achieve high reliability and power
function
Fan speed can be auto conditioned according to the loads, input voltage or working
mode
Digitally controlled charger current and voltage, compared with the previous generation
which is fixed in hardware
Super high power density
Failure waveform record function helps to solve problem quickly
1.3 Models
Available models are shown as Table1-1:
Table 1- 1: Models
Model Nominal Power Type
6KH 6kVA/6kW long backup model
10KH 10kVA/10kW
6KS 6kVA/6kW standard model
10KS 10kVA/10kW
1.4 Appearance
6/10KH

Product description
4
6/10KS
Fig 1- 1: Front View
6/10KH
(
1/1
)
6/10KS
(
1/1
)
6/10KH
(
3/1
)

Product description
5
6/10KS
(
3/1
)
Fig 1- 2: Rear View
As shown in Fig 1-2, the rear panel provides the following compoentes and function:
SNMP: DB9 type, used to connect monitoring software
Fans: intelligent fan speed control
Parallel port: option
RS232: DB9 type, used to connect monitoring software
EPO: NC
USB: B type, used to connect monitoring software
Battery temperature option
GND
Bypass breaker: surge proection
Terminal and cover
Battery pack

Product description
6
1.5 System Description
Fig 1- 3: UPS system
1.5.1 Transient Voltage Surge Suppression (TVSS) and EMI/FRI Filters
These UPS components provide surge protection and filter both electromagnetic
interference (EMI) and radio frequency interference (RFI). They minimize any surge or
interference present in the utility line and keep the sensitive equipment protected.
1.5.2 Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC
power to regulated DC power for use by the inverter while ensuring that the waveform of the
input current used by the UPS is near ideal. Extracting this sinewave input current achieves
two objects:
The utility power is used as efficiency as possible by the UPS.
The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the building not being
protected by the UPS.
1.5.3 Inverter
In normal operation, the inverter utilizes the DC output of the power factor correction circuit
and inverters it into precise, regulated sinewave AC power. Upon a utility power failure, the
inverter receives its required energy from the battery through the DC-to-DC converter. In
both modes of operation, the UPS inverter is on-line and continuously generating clean,
precise, regulated AC output power.

Product description
7
1.5.4 Battery Charger
The battery charger utilizes energy from the DC bus and precisely regulates it to
continuously charge the batteries. The batteries are being charged whenever the UPS is
connected to utility power.
1.5.5 DC to DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage
to the optimum operating voltage for the inverter. The converter includes boost circuit which
is also used as PFC.
1.5.6 Battery
The 6KS/10KS Standard includes value regulated, sealed lead acid, maintenance free
batteries inside. To maintain battery design life, operate the UPS in an ambient temperature
of 15-25°C.
1.5.7 Static Bypass
The UPS provides an alternate path for utility power to the connected load in the unlikely
event of a UPS malfunction. Should the UPS have an overload, over temperature or any
other failure condition, the UPS automatically transfers the connected load to bypass.
Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED. To
manually transfer the connected load from the inverter to bypass, press the “ + ”
button once.
NOTICE: The bypass power path does NOT protect the connected equipment from
disturbances in the utility supply.
1.6 UPS Working Mode
Normally UPS working mode include normal mode, bypass mode, battery mode, ECO mode,
frequency converter mode, self aging mode.
Normal Mode
Shown as Fig 1-4, rectifier supply DC supply to inverter, the load is feed by inverter. Charger
is charging the battery.

Product description
8
Fig 1- 4: Normal Mode
Static Bypass Mode
If inverter is failure or overload, UPS will transfer to bypass mode. Or press“ + ”to
transfer to bypass mode in normal mode. The load is feed by input power directly, and UPS
can not protect load from surge. Shown as Fig 1-5.
Fig 1- 5: Bypss Mode
Battery Mode
If input power is failure when in normal mode, UPS will transfer to battery mode. In this
mode, the battery provide power to inverter. Shown as Fig 1-6.
NOTICE: press“ + ”in battery mode will shutdown UPS completely.
Fig 1- 6: Battery Mode
ECO Mode (only available for single unit)
When UPS works in ECO mode, load is feed by bypass. Inverter is standby, charger is
working normally. The efficiency is up to 98%, but UPS can protect the load from surge
disturb. If input power is failure, UPS transfer to battery mode. Shown as Fig 1-7.

