S&C 2000 series User manual

S&C Series 2000 Circuit-Switchers
Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
S&C ELECTRIC COMPANY
Supersedes Instruction Sheet 716-501 dated
11-29-93 c
2002
s
INSTRUCTION SHEET
716-501
Page 1 of 26
August 12, 2002
INSTRUCTIONS
For Field Assembly and Installation
Section Page Number
INTRODUCTION
Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Read this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Retain this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Proper Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY INFORMATION
Understanding Safety-Alert Messages . . . . . . . . . . . . . . . . . . . 3
Following Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 3
Replacement Instructions and Labels . . . . . . . . . . . . . . . . . . . 3
GENERAL
Interrupters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Power Train . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mounting Pedestals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Usual Operating Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Inspection Schedule and Procedures . . . . . . . . . . . . . . . . . . . . 5
Catalog Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Section Page Number
BEFORE STARTING INSTALLATION
Checking the Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Gas-Pressure Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
OPERATION
Electrical Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Decoupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Adjusting Auxiliary Switch Contacts . . . . . . . . . . . . . . . . . . . 26
TABLE OF CONTENTS

S&C ELECTRIC COMPANY s
716-501
INSTRUCTION SHEET
Page 2 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers
Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
INTRODUCTION
Ç
WARNING
The equipment covered by this publication must be installed, operated, and main-
tained by qualified persons who are knowledgeable in the installation, operation,
and maintenance of overhead electric power distribution equipment along with
the associated hazards. A qualified person is one who is trained and competent in:
•
The skills and techniques necessary to distinguish exposed live parts from
non-live parts of electrical equipment.
•
The skills and techniques necessary to determine the proper approach dis-
tances corresponding to the voltages to which the qualified person will be
exposed.
•
The proper use of the special precautionary techniques, personal protective
equipment, insulating and shielding materials, and insulated tools for working
on or near exposed energized parts of electrical equipment.
These instructions are intended only for such qualified persons. They are
not
intended to be a substitute for adequate training and experience in safety proce-
dures for this type of equipment.
Qualified Persons
Read this
Instruction Sheet
Thoroughly and carefully read this instruction sheet before installing or operating
your Series 2000 Circuit-Switcher Model 2010. Familiarize yourself with “SAFETY
INFORMATION” on page 3.
Retain this
Instruction Sheet
This instruction sheet is a permanent part of your S&C Series 2000 Circuit-
Switcher. These instructions should be stored inside the Series 2000 operator
enclosure using the instruction manual holder.
Warranty
The standard warranty contained in S&C’s standard conditions of sale, as set forth in
Price Sheet 150, is applicable to the S&C Series 2000 Circuit-Switcher covered in
this instruction sheet, except that the first paragraph of said warranty is replaced by
the following:
(1) General: Seller warrants to purchaser for a period of 5 years from the date of
shipment that the equipment delivered will be of the kind and quality specified in
the contract description and will be free of defects of workmanship and mate-
rial. Should any failure to conform to this warranty appear under proper and
normal use within five years after the date of shipment the seller agrees, upon
prompt notification thereof and confirmation that the equipment has been
stored, installed, operated, inspected, and maintained in accordance with recom-
mendations of the seller and standard industry practice, to correct the noncon-
formity either by repairing any damaged or defective parts of the equipment or
(at seller’s option) by shipment of necessary replacement parts.
Replacement parts provided by seller under the warranty for the original
equipment will be covered by the original-equipment warranty for its duration.
Replacement parts purchased separately will be covered by the warranty con-
tained in seller’s standard conditions of sale, as set forth in Price Sheet 150.
Ç
CAUTION
The equipment in this publication must be selected for a specific application. The
application must be within the ratings furnished for the equipment.
Proper Application

