manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Salicru
  6. •
  7. UPS
  8. •
  9. Salicru SLC ADAPT Series User manual

Salicru SLC ADAPT Series User manual

SLC serie ADAPT
180, 300 y 500 kVA
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL
2SALICRU
General index
1. INTRODUCTION.
1.1. THANK YOU LETTER.
2. SAFETY INFORMATION.
2.1. USING THIS MANUAL.
2.1.1. Conventions and symbols used.
3. QUALITY ASSURANCE AND STANDARDS.
3.1. STATEMENT BY THE MANAGEMENT.
3.2. STANDARDS.
3.2.1. First and second environment.
3.2.1.1. First environment.
3.2.1.2. Second environment.
3.3. ENVIRONMENT.
4. PRESENTATION.
4.1. VIEWS.
4.1.1. Views of the device.
4.1.2. Device configurations.
4.2. DEFINITION OF THE PRODUCT.
4.2.1. Nomenclature.
4.3. GENERAL DESCRIPTION.
4.3.1. Introduction.
4.3.2. Conceptual diagram of the system.
4.3.2.1. Power modules (PM).
4.3.2.2. Static bypass.
4.3.2.3. Extra charger modules for 180 and 300kVA devices.
4.3.3. UPS operating modes.
4.3.3.1. Normal mode.
4.3.3.2. Battery mode.
4.3.3.3. Bypass mode.
4.3.3.4. Manual Bypass mode (maintenance bypass).
4.3.3.5. Parallel-Redundant mode.
4.3.3.6. ECO mode.
4.3.3.7. Frequency converter mode.
5. INSTALLATION.
5.1. RECEPTION OF THE DEVICE.
5.1.1. Reception, unpacking and contents.
5.1.2. Storage.
5.1.3. Unpacking and transportation to the site.
5.1.3.1. Unpacking the power module.
5.1.4. Siting, immobilising and considerations.
5.1.5. Room for the batteries.
5.2. CABINET POSITIONING.
5.2.1. 180 to 300kVA devices.
5.2.2. 500kVA devices.
5.2.3. Batteries.
5.2.4. Installation of seismic kits (optional).
5.2.5. Installation of power modules.
5.2.6. Installation of extra charger modules.
5.3. CONNECTIONS.
5.3.1. Cable entry for 180 and 300kVA devices.
5.3.2. Cable entry for 500kVA devices.
5.3.3. Connection to the entry.
5.3.3.1. Specifications.
5.3.3.2. Specifications for power cable terminals.
5.3.3.3. Circuit breakers.
5.3.3.4. Connection of the power cables.
5.3.4. Control and communication cables.
5.3.4.1. Relay interface.
5.3.4.2. Communications interface.
6. OPERATION.
6.1. STARTUP PROCEDURE.
6.1.1. Startup in Normal mode.
6.1.2. Startup from Battery mode (COLD START function).
6.2. SHUTTING DOWN THE UPS.
6.3. PROCEDURE TO TRANSFER BETWEEN OPERATING MODES.
6.3.1. Transfer from Normal mode to Battery mode.
6.3.2. Transfer from Normal mode to Bypass mode.
6.3.3. Transfer from Bypass mode to Normal mode.
6.3.4. Transfer from Normal mode to maintenance Bypass mode.
6.3.5. Transfer from maintenance Bypass mode to Normal mode.
6.4. BATTERY MAINTENANCE.
6.5. EPO.
3
6.6. INSTALLATION OF THE PARALLEL SYSTEM.
6.6.1. Location of parallel cards.
6.6.2. Jumper settings for parallel operation.
6.6.2.1. Case of 2 UPSs in parallel.
6.6.2.2. Case of 3 UPSs in parallel.
6.6.3. Setting the parameters on the display screen.
6.6.4. Connection of parallel cables.
6.6.5. Verification of the parallel system.
6.6.6. Parallel system switching.
7. CONTROL PANEL OF THE MODULES AND
THE UPS.
7.1. CONTROL PANEL OF THE MODULES.
7.1.1. Status LED.
7.1.2. Operation and control buttons.
7.1.3. LCD.
7.2. UPS CONTROL PANEL.
7.2.1. LED indicators.
7.2.2. Control and operation buttons.
7.2.3. LCD touch screen.
7.3. MAIN MENU.
7.3.1. Cabinet.
7.3.2. Power module.
7.3.3. Settings.
7.3.3.1. Date & Time setting.
7.3.3.2. Language setting.
7.3.3.3. Communications protocol setting.
7.3.3.4. User settings.
7.3.3.5. Battery settings.
7.3.4. Log.
7.3.5. Operate menu.
7.3.6. Charts.
8. MAINTENANCE, WARRANTY AND SERVICE.
8.1. PRECAUTIONS.
8.2. POWER MODULE MAINTENANCE INSTRUCTIONS.
8.3. MAINTENANCE INSTRUCTIONS.
8.3.1. CONTROL AND BYPASS UNIT MAINTENANCE
INSTRUCTIONS.
8.4. BATTERY MAINTENANCE.
8.4.1. Notes for the installation and replacement of the battery.
8.5. REPLACE DUST FILTER (OPTIONAL).
8.6. WARRANTY CONDITIONS.
8.6.1. Terms of the warranty.
8.6.2. Exclusions.
8.7. TECHNICAL SERVICES NETWORK.
9. ANNEXES.
9.1. GENERAL TECHNICAL SPECIFICATIONS.
9.2. GLOSSARY.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
4SALICRU
1. INTRODUCTION.
1.1. THANK YOU LETTER.
We thank you in advance for the trust placed in us in the pur-
chasing of this product. Read this instruction manual carefully
in order to familiarise yourself with its content, since the more
you know and understand the device the greater your satisfac-
tion, level of safety and optimisation of its functionalities will
be.
We remain at your disposal for any additional information or
queries that you may wish to make.
Yours sincerely
SALICRU
•The device described here is capable of causing sig-
nificant physical injury if improperly handled. For this
reason, its installation, maintenance and/or repair must be
carried out exclusively by our staff or qualified personnel.
•Although no effort has been spared to ensure that the in-
formation in this user manual is complete and accurate,
we accept no liability for any errors or omissions that may
exist.
The images included in this document are for illustrative
purposes and may not exactly represent the parts of the
device shown; therefore they are not contractual. However,
any divergence that may arise will be remedied or solved
with the correct labelling on the unit.
•Following our policy of constant evolution, we reserve
the right to modify the characteristics, operations
or actions described in this document without prior
notice.
•Reproduction, copying, assignment to third parties,
modification or total or partial translation of this
manual or document, in any form or by any means, without
