Clevertronics Clever-test
The Clevertronics Clever-test Lifelight (LLIFEM-PRO-SA-CT) can be programmed to perform 90 minute
discharge tests at 6-month intervals. A manual test is initiated by pressing the test switch 3 times within a
5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully charge before a
test) can be initiated by pressing the test switch and hold for 10 seconds (i.e., until LED Test Switch
indicator flashes rapidly). Refer Clever-test Operation Guide for more information. Once the test has been
completed, maintenance personnel then view the Status Indicator of each fitting to determine a pass or
failure:
SOLID GREEN (not flashing)
NORMAL –The luminaire is in a normal state charging and awaiting
next discharge test.
SLOW YELLOW FLASH
(2s Yellow, 2s Off)
TESTING –The luminaire is currently performing a test.
VERY SLOW YELLOW & Green
(4s Yellow, 1s Green)
RECENTLY PASSED –The luminaire has previously tested and
passed. This indication remains for 5 days after the completion of the
test and then changes to SOLID Green to indicate a normal state.
FAST YELLOW & Green FLASH
(0.5s Yellow, 0.5s Green)
FAILED LAST TEST –The luminaire has previously tested and failed
to remain illuminated for the required duration. This indication will
remain until the required maintenance work has been completed and
the luminaire passes a subsequent discharge test.
Zoneworks and DATA Monitored Options
Lifelights with part numbers LLIFEM-PRO-SA-ZW, LLIFEM-PRO-SA-DATA are fitted with Zoneworks
communications modules (nodes).These fittings are monitored using either Powerline Carrier Technology
that utilising the power cable to provide data communication or a dedicated data cable to/from data routers
installed on a dedicated data trunk connected to a central Server (can also be connected via
Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and
collate test data from each Lifelight. Zoneworks Lifelights can be commissioned by a single push of the test
switch, or scanning of the supplied barcode. The LED Test Switch indicator provides a multifunction
indication of the status of the Lifelight during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress
LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATAversion a 2-way “figure 8” cable and terminal block facilitates the connection to the
DATA network via a multi-drop bus (daisy chain connection). For further information of installation of a
Zoneworks LW system, please refer to theZoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Lifelights with part numbers LLIFEM-PRO-SA-DALI are fitted with DALI modules (nodes) that facilitate
connection and integration to 3rd Party Lighting Control Systems. Before installing the LLIFE-PRO-DALI
please confirm that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.
The LLIFE-PRO-DALI will be addressed and configured into the control system by the Lighting Control
System Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way
“structured wiring system” lead and plug facilitating the power and DALI connection. DALI connections
are marked as Da Da.
MAXWELL SUB-ZERO REMOTE MAINTAINED
Installation & Maintenance Supplement
Models: Testing Options: xx=
MAXWELL SUB-ZERO MAINTAINED 184190 CT Clevertest
ZW Zoneworks
DATA Zoneworks DATA
DALI DALI
Spare Parts: LLIFEM-PRO-SASAMEMIPRM-xx-FIT
1530230 Battery, 3.3 Volt 5Ah Li-ion
LLIFEM-PRO-SA-CKIT13V300C PCA: Lifelight Control-SA 300mA CT10142Lx
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before
installation, ensure that the electricity supply has been switched off and isolated. Installation must be
carried out in accordance with the relevant Australian and International Standards.
Sammode Lighting Australia Pty Ltd
15 Industrial Avenue
WACOL QLD 4076
Phone: 61 (0) 7 3335 3504
Fax: 61 (0) 7 3335 3522
Designed in Australia to comply with the requirements
of AS2293.3: 2005, AS/NZS CISPR15: 2011
SAMMODE
Initial Testing:
When the fitting is connected to the un-switched active, it must be allowed to charge the battery for at least
24 hours. The emergency lamp only illuminates during a power failure. Conduct the following tests:
During the first commissioning test the emergency lamp must illuminate for at least 2 hours after
disconnection from the main supply. The results of all tests are required to be recorded in a service
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time,
remedial action must be taken to repair the situation and once completed, the unit must pass a
subsequent test.
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off
(Non-maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
CEILING MOUNT C0=D63, C90=D32, C180=D63, C270=D32
WALL MOUNT C0=D25, C90=C25, C180=B10, C270=C25
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or
“cycled”. The Li-ion battery in the Lifelight has been selected to give excellent long life performance in a
controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life
performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse,
are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
The manufacturer warrants the goods against defects solely due to faulty parts or workmanship of the
manufacturer for a period of 48 months from the date of purchase. This warranty covers the repair or
replacement of the goods at the discretion of the manufacturer, upon the goods being returned to the
nearest branch of the manufacturer at the clients cost. Any other warranty or guarantee, expressed or
implied, to the extent permitted by law, is expressly excluded. Themanufacturer shall not be liable for any
costs or consequential losses that may arise through the use of any of the manufacturers’products.
Installation or operation of this product in a manner NOT complying with this instruction leaflet will
automatically void any and all warranties.
1940994 V1.0 May 2017
Installation: Emergency Fitting
Refer to the Maxwell Installation Instruction for specific mounting hardware and methods for the fitting
body.
Refer to Supplementary Installation Instruction below for proper alignment of the gear tray and diffuser
image.
Installation: Remote Enclosure
1. 1. Remove the enclosure cover.
2. 2. Remove the gear tray.
3. 3. Use the enclosure base to mark out the (4) mounting holes.
4. 4. Install the enclosure base using appropriate fixings.
5. 5. Route power to the fitting and connect to the terminal block.
6. 6. Route the LED drive output from the terminal block to the exit fitting.
7. 7. Apply power and test the fitting operation.
Recessed LIFELIGHT Control Pack
Minimum ceiling cavity height = 80mm
Upgrading a LLIFEM-PRO-SA LED Driver to Clever-test,
Zoneworks (incl. DATA) or DALI EM
All L10 Lifelight Pro LED Driver (LLIFEM-PRO-SA) can be upgraded to Clever-test, Zoneworks,
Zoneworks DATA or DALI EM.
When upgrading simply insert the relevant smart node board.
1. Install the fitting mounting straps per the Maxwell Instruction.
2. Install the diffuser tube to the mounting straps.
3. Connect power to the gear tray terminal block.
4. Apply power and test the fitting operation.
5. Install the LED gear tray in the tube.
6. Align the RED arrow on the end cap with the RED arrow on the mounting bracket which
corresponds to the mounting (Ceiling or Wall) of the fitting.
Ceiling Mount
Wall Mount
Enclosure Base