Product description
9
Fig 1- 7: ECO Mode
Frequency Converter Mode
In this mode, input and output nominal frequency is different, and the bypass is forbidden to
use.
NOTICE: if overload timeout, UPS will shutdown output.
NOTICE: the load should be derated to 50% and below.
Self Aging Mode
If users want to burn in UPS without load, could set the UPS as Self Aging Mode, in this
mode, the current flow through rectifier, inverter, and back to input through bypass. It needs
only 5% loss to burn in UPS with 100% load. Shown as Fig 1-8.
Fig 1- 8: Self Aging Mode
1.7 Product Specifications
1. General Specifications
Model 6kH/S(1/1) 10kH/S(1/1) 6kH/S(3/1) 10kH/S(3/1)
Power Rating PF=1, kVA=kW
Frequency (Hz) 50/60
Input
Voltage
L-N(176-288)Vac L-L(304-478)Vac
Current
Max. 36A Max. 60A Max. 12A Max. 20A

Product description
10
Battery
Voltage
192Vdc
Current
Max. 40A Max. 67 A Max. 40A Max. 67A
Output
Voltage
220(default) /230/240Vac
Current
27 A 45.5A 27 A 45.5A
Efficiency Max. 94.5% Max. 95% Max. 94.5% Max. 94.5%
Dimension
(WxDxH) (mm)
440 * 88 *580(H)
440 * 176 *660(S)
440 * 88 *650(H)
440 * 176 *660(S)
Weight (kg) 12(H)/58(S) 14(H)/63(S) 17(H)/63(S) 17(H)/67(S)
2. Electrical Performance
Input
Model Voltage Frequency Power Factor
UPS Single-phase 40-70Hz >0.99(Full load)
3. Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-40°C <95% <1000m 0°C- 70°C
NOTICE
:
If the UPS is installed or used in a place where the altitude is above than 1000m,
the output power must be derated in use, please refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
DeratingPower
100%
95% 91% 86% 82% 78% 74% 70% 67%
Output
Voltage
Regulatio
n
Power
Factor
Frequency
tolerance. Distortion Overload capacity Crest ratio
±1% 1 ±0.1 ofnormal
THD< 1%
Full load
(Linear
Load)
110% load:
transfers to
Bypass mode after 6
0
minutes
125% load:
transfers to
Bypass mode after 1
minute
150% load:
transfers to
Bypass mode after
0.5minute
and shutdown
the output after 1 minute
3:1
maximum

Installation
11
2 Installation
The system should be installed and wired only by qualified electricians in accordance with
applicable safety regulations.
NOTICE
:
UPS operation in sustained temperature outside the range of 15-25°C (59-77°F)
reduces battery life.
2.1 Unpacking and Inspection
1. Unpack the packaging and check the package contents. The shipping package contains:
1 UPS
1 user manual
2. Inspect the appearance of the UPS to see if there is any damageduring transportation. Do
not turnon the unit and notify the carrier and dealer immediately if there is any damage or
lacking of some parts.
2.2 Main cabinet installation
Two installation modes are available: tower installation and rack installation, depending on
available space and user considerations. You can select an appropriate installation mode
according to the actual conditions
1.Notes for installation
(1) The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
(2)Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of
space on each side.
(3) Condensation to water drops may occur if the UPS is unpacked in a very low temperature
environment. In this case it is necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of electric shock.
(4)The circuit breaker (CB) with residual current device (RCD) should not be used in the input
of UPS.
2.Tower Installation
Various installation configurations are available: single UPS, single UPS with single or multiple
battery cabinets. Their installation methods are all the same.
The installation procedures are as follows:
Step 1: Take out the support bases from the accessories. Their appearances are shown in
Fig.2-1.

Installation
12
Fig.2-1 Support bases
Step 2: If optional external battery cabinets are connected to the UPS to provide additional
battery run time, assemble the spacers and the support bases, as shown in Fig.2-2.
Fig.2-2 Installing support bases with spacers
Step 3: Adjust the direction of UPS operation and display panel.
1. Remove the front plastic bezel cover gently, as shown in Fig.2-3.
Fig.2-3Removing the front plastic bezel cover
2. Pull the operation and display panel gently, rotate it 90 degrees clockwise (1/1) or
anticlockwise(3/1) and snap it back into position, as shown in Fig.2-4

Installation
13
Fig.2-4Rotating the operation and display panel
3. Restore the front plastic bezel cover to the UPS. At this point, the UPS operation and display
panel have been rotated 90 degrees clockwise, which provides upright viewing for users.
Step 4: Place the UPS (and battery cabinet) on the support bases. Each UPS needs two pairs
of support bases to install, as shown in Fig.2-5.
Fig.2-5 Tower installation
2. Rack Installation
1. Various installation configurations are available: single UPS, single UPS with single or

Installation
14
multiple-battery. Their installation methods are all the same.
2. Because battery cabinets are too heavy, they must be installed first, and two or more
installation personnel are required to install them at the same time. Please install them from
bottom to top.
Rack installation: fix the UPS and battery cabinet onto the rack through brackets.
Installation method:
1. Take out two brackets and six M4 screws from the accessories, and fix the brackets onto the
UPS using the screws through installation hole, as shown in Fig.2-6.
Fig.2-6Installing brackets
2. Place the UPS onto the guide rail in the rack, and push it completely into the rack along the
guide rail (it is prohibited to move the UPS through the brackets). And fix the UPSt onto the
rack using the screws through installation hole on the bracket, as shown in Fig.2-7.