previous written permission by us is prohibited, with
the company reserving full and exclusive property rights
over it.
5
2. SAFETY INFORMATION.
2.1. USING THIS MANUAL.
The documentation for any standard device is available to the
customer for download on our website (www.salicru.com).
•For devices ‘powered by socket,’ this is the website for
obtaining the user manual and ‘Safety Instructions’
EK266*08.
•For devices with ‘permanent connection’ via terminals, a
CD-ROM or pen drive containing all necessary information
for connection and startup, including ‘Safety Instructions’
EK266*08, may be supplied with it.
Before carrying out any action on the device relating to its in-
stallation or startup, change of location, configuration or han-
dling of any kind, carefully read the safety instructions.
The purpose of the user manual is to provide information re-
garding safety and explanations of the procedures for installa-
tion and operation of the equipment. Read them carefully and
follow the steps indicated in the order established.
Compliance with the ‘Safety Instructions’ is man-
datory and the user is legally responsible for com-
pliance and enforcement.
The device is delivered properly labelled for correct identification
of each of its parts, which, together with the instructions
described in this user manual, allows installation and startup
operations to be performed in a simple and organised manner
without any doubts whatsoever.
Finally, once the equipment is installed and operating, it is
recommended to save the documentation downloaded from the
website, CD-ROM or pen drive in a safe and easy-to-access
place, for any future queries or doubts that may arise.
The following terms are used interchangeably in the document
to refer to:
•‘SLC ADAPT,’ ‘device,’ ‘unit’ or ‘UPS’ - Uninterruptible
power supply.
Depending on the context of the phrase, it can refer either
to the actual UPS itself or to the UPS and the batteries,
regardless of whether or not it is all assembled in the same
metal enclosure.
•‘Batteries’ or ‘accumulators’ - Bank or set of elements
that stores the flow of electrons by electrochemical means.
•‘T.S.S.’ - Technical Service and Support.
•‘Customer,’ ‘installer,’ ‘operator’ or ‘user’ - These are
used interchangeably and by extension to refer to the in-
staller and/or operator who will carry out the corresponding
actions, and the same person may be responsible for car-
rying out the respective actions when acting on behalf, or
in representation, of the above.
2.1.1. Conventions and symbols used.
Some symbols may be used and appear on the device, batteries
and/or in the context of the user manual.
For more information, see Section 1.1.1 of the ‘Safety Instruc-
tions’ document EK266*08.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
6SALICRU
3. QUALITY ASSURANCE AND STANDARDS.
3.1. STATEMENT BY THE MANAGEMENT.
Our goal is customer satisfaction, therefore this Management
has decided to establish a Quality and Environment Policy,
through the implementation of a Quality and Environmental
Management System that will enable us to comply with the
requirements demanded in the ISO9001 and ISO14001 and
also by our Customers and Stakeholders.
Likewise, the management of the company is committed to
the development and improvement of the Quality and Environ-
mental Management System, through:
•Communication to the entire company of the importance
of satisfying both the customer's requirements as well as
legal and regulatory requirements.
•The dissemination of the Quality and Environment Policy
and the setting of the Quality and Environment objectives.
•Conducting reviews by the Management.
•Providing the necessary resources.
3.2. STANDARDS.
The SLC ADAPT is designed, manufactured and sold in accord-
ance with Quality Management Standard ENISO9001. The
marking indicates conformity with EC Directives through the ap-
plication of the following standards:
•2014/35/EU. - Low voltage safety.
•2014/30/EU. - Electromagnetic Compatibility (EMC).
•2011/65/EU. - Restriction of the use of hazardous sub-
stances in electrical and electronic equipment (RoHS).
In accordance with the specifications of the harmonised
standards. Reference standards:
•EN-IEC 62040-1. Uninterruptible power supplies (UPS).
Part 1-1: General and safety requirements for UPS used in
user access areas.
•EN-IEC 60950-1. Information technology equipment.
Safety. Part 1: General requirements.
•EN-IEC 62040-2. Uninterruptible power supplies (UPS).
Part 2: EMC requirements.
The UPS has been designed in accordance with the following
European and international standards:
Element Standard reference
General safety requirements for
UPSs used in areas accessible to
operators
EN50091-1-1
IEC62040-1-1
AS62040-1-1
Electromagnetic compatibility
(EMC) requirements for UPSs
EN50091-2
IEC62040-2
AS62040-2(C3)
Method for specifying the
performance and testing
requirements of UPSs
EN50091-3
IEC62040-3
AS62040-3(VFI SS 111)
The product standards mentioned above incorporate
relevant clauses that comply with IEC and EN standards
for safety (IEC/EN/AS60950), electromagnetic emission
and immunity (IEC/EN/AS61000 series) and construction
(IEC/EN/AS60146 series and 60950).
The manufacturer is not liable in the event of modifica-
tion or intervention on the device by the user.
WARNING!:
The SLC ADAPT is a modular double-conversion on-line
30 to 1500 kVA C3 category UPS.
The product’s CE declaration of conformity is available