Other Sammode Lighting Equipment manuals

Sammode BOYLE Series User manual

Sammode

Sammode BOYLE Series User manual

Sammode HOKUSAI IM User guide

Sammode

Sammode HOKUSAI IM User guide

Sammode ELGAR 70 User guide

Sammode

Sammode ELGAR 70 User guide

Popular Lighting Equipment manuals by other brands

thomann STAIRVILLE LED Vintage Bowl 50 RGBA user manual

thomann

thomann STAIRVILLE LED Vintage Bowl 50 RGBA user manual

DOTLUX LUNAsensor user manual

DOTLUX

DOTLUX LUNAsensor user manual

Bionizer BioDoser Instruction book

Bionizer

Bionizer BioDoser Instruction book

EXTOL LIGHT 43281 Translation of the original user manual

EXTOL LIGHT

EXTOL LIGHT 43281 Translation of the original user manual

Altman SS-STRIP series Specifications

Altman

Altman SS-STRIP series Specifications

olympia electronics RT-15 quick start guide

olympia electronics

olympia electronics RT-15 quick start guide

LOTRONIC LED-STOOL instruction manual

LOTRONIC

LOTRONIC LED-STOOL instruction manual

Harman Martin ERA 400 Performance CLD user manual

Harman

Harman Martin ERA 400 Performance CLD user manual

Chauvet Freedom Strip HEX-4 user manual

Chauvet

Chauvet Freedom Strip HEX-4 user manual

Vision & Control LDLF60x540-W5K7/24V Instructions for use

Vision & Control

Vision & Control LDLF60x540-W5K7/24V Instructions for use

Blizzard Lighting Motif Sketch user manual

Blizzard Lighting

Blizzard Lighting Motif Sketch user manual

Robe Colormix 240 AT user manual

Robe

Robe Colormix 240 AT user manual

Meanwell LCM-40TW installation manual

Meanwell

Meanwell LCM-40TW installation manual

Show Tec Revolution 250 user guide

Show Tec

Show Tec Revolution 250 user guide

Claypaky MINI-B SPOT manual

Claypaky

Claypaky MINI-B SPOT manual

Briteq LDP COBWASH Operation manual

Briteq

Briteq LDP COBWASH Operation manual

Martin MAC 600 user manual

Martin

Martin MAC 600 user manual

SilverStar MX-COLOR user manual

SilverStar

SilverStar MX-COLOR user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.