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET
716-501
Page 3 of 26
August 12, 2002
Understanding
Safety-Alert Messages
There are several types of safety-alert messages which may appear throughout this
instruction sheet as well as on labels and tags attached to the Series 2000 Circuit-
Switcher. Familiarize yourself with these types of messages and the importance of
the various signal words, as explained below.
Following Safety
Instructions
If you do not understand any portion of this instruction sheet and need assistance,
contact your nearest S&C Sales Office or S&C Authorized Distributor, or call S&C
Headquarters at (773) 338-1000, Monday through Friday between 8:30 AM and 5:00
PM Central Standard Time. (In Canada, call S&C Electric Canada Ltd. at (416) 249-
9171, Monday through Friday between 8:00 AM and 5:00 PM Eastern Standard
Time.)
Replacement
Instructions and Labels
If you need additional copies of this instruction sheet, contact your nearest S&C
Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric
Canada Ltd.
It is important that any missing, damaged, or faded labels on the equipment be
replaced immediately. Replacement labels are available by contacting your nearest
S&C Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric
Canada Ltd.
Ç
DANGER
“DANGER” identifies the most serious and immediate hazards which
will likely
result in serious personal injury or death if instructions, including recommend-
ed precautions, are not followed.
Ç
WARNING
“WARNING” identifies hazards or unsafe practices which
can
result in serious per-
sonal injury or death if instructions, including recommended precautions, are not
followed.
Ç
CAUTION
“CAUTION” identifies hazards or unsafe practices which
can
result in minor per-
sonal injury or product or property damage if instructions, including recommend-
ed precautions, are not followed.
NOTICE
“NOTICE” identifies important procedures or requirements that, if not followed,
can
result in product or property damage if instructions are not followed.
NOTICE
Read this instruction sheet thoroughly
and carefully before installing or oper-
ating your S&C Series 2000 Circuit-
Switcher.
SAFETY INFORMATION

S&C ELECTRIC COMPANY s
716-501
INSTRUCTION SHEET
Page 4 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers
Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
GENERAL
Interrupters
Series 2000 Circuit-Switchers employ single-gap SF
6
puffer-type interrupters designed to close the circuit in
6 cycles, interrupt the circuit in 6 cycles, and maintain
rated dielectric strength when open. These dual-function
interrupters are factory-filled to full pressure under con-
trolled conditions and then permanently sealed. Field fill-
ing is neither necessary nor possible, thus eliminating the
risk of contaminating the interrupting medium.
Operator
The interrupters are driven by a single stored-energy
mechanism located at ground level in a 48-volt dc, 125-volt
dc, or 115-volt 60-hertz operator furnished with the Cir-
cuit-Switcher. Refer to the “STANDARD FEATURES”
table on page 6, and also Figures 15 and 17. This operator
includes the following features:
•
Trip and close push buttons located inside operator
enclosure.
•
Manual trip lever, for tripping interrupters in the event
control voltage has been lost.
•
Manual charging handle, for opening disconnect after
interrupters have been manually tripped open—in the
event control voltage has been lost.
•
Charged and discharged indicators for stored-energy
mechanism.
•
Non-reset electric operation counter.
•
Eight nonadjustable single-pole double-throw auxil-
iary-switch contacts which follow the interrupters.
•
Weatherproof, dustproof enclosure.
•
Decoupling mechanism which allows decoupling and
locking of disconnect-blade power train in the open
position, permitting operational checkout of interrupt-
ers, stored-energy mechanism, and relaying equipment
without closing the high-voltage circuit.
•
Two individually adjustable auxiliary-switch contacts
which follow the disconnect-blade power train and
operator when coupled, operator only when decou-
pled.
The mechanism in the operator has an instantaneous
trip-free capability: should the Series 2000 Circuit-
Switcher be inadvertently closed into a fault sensed by
user-furnished relaying, the mechanism will trip immedi-
ately. To accomplish trip-free operation, the mechanism
utilizes two spring assemblies: one for closing, one for
opening. Both springs are charged by the operator motor
before the Series 2000 Circuit-Switcher can be closed.
Recharging time after a trip operation is approximately
5 seconds for Circuit-Switchers rated 69 kV through
138 kV, and approximately 10 seconds for Circuit-Switch-
ers rated 161 kV and 230 kV.
Power Train
The operator directly drives the interrupters open and
closed through a simple high-speed power train leading
from the top of the operator, through a horizontal inter-
phase linkage enclosed in a steel-sheathed box-type base,
to reciprocating-action insulated operating rods which
pass through the center of insulating support columns. A
transfer linkage at the top of each insulating support
column converts the vertical reciprocating motion of the
operating rod into horizontal reciprocating motion, to
drive the interrupter.
The operator also drives the disconnect open and
closed through a low-speed power train which rotates the
insulating support columns. The disconnect on models
rated 69 kV through 138 kV is capable of opening and clos-
ing without hesitation under
³⁄₄
-inch ice formation. The
disconnect on models rated 161 kV and 230 kV is capable
of opening without hesitation under
³⁄₄
-inch ice formation
and of closing without hesitation under
¹⁄₂
-inch ice forma-
tion. A decoupling mechanism allows decoupling and
locking of the disconnect-blade power train in the open
position, permitting operational checkout of the interrupt-
ers, the stored-energy mechanism, and the relaying equip-
ment without closing the high-voltage circuit.
Permanently lubricated bearings are used throughout
both the high-speed and low-speed power trains. The insu-
lating support columns are filled with a lubricated dielec-
tric filler which prevents contamination from affecting the
dielectric integrity of the column or the insulated operat-
ing rod. An aerator is utilized at the upper end of each
insulating support column to eliminate water being
pumped-in due to pressure differentials caused by tem-
perature cycling.