to the customer upon express request to our head office.
3.2.1. First and second environment.
3.2.1.1. First environment.
Environment including residential, commercial and light in-
dustry installations, directly connected, without intermediate
transformers, to a low voltage public power grid.
3.2.1.2. Second environment.
An environment that includes all commercial, light industrial
and industrial establishments that are not directly connected
to a low voltage power grid supplying buildings used for resi-
dential purposes.
3.3. ENVIRONMENT.
This product has been designed to respect the environment and
manufactured in accordance with ISO14001.
Recycling of the device at the end of its useful life:
Our company undertakes to use the services of authorised and
regulatory companies to treat the set of products recovered at
the end of their useful life (contact your distributor).
Packaging:
For the recycling of the packaging there must be compliance
with the legal requirements in force, in accordance with the
specific regulations of the country where the device is installed.
Batteries:
Batteries pose a serious danger to health and the environment.
The disposal of them shall be carried out in accordance with
the laws in force.
7
4. PRESENTATION.
4.1. VIEWS.
4.1.1. Views of the device.
Fig. 1 to Fig. 13 show the views and dimensions (in mm) of
6-slot (180 kVA) and 10-slot (300 kVA and 500 kVA) devices.
Because the product is constantly evolving, however, slight
discrepancies or contradictions may arise. If in any doubt, the
labelling on the device itself will always prevail.
1300
1600
2000
2000
600
600
Fig. 1. General view of 6- and 10-slot cabinets.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
8SALICRU
19.8
LCD
4.98
Fig. 2. Front view of 30 kVA module
(20 kVA for 3x208 V AC voltages).
Touch display
Fig. 3. Front and rear view of 6-slot cabinet - 180 kVA
(120 kVA at 3x208 V) with closed doors.
9
Fig. 4. Rear view of 30 kVA module
(20 kVA for 3x208 V AC voltages).
30kVA power
modules
Module
display
Cold Start
Manual bypass
marking
Free slot for
Bypass module
Bypass input
A B C N
Output
A B C N Input
A B C N
Batteries
+ N –
SPD
(option)
Relay
interface Communications
interface
Power
module
connector
Fig. 5. Front and rear view of 6-slot cabinet - 180 kVA
(120 kVA at 3x208 V) with open doors.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
10 SALICRU
Fig. 6. Front and rear view of 10-slot cabinet - 300 kVA
(200 kVA at 3x208 V) with closed doors.
11
Bypass input
A B C N
Output
A B C N Batteries
+ N –
PE
Input
A B C N
Cold Start
Manual bypass
marking
SPD
(option)
Relay
interface
Module
display
Free slot
for Bypass
module
Communications
interface
30 kVA power
modules
Power
module
connector
Fig. 7. Front and rear view of 10-slot cabinet - 300 kVA
(200 kVA at 3x208 V) with open doors.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
12 SALICRU
Fig. 8. Front view of 10-slot cabinet - 500 kVA
(300 kVA at 3x208 V) with closed doors.
13
Fig. 9. Rear view of 10-slot cabinet - 500 kVA
(300 kVA at 3x208 V) with closed doors.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
14 SALICRU
LCD
Fig. 10. Front view of 50kVA module
(30 kVA for 3x208 V AC voltages).
UPS input
Q1 Q2 Q4 Q3
Bypass input UPS output
Manual bypass
Cold Start
Module
display
Bypass
module
50 kVA power
modules
Communications
interface
UPS input
disconnector
UPS output
disconnector
Manual Bypass
disconnector
Bypass input
disconnector
SPD (Surge Protection Device)
(Optional)
Fig. 11. Front view of 10-slot cabinet - 500 kVA
with open doors.
15
Fig. 12. Rear view of 50 kVA module
(30 kVA for 3x208 V AC voltages)
Bypass input
A B C
Input
A B C N
Output
A B C N
Batteries
+ N – PE
Fig. 13. Rear view of 10-slot cabinet - 500 kVA
with open doors.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
16 SALICRU
4.1.2. Device configurations.
The following table provides information about the configura-
tion of the UPS:
Item Components Quantity Note
6-slot cabinet
Manual bypass 1Requirement,
installed in factory
Bypass and
monitoring module 1Requirement,
installed in factory
Dust filter 1Optional
10-slot cabinet
Manual bypass 1Requirement,
installed in factory
Bypass and
monitoring module 1Requirement,
installed in factory
Dust filter 1Optional
30 kVA power
module Power module 1-10 Requirement,
installed on site
50 kVA power
module Power module 1-10 Requirement,
installed on site
4.2. DEFINITION OF THE PRODUCT.
4.2.1. Nomenclature.
SLC-6+1/10A-ADAPT 100X R P2LBDCS B1 0/36AB165 EE116502
EE Special device EE
165 Last three digits of the battery code
AB Letters of the battery family
36 Number of batteries in a single branch. For banks of common
batteries, all batteries in the system will be indicated
0/ Devices prepared for standard backups
B1 Subrack/cabinet with external batteries
S Ambient temperature sensor
C Subrack mounted on box-type BATT MOD (batteries supplied
factory mounted)
D Transient protection filter
B Independent bypass line
L Single-phase input/single-phase output device
N Three-phase input/single-phase output devices (independent
bypass line must be included)
M Single-phase input/three-phase output device (independent
bypass line must be included)
Three-phase input/three-phase output device
2 Number of subracks/cabinets in parallel
P Material needed to parallel subrack/cabinets
R ADAPT X series device in subrack format (subrack not inte-
grated into a cabinet)
Y IP20 protection rating with open door and keyless lock
X Indication for modules with 2U height. Disregard for ≥3U
