Initial Testing:
When the fitting is connected to the un-switched active, it must be allowed to charge the battery for at least
24 hours. The emergency lamp only illuminates during a power failure. Conduct the following tests:
During the first commissioning test the emergency lamp must illuminate for at least 2 hours after
disconnection from the main supply. The results of all tests are required to be recorded in a service
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time,
remedial action must be taken to repair the situation and once completed, the unit must pass a
subsequent test.
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off
(Non-maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
CEILING MOUNT C0=D63, C90=D32, C180=D63, C270=D32
WALL MOUNT C0=D25, C90=C25, C180=B10, C270=C25
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or
“cycled”. The Li-ion battery in the Lifelight has been selected to give excellent long life performance in a
controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life
performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse,
are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
The manufacturer warrants the goods against defects solely due to faulty parts or workmanship of the
manufacturer for a period of 48 months from the date of purchase. This warranty covers the repair or
replacement of the goods at the discretion of the manufacturer, upon the goods being returned to the
nearest branch of the manufacturer at the clients cost. Any other warranty or guarantee, expressed or
implied, to the extent permitted by law, is expressly excluded. Themanufacturer shall not be liable for any
costs or consequential losses that may arise through the use of any of the manufacturers’products.
Installation or operation of this product in a manner NOT complying with this instruction leaflet will
automatically void any and all warranties.
1940994 V1.0 May 2017