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 5 of 26
August 12, 2002
MODEL 2010—With Horizontal Interrupters and Vertical-Break Power-Operated Disconnect
Rating
Phase Spacing,
Inches
(mm)
Circuit-Switcher
Catalog Number
kV Amperes, RMS
Nom. Max BIL Cont. Short-Time Fault-Closing,
Duty-Cycle,
One-Time1
Mom. 1-Sec.
69 72.5 350 1200 64 000 40 000 40 000 48 (1219) 197436
84 (2134) 197736
115 121 550 1200 64 000 40 000 40 000 84 (2134) 197738
102 (2591) 197838
138 145 650 1200 64 000 40 000 40 000 84 (2134) 197739
102 (2591) 197839
161 169 750 1200 64 000 40 000 40 000 120 (3048) 197030
230 242 900 1200 64 000 40 000 40 000 120 (3048) 197031
1The one-time duty-cycle fault-closing rating expressed in amperes
RMS asymmetrical is 1.6 times the symmetrical value listed (or 64,000
amperes).
Mounting Pedestals
Series 2000 Circuit-Switchers are furnished with mount-
ing pedestals. Refer to the “STANDARD FEATURES” table
on page 6. Anchor bolts are furnished when specified sep-
arately.
Usual Operating Conditions
Series 2000 Circuit-Switchers will perform as intended at
temperatures within the range of –40ºC to +40ºC (–30ºC to
+40ºC for 161-kV and 230-kV models), at altitudes of up to
5000 feet, and at wind loadings of up to 80 miles per hour.
Further, Series 2000 Circuit-Switchers, when installed
with the recommended S&C anchor bolts and with flexi-
ble-conductor connections at all six terminal pads, are
capable of withstanding seismic loading of 0.2 g ground
acceleration in any direction, as well as performing as
intended during such loading and afterward. For applica-
tions at temperatures not within the specified range, at
higher altitudes, at higher wind loadings, or where higher
seismic withstand capabilities are required, refer to the
nearest S&C Sales Office.
Inspection Schedule and Procedures
To assure Series 2000 Circuit-Switcher’s continued proper
performance, it should be inspected in accordance with
S&C’s recommended schedule and procedures contained
in S&C Instruction Sheet 716-590.
Catalog Number Description
The following table lists the basic catalog numbers and
ratings of Model 2010 Series 2000 Circuit-Switchers. The
catalog number and ratings of the Circuit-Switcher fur-
nished are stamped on the nameplate located on the door
of the operator.
GENERAL — Continued