modules
100 Total power of subrack/cabinet
ADAPT UPS series
A,B,C Cabinet type
10 Total number of slots in subrack/cabinet
1 Number of redundant modules (disregard if none)
6 Number of modules installed in subrack/cabinet without
taking into account redundancy
17
4.3. GENERAL DESCRIPTION.
The SLC ADAPT series is classified as an on-line double-
conversion uninterruptible power supply with DSP control and
three-level IGBT inverter technology, modular topology and
great flexibility.
Reliability: The DSP control associated with three-level PWM
technology increases the performance of the system and, together
with the redundancy of the modules, manages to increase the
availability of power to the critical loads, a parameter that
contributes to achieving a good TIER classification for the entire
system.
Availability: Its hot-swap modules can be added or replaced
during operation, thereby improving mean time to repair
(MTTR) and reducing maintenance costs. Moreover, both the
control display and the bypass module can be replaced without
affecting the operation of the device. In addition, the sys-
tem’s remote management, which can be integrated into any
platform, also makes operation easier. The extensive backup
options available, along with smart battery charging, ensure
continuous operation of the protected critical loads.
Modularity: This allows simple configurable solutions from
30 to 1500 kVA by installing 30 or 50 kVA modules in the 6-slot
(30 kVA modules) or 10-slot cabinets. As composite solutions,
a maximum of 30modules can be paralleled to obtain higher
power systems or N+n structures. Either way, it is only possible
to install identical modules in the same cabinet and/or parallel
cabinets with modules of equal power. This enables gradual
growth and scaling for future expansion depending on the
need for pay-as-you-grow protection, improving the total cost
of ownership (TCO) and providing a high level of flexibility. At
operational level, a cabinet consisting of ‘N’ modules connected
in parallel is considered a single UPS.
Any expansion or structural change to the number of modules
is possible even during normal operation and without needing
to shut down the hot-swappable system, all with the simple
use of a screwdriver to remove or screw the fixing screws of
the module(s). Although all of the UPS’s modules incorporate a
battery charger that can allocate up to 20% of its rated power
to maintaining them at an optimum charge level depending on
the type and number of elements, 50 A battery charger modules
are available to be installed solely with the 30 kVA SLC ADAPT
modules. As many charging modules as considered appropriate
can be installed, but this will be to the detriment of the total
number of UPS modules and, consequently, the total power of
the system, which will be reduced.
Backup: The capacity of the batteries determines the backup
time of the system when replacing the usual source of energy
during mains failures. The accumulator bank is always common
to any system mounted in the same cabinet. Batteries owned by
the customer or supplied with the UPS, depending on different
factors in addition to the power and/or backup requested, can
be installed in a back or one or more cabinets, always external
to the UPS itself.
4.3.1. Introduction.
SLC ADAPT series UPSs basically consist of:
•6- or 10-slot cabinet to install the power modules.
•Power modules consisting of the following blocks:
AC/DC PFC rectifier.
Battery charger.
DC/AC inverter.
Digital control and UPS management.
•Centralised bypass module: control of UPS and parallel pa-
rameters.
•Maintenance bypass.
•Control panel with touch screen (see section X for more
information).
•Batteries (number, type and location depending on the
backup time).
•Self-supporting 36 and 46U cabinets for the placement of
the different modules.
4.3.2. Conceptual diagram of the system.
The modular UPSs of the SLC ADAPT series consist of power
modules, a bypass and monitoring module, and a cabinet with
a range of disconnectors for Input, Bypass Output and Manual
Bypass. The 180 and 300 kVA UPSs only have a manual bypass
switch. One or more battery branches should be installed to
provide backup power in the event of a power failure. The
structure of the UPS is shown in Fig. 14.
STATIC BYPASS MODULE
DC / AC
INVERTER
MANUAL BYPASS
REC / PFC
BAT / DC
DC / DC
INVERTER
BYPASS
STATIC BYPASS
LINE INPUT -R, S, T-
N
POWER MODULE # 1
DC / AC
INVERTER
REC / PFC
BAT / DC
DC / DC
INVERTER POWER MODULE #N
•
•
•OUTPUT
U, V, W
N
BATTERY MODULE
BCB
BATTERY MODULE
BCB
Connection strips
between phases for mains.
Q1
Q2
INLET LINE OF UPS
-R, S, T-
The batteries are represented in
the structural diagram as they are
an essential part of all UPSs,
although they will never be
included in the cabinet itself. The
batteries can be supplied in a
separate cabinet, in a bank or not
supplied if the customer already
has them.
Fig. 14. Conceptual diagram of the SLC ADAPT series
modular UPS.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
18 SALICRU
Fig. 14 shows, byway of example, a single-line diagram of the
device with three-phase input and output.
All modules in the cabinet are structured according to the same
criteria, terminals for the power supply of the PFC rectifier and
independent static bypass, and input, output, static bypass
and manual bypass disconnectors. However, unless otherwise
requested, for separate networks originally from the factory,