Installation
15
Fig.2-7Installing UPS
2.3 Connect Input/Output Power
1.Notes for installation
(1) The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
(2)Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of
space on each side.
(3) Condensation to water drops may occur if the UPS is unpacked in a very low temperature
environment. In this case it is necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of electric shock.
(4)The circuit breaker (CB) with residual current device (RCD) should not be used in the input
of UPS.
2. Installation
Installation and wiring must be performed in accordance with the local electric code and the
following instructions by professional personnel.
For safety, please cut off the mains power switch before installation. Open the battery breaker
for long backup time model (“H” model).
(1)Open the terminal block cover located on the rear panel of the UPS, please refer to the
appearance diagram.
(2)For 6kVA) UPS, it is recommended to select the UL1015 10 AWG(6 mm
2
) wire or other
insulated wire which complies with AWG Standard for the UPS input and output wirings.
(3) For10kVA UPS, it is recommended to select the UL1015 8 AWG(10 mm
2
) wire or other
insulated wire which complies with AWG Standard for the UPS input and output wirings.
NOTICE
:
Do not use the wall receptacle as the input power source for the UPS, as its rated

Installation
16
current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned
and destroyed. For the long backup time modes, make sure that the capacity of batteries is
larger than 24Ah to avoid over charging. If not, please confirm the charge current and set the
charge current according to battery capacity.
6/10kH/S(1/1)
6/10kH/S(3/1)
Fig 2- 8: Terminal Block Wiring Diagram
NOTICE
:
Make sure that the input and output wires and the input and output terminals are
connected tightly.
(4)Connect the input, output and battery wires to the terminals as Fig2-8.
(5)The protective earth ground wire refers to the wire connection between the equipment which
consumes electric equipment and the ground wire. The wire diameter of protective earth ground
wire should be at least as above mentioned for each model and green wire or green wire with
yellow ribbon wire is used.
(6)After having completed the installation, make sure the wiring connection iscorrect.
(7) Please install the output breaker between the output terminal and the load.
(8) To connect the load with the UPS, please turn off all the loads first, then perform the
connection and finally turn on the loads one by one.

Installation
17
(9) No matter the UPS is connected to the utility power or not, the output of the UPS may have
electricity. The parts inside the unit may still have hazardous voltage after turning off the UPS.
To make the UPS have no output, power off the UPS, and then disconnect the utility power
supply.
(10) Suggest charging the batteries for 8 hours before use. After connection, turn the input
breaker in the “ON” position, the UPS will charge the batteries automatically. You can also use
the UPS immediately without charging the batteries first, but the backup time may be less than
the standard value.
(11) If it is necessary to connect the inductive load such as a motor or a laser printer to the UPS,
the start-up power should be used for calculating the capacity of the UPS, as its start-up power
consumption is too big when it is started.
2.4 Connect External Batteries(Long Backup Model UPS)
1.The nominal DC voltage of external battery pack is 192 Vdc. Each battery pack consists of 16
pieces of 12V maintenance free batteries in series. To achieve longer backup time, it is
possible to connect multi-battery packs, but the principle of “same voltage, same type” should
be strictly followed.
2.For UPS 6/10KH, select the UL1015 10/8AWG(6/10mm
2
)or other insulated wire which
complies with UL Standard for the UPS battery wirings. The procedure of installing battery bank
should be complied with strictly. Otherwise you may encounter the hazardous of electric shock.
(1) A DC breaker must be connected between the battery pack and the UPS. The capacity of
breaker must be not less than the data specified in the general specification.
(2) Set the battery pack breaker in “OFF” position and connect the 16 pieces of batteries in
series.
(3) You must connect the external battery cable to the battery first, if you connect the cable to
the UPS first, you may encounter the hazardous of electric shock. The positive pole of the
battery is connected to the UPS with red wire; the negative pole of the battery is connected to
the UPS with black wire; the green and yellow ribbon wire is connected to the ground of the
battery cabinet.
3. To complete the connection of the external battery cable into the UPS. Do not attempt to
connect any loads to the UPS now. You should connect the input power wire to the right
position first. And then set breaker of the battery pack in the “ON” position. After that set the
input breaker in the“ON” position, the UPS begins to charge the battery packs at the time.

Installation
18
2.5 Connect Parallel Cables
1. Brief introduction
As long as the UPS is equipped with parallel cables, up to 4 UPS can be connected in parallel
to realize output power sharing and power redundancy. The unit ID in paralleled system must
be set to be different.
2. Parallel installation
(1) Users need to opt two standard 15-pin communication cables which length is appropriate to
be less than 3m.
(2)Strictly follow the stand-alone wiring requirement to perform the input wiring of each UPS.
(3) Connect the output wires of each UPS to an output breaker panel.
(4) Each UPS needs an independent battery pack.
(5) Please refer to the wiring diagram in the next page, and opt suitable breaker.
The requirement of the output wiring is as follows:
It’s recommended that the wires of output of the UPS to be less than 20m.
The difference between the wires of input & output of the UPS is required to be less than
10%.
The wiring diagram is shown as follows:
6/10KH/S(1/1)
This manual suits for next models
4
Table of contents