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 6 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
GENERAL — Continued
STANDARD FEATURES
Feature Suffix
Added to
Circuit-Switcher
Catalog Number
Item Description
Operator Control Voltage
48 V dc -A
125 V dc -B
115 V 60 Hz -D
Mounting Pedestal Height1
96 inch (2438 mm) -E8
120 inch (8048 mm) -E10
144 inch (3658 mm) -E12
168 inch (4267 mm) -E14
192 inch (4877 mm) -E16
216 inch (5486 mm) -E18
240 inch (6096 mm) -E20
Operator Space-HeaterVoltage Regular Wattage 120 V 60 Hz -H1
240 V 60 Hz -H2
Reduced Wattage2120V 60 Hz -H3
1Anchor bolts are specified separately.
2For applications in temperate climates.
Suffixes to the basic catalog number specify operator
control voltage, space-heater voltage, and mounting ped-
estal height, in accordance with the following standard
features table:

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 7 of 26
August 12, 2002
OPTIONAL FEATURES
Item
Suffix
Added to
Circuit-Switcher
Catalog Number
Bypass Accessory, single-pole, stick-operated, set of three, 1200 amperes continuous, 61,000 amperes momentary rating.
Permits operational checkout of Circuit-Switcher and relaying equipment without opening high-voltage circuit -F
Grounding Switch, manual, three-pole, group-operated, 64,000 amperes momentaryrating, with flexible straps for current
transfer at hinge end of grounding-switch blades; blades parallel to pole-unit bases when in open position. Grounds jaw-contact
terminal pads -G2
Grounding Switch, manual, three-pole, group-operated, 64,000 amperes momentaryrating, with flexible straps for current trans-
fer at hinge end of grounding-switch blades; blades parallel to pole-unit bases when in open position. Grounds interrupter-end
terminal pads -G4
Deletion of Trip and Close Push Buttons located inside operator enclosure1-J
Space Heater Thermostat for operator -K
Key Interlock located inside operator enclosure. Key may be removed when interrupters are tripped—thereby locking the inter-
rupters open and disconnecting the control circuit. Key may then be used in interlock associated with grounding switch (such as
Key Interlock Option Suffix “-L4”), or other device -L1
Key Interlock mounted on grounding-switch manual operating handle. Works in conjunction with Key Interlock Option Suffix
“-L1” to guard against operating grounding switch with disconnect blades closed or with interrupters closed -L4
Position-Indicating Lamps (one red, one green) located inside operator enclosure. Lamps are wired in series with trip coil, for
local indication of Circuit-Switcher position and operator trip-circuit continuity -M
Anti-Pump Circuit. For applications where user’s control scheme utilizes closing contact which is maintained longer than 6 sec-
onds. Prevents alternating opening and closing attempts in the event Circuit-Switcher is closed into a fault, by causing Circuit-
Switcher to remain open -P
Remote Gas-Density Monitor. Provides a system to monitor the SF6gas density in each interrupter. System outputs include
two alarm relays that actuate at pre-set gas densities, a system status alarm relay, 0 to 1 mA analog outputs for each inter-
rupter, and a liquid crystal display inside the operator enclosure -R
Trip-Circuit-Monitoring Relay wired in series with operator trip coil. Monitors continuity of trip circuit. Includes one normally open
and one normally closed contact suitable for use with remotely located indicating lamps or alarms -T
Disconnect/Interrupter Simultaneous-Opening Circuit. For applications where user’s protective-relay contact closure is to initiate
disconnect blade opening simultaneously with interrupter tripping -U
Duplex Receptacle with Ground-Fault Circuit Interrupter and Convenience-Light Lampholder with Switch located inside operator
enclosure -V
Eight Additional Nonadjustable Single-Pole Double-Throw Auxiliary-Switch Contacts in Operator which follow the interrupters -W1
Local-Remote Selector Switch. Prevents remote operation of operator when selector switch is placed in “local” mode as, for
example, during inspection1-Y
1Suffix “-J” cannot be furnished if suffix “-Y” is specified, and vice
v
ersa.
The basic catalog number may also be suffixed to spec-
ify one or more optional features, in accordance with the
following table:
GENERAL — Continued

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 8 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
Transition box
Operator support plate
Operator
Channel base
Insulating support column
Single-gapSF6puffer-type
interrupter Pressure-relief device and
low-gas-pressure indicator
(not visible in photo)
High-speed interrupter
power train enclosed in
steel-sheathed box-type
cross base
Disconnect blade
Switch-position
indicator
Support-arm channel
assembly
Low-speed
disconnect
power train
GENERAL — Continued
Figure 1. Model 2010 Series 2000 Circuit-Switcher rated 138 kV.