the terminals of the phases of both blocks are connected by
means of strips to provide a single common input.
When separate power supplies are required, it is
obligatory to remove the strips between the phases of
both blocks before connecting the power cables, leaving the
connection strip of the neutral terminals.
4.3.2.1. Power modules (PM).
Power modules are the basic core of the entire SLC ADAPT
system. Apart from the static bypass block and LCD touch
screen, each power module contains all of the converters and
functionalities of a traditional UPS. Since this device consists
of a number of variable modules depending on the cabinet
used, a multi-parallel system is obtained with the behaviour
equivalent to that of a single mono-bloc UPS and the advan-
tages of a modular UPS.
The system supplies power to the critical load (such as com-
munication and data processing equipment) with uninterrupted
high quality AC power. The power supplied by the unit is stable,
without voltage and/or frequency variations and free from
other disturbances such as cuts or micro-cuts, sine wave al-
terations, electrical noise, anomalies commonly present in the
commercial AC network.
This is achieved through the double-conversion high frequency
Pulse Width Modulation (PWM), in combination with a digital
control based on a Digital Signal Processor (DSP), which pro-
vides high reliability and availability.
As can be seen in Fig. 14, the AC power supplied to the UPS
input is converted into DC voltage. This voltage supplies a con-
verter that transforms the voltage type from DC to AC, clean of
disturbances and variations of the AC input mains. If this fails,
the PFC rectifier changes the input source of the AC mains to
that of the batteries, powering in the same way through the
output of the UPS to the load for a limited time, that of the
backup determined by the battery pack.
4.3.2.1.1. Available power ratings.
The SLC ADAPT series has two different power modules, 30
and 50 kVA, as can be seen in Fig. 2, Fig. 4, Fig. 10 and Fig. 12.
4.3.2.2. Static bypass.
Static transfer switch.
In the event of inverter failure, overload or overtemperature,
the voltage connected to the static bypass line can supply
power to the load connected to the UPS output.
The static bypass module identified in Fig. 14 contains the
power management and control circuits that allow the most
optimum decision in each scenario to be made, in order to se-
lect the most favourable power to the critical load connected
to the output of the UPS, either from the inverter or from the
static bypass itself.
During normal system operation, the load is connected to the
inverter and in case of overload or failure, it will automatically
transfer to the static bypass line. In order to provide a clean
transfer (without interruption) between the inverter output and
the bypass line, they must be fully synchronized during normal
operation. This is achieved through real-time digital control of
the inverter, so that the frequency of the inverter follows the
frequency of the bypass line if the bypass is within the range of
acceptable frequencies.
In addition, a Manual Bypass, which is very useful during periods
of maintenance or failure, is included and allows continuous
powering of the critical load while the UPS is out of service.
When the UPS is operating in bypass mode (over static
bypass), connected devices are not protected against
power cuts or micro-cuts, overvoltages, voltage and/or fre-
quency variations as they are powered directly from the AC
mains.
4.3.2.3. Extra charger modules for 180 and 300 kVA devices.
The smart charging module is designed to supply the necessary
charging current for long backup applications. The module is hot
swappable and has the same size and appearance of any power
module, supplying an adjustable current of between 0 and 50 A.
On the front, they have a high resolution LCD where the user
can monitor the different load parameters in real time.
The modules are designed to be inserted in 6- and 10-slot
cabinets with only 30 kVA modules - 180 and 300 kVA devices
- and can be inserted in the necessary number to meet battery
charging needs.
4.3.2.3.1. Wiring diagram.
As can be seen in the diagram in Fig. 15, the charger modules
are connected in parallel to the power modules. The total cur-
rent of the system is the sum of the current supplied by the
power modules and the charger modules.
19
Input
terminal
Power module 1
Output
terminal
Power module n
Power modules
Extra charger modules
Charger module 1
Charger module m
Battery
terminal
Fig. 15. Conceptual diagram of the extra charger modules.
4.3.3. UPS operating modes.
The modular double-conversion on-line UPS has the following
operating modes:
•Normal mode
•Battery mode
•Bypass mode
•Maintenance mode (manual bypass)
•ECO mode
•Frequency converter mode
During the description of the operating modes the operation
is described referring to the PFC-rectifier and inverter parts as
functional parts of a module, although there will be as many of
them as there are modules connected in parallel.
4.3.3.1. Normal mode.
The inverter of each power module is responsible for powering
the critical loads at all times. The rectifier/charger of the AC
input powers the inverter with DC voltage while simultaneously
charging the associated backup battery, either at float or quick
voltage.
PFC rectifier
AC / DC
BAT / DC
DC / DC Battery
Charger
Inverter
DC / AC
Static bypass
Manual bypass
Batteries
AC input
Bypass
AC input
Rectifier
AC output



 
Connection strips between
phases for mains.
Fig. 16. Conceptual diagram of the UPS in Normal mode.
Indicates the direction of the energy flow.
4.3.3.2. Battery mode.
In the event of failure of the AC input power mains, the inverter,
by means of the power it obtains from the battery, supplies the
critical loads of the output in AC. By doing so, the power supply
is not interrupted in the event of failure. Once the AC power
input is restored, the ‘Normal mode’ function will be restored
automatically without the user needing to intervene.
PFC rectifier
AC / DC
BAT / DC
DC / DC Battery
Charger
Inverter
DC / AC
Static bypass
Manual bypass
Batteries
AC input
Bypass
AC input
Rectifier
AC output




Connection strips between
phases for mains.
Fig. 17. Conceptual diagram of the UPS in Battery mode.
With the Battery Cold Start function, the UPS can be
started without mains power. See details in section
6.1.2.
SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY (UPS)USER'S MANUAL
20 SALICRU
4.3.3.3. Bypass mode.
If the inverter’s overload capacity is exceeded in Normal
mode, or if the inverter cannot supply power to the loads for
any reason, the static switch will transfer the inverter’s load
to bypass, without interrupting the power to the critical loads.
If the inverter is not synchronised with the bypass, the static
switch will transfer the load from the inverter to the bypass,
interrupting the load. This is done to prevent short circuits due
to the paralleling of non-synchronised AC inputs. The time of
this interruption is programmable, the typical value being less
than 3/4 of a cycle, e.g. less than 15 ms (50Hz) and 12.5 ms
(60Hz). The transfer or retransfer action can be performed via
commands through the control panel.
PFC rectifier
AC / DC
BAT / DC
DC / DC Battery
Charger
Inverter
DC / AC
Static bypass
Manual bypass
Batteries
AC input
Bypass
AC input
Rectifier
AC output





Connection strips between
phases for mains.
Fig. 18. Conceptual diagram of the UPS in Bypass mode.
4.3.3.4. Manual Bypass mode (maintenance bypass).
If the UPS requires intervention due to breakdown or main-
tenance (for example, because there is a power module, the
bypass or the LCD with anomalies), there is the possibility of
continuing to supply the loads through the internal manual by-
pass (maintenance bypass).
When the UPS is operating in ‘Manual Bypass Mode’
(maintenance or repair period), the connected equip-
ment is not protected against power cuts or micro-cuts, over-
voltages, voltage and/or frequency variations, etc. when fed
directly from the commercial AC network.
PFC rectifier
AC / DC
BAT / DC
DC / DC Battery
Charger
Inverter
DC / AC
Static bypass
Manual bypass
Batteries
AC input
Bypass
AC input
Rectifier
AC output


Connection strips between
phases for mains.
Fig. 19. Conceptual diagram of the UPS in manual Bypass
mode (maintenance).
DANGER: During manual bypass mode, the input,
output and bypass terminals (version B) are live even if
all modules are switched off.
It is recommended in this operating mode:
–Remove the fastening screws of all power, control
and bypass modules.
–Slightly pull the handles on each one until they are
protruding by about 4-5 cm from their housing in
order to enable them to be unplugged from their
connector located on the backplane of the device.
Before any change of operating mode and after carrying out the
possible corrective actions, it is necessary to correctly insert
the modules to their original position and fix them with their
screws.
4.3.3.5. Parallel-Redundant mode.
This operating mode allows to obtain a greater capacity, reli-
ability or both, being able to be configured like extension of
power or like redundancy.
As a consideration to be taken into account when the cabinets
are in parallel, the controller included in each one guarantees
the automatic distribution of the load in all of them and all of
its modules.
4.3.3.6. ECO mode.
ECO mode saves energy. In this mode, when the input voltage
of the Bypass is within the ECO voltage range, the static bypass
that supplies power directly to the loads is activated, leaving
the inverter in standby. When the Bypass voltage or frequency
is out of range, the UPS transfers the output to Inverter.
During the transfer of the load on the inverter from ECO
mode, a small interruption (less than 10 ms) occurs. It is
very important to ensure that the critical load powered in this
UPS mode tolerates that interruption time.
PFC rectifier
AC / DC
BAT / DC
DC / DC Battery
Charger
Inverter
DC / AC
Static bypass
Manual bypass
Batteries
AC input
Bypass
AC input
Rectifier
AC output





Connection strips between
phases for mains.
Fig. 20. Conceptual diagram of the UPS in ECO mode.
4.3.3.7. Frequency converter mode.
When operating in this mode, the device supplies a fixed
output frequency of 50 or 60 Hz, or different input and output.
When operating in this mode, the static bypass is inhibited
and the manual bypass switch should not be operated due to
the consequences it could have on the loads connected to the
output.

This manual suits for next models

6

Other Salicru UPS manuals

Salicru SPS.ONE User manual

Salicru

Salicru SPS.ONE User manual

Salicru SLC CUBE 3+ User manual

Salicru

Salicru SLC CUBE 3+ User manual

Salicru SPSNET User manual

Salicru

Salicru SPSNET User manual

Salicru SLC-700-TWIN RT User manual

Salicru

Salicru SLC-700-TWIN RT User manual

Salicru SPS 500 SOHO+ User manual

Salicru

Salicru SPS 500 SOHO+ User manual

Salicru SPS.ONE User manual

Salicru

Salicru SPS.ONE User manual

Salicru SLC ADAPT User manual

Salicru

Salicru SLC ADAPT User manual

Salicru SLC-1000-TWIN PRO2 A User manual

Salicru

Salicru SLC-1000-TWIN PRO2 A User manual

Salicru SLC TWIN PRO2 User manual

Salicru

Salicru SLC TWIN PRO2 User manual

Salicru SPS.ADVANCE RT2 User manual

Salicru

Salicru SPS.ADVANCE RT2 User manual

Salicru SLC-1000-TWIN PRO2 A User manual

Salicru

Salicru SLC-1000-TWIN PRO2 A User manual

Salicru UNINTERRUPTIBLE POWER SUPPLY ADVANCE series Installation manual

Salicru

Salicru UNINTERRUPTIBLE POWER SUPPLY ADVANCE series Installation manual

Salicru SPS 750 ADV R User manual

Salicru

Salicru SPS 750 ADV R User manual

Salicru SPS.750.ADV RT User manual

Salicru

Salicru SPS.750.ADV RT User manual

Salicru SLC TWIN PRO2 User manual

Salicru

Salicru SLC TWIN PRO2 User manual

Salicru SLC ELITE MAX Series User manual

Salicru

Salicru SLC ELITE MAX Series User manual

Salicru SPS.400.TOP Installation manual

Salicru

Salicru SPS.400.TOP Installation manual

Salicru SLC-700-TWIN RT2 (B0) User manual

Salicru

Salicru SLC-700-TWIN RT2 (B0) User manual

Salicru SLC TWIN RT2 User manual

Salicru

Salicru SLC TWIN RT2 User manual

Salicru SLC-700-TWIN PRO User manual

Salicru

Salicru SLC-700-TWIN PRO User manual

Salicru SPS.HOME User manual

Salicru

Salicru SPS.HOME User manual

Salicru SLC TWIN PRO Series User manual

Salicru

Salicru SLC TWIN PRO Series User manual

Salicru SLC X-PERT Series User manual

Salicru

Salicru SLC X-PERT Series User manual

Salicru UPS SLC TWIN PRO series User manual

Salicru

Salicru UPS SLC TWIN PRO series User manual

Popular UPS manuals by other brands

Energenie EG-UPS-PS2000-02 user manual

Energenie

Energenie EG-UPS-PS2000-02 user manual

Emerson Liebert Nfinity 12-20kVA Brochure & specs

Emerson

Emerson Liebert Nfinity 12-20kVA Brochure & specs

Alvarado MSTX Retrofit Instructions

Alvarado

Alvarado MSTX Retrofit Instructions

Ablerex 3 MS series user manual

Ablerex

Ablerex 3 MS series user manual

HP 3 Phase SERIES user guide

HP

HP 3 Phase SERIES user guide

CyberPower CP900EPFCLCD user manual

CyberPower

CyberPower CP900EPFCLCD user manual

ICA CE Series user manual

ICA

ICA CE Series user manual

GE VH UL series user manual

GE

GE VH UL series user manual

AEG Protect B operating instructions

AEG

AEG Protect B operating instructions

INFOSEC UPS SYSTEM M5T Series user guide

INFOSEC UPS SYSTEM

INFOSEC UPS SYSTEM M5T Series user guide

Tripp Lite SmartPro SMART500RT1U owner's manual

Tripp Lite

Tripp Lite SmartPro SMART500RT1U owner's manual

Tripp Lite SU10000RT3UPM Specification sheet

Tripp Lite

Tripp Lite SU10000RT3UPM Specification sheet

Tripp Lite S750UNAFTA Specification sheet

Tripp Lite

Tripp Lite S750UNAFTA Specification sheet

PowerWalker PF 1 6K user manual

PowerWalker

PowerWalker PF 1 6K user manual

Tripp Lite OMNISMART OMNIVS500 owner's manual

Tripp Lite

Tripp Lite OMNISMART OMNIVS500 owner's manual

Delta Amplon RX series user manual

Delta

Delta Amplon RX series user manual

Tripp Lite BC Pro owner's manual

Tripp Lite

Tripp Lite BC Pro owner's manual

PowerGuard 6KT user manual

PowerGuard

PowerGuard 6KT user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.