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 9 of 26
August 12, 2002
BEFORE STARTING INSTALLATION
Checking the Shipment
An S&C catalog drawing will be found in a water-resistant
envelope attached to the plastic bubble-wrap around one
of the insulating support columns. Study this drawing
carefully and check the bill of material to verify that all
parts are at hand.
The Model 2010 Series 2000 Circuit-Switcher shipment
should include the following items, as shown in Figures 2
and 5:
1. Three pole-units, each consisting of an interrupter,
integral disconnect blade, insulating support column,
support insulator, and channel base—all factory-
assembled and adjusted.
2. A single cross base, enclosing the high-speed inter-
phase power train which drives the interrupters.
3. The appropriate number of mounting pedestals, com-
plete with support arms and channels. A single pedes-
tal is used for Circuit-Switchers rated 69 kV (with 48-
inch phase spacing); a set of two pedestals is used for
Circuit-Switchers rated 69 kV (with 84-inch phase spac-
ing), 115 kV, and 138 kV; and a set of three pedestals is
used for Circuit-Switchers rated 161 kV and 230 kV.
4. A Series 2000 Circuit-Switcher Operator.
5. A low-speed interphase power train which drives the
disconnect blades.
6. A container of miscellaneous operating-mechanism
components and hardware—all individually identified.
7. Any optional features specified, such as a grounding
switch.
Gas-Pressure Indicator
Series 2000 Circuit-Switchers have sealed interrupters
containing gas under pressure. Low gas pressure is sig-
naled by a red target in the gas-pressure indicator at the
terminal end of the interrupter.
DO NOT INTERMIX COMPONENTS FROM
DIFFERENT INSTALLATIONS
Series 2000 Circuit-Switchers are completely fac-
tory-assembled and thoroughly tested. To speed
installation and maintain proper adjustment of the
Circuit-Switcher and its operator, it is imperative
that components belonging to a specific Circuit-
Switcher installation not be intermixed with compo-
nents belonging to a different installation. For this
reason, each Series 2000 Circuit-Switcher is serially
numbered. This serial number appears on the indi-
vidual pole-units, the cross base, the mounting ped-
estals, and the operator.
It is further important that components from dif-
ferent installations not be intermixed in that S&C
maintains an historical record—by serial num-
ber—of every Circuit-Switcher produced. This
record lists information pertinent to each installa-
tion, such as application, date of shipment, and any
service performed by S&C field service specialists.
This record is invaluable when questions arise rela-
tive to modifications or replacements.
Please complete and mail the Circuit-Switcher
registration card (enclosed in a vinyl envelope
located inside the operator) after the Circuit-
Switcher has been installed. The information
requested on this card is vital to ensure prompt
notification in the event field modifications are
needed.
Storage
If the Circuit-Switcher must be stored before installation,
keep it in a clean, dry, corrosion-free area to protect it
from damage. If storing outside or in a non-climate con-
trolled area, connect control power to the space heater
inside the Circuit-Switcher Operator per wiring diagram.
Inspect the Circuit-Switcher regularly when stored for
prolonged periods.
NOTICE
The Series 2000 Circuit-Switcher Operator is equipped
with a space heater that must be energized during
storage to prevent condensation and corrosion within
the operator enclosure.
NOTICE
Loss of gas pressure may result in improper interrupt-
ing action. The red target should not be visible. If the
red target is visible, stop the installation and notify
S&C Electric Company.

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 10 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
INSTALLATION
Pole-unit
Support arms
Mounting pedestal
Miscellaneous operating-mechanism
components and hardware
Cross base
Interphase pipe assembly and
interphase drive link
Figure 2. Typical shipment of Model 2010 Series 2000 Circuit-Switcher. Operator is shipped on a separate skid; see Figure 5.
BOLTED AND PINNED CONNECTIONS
A typical bolted connection for field assembly
requires a flat washer under the cap screw and one
under the nut. In instances where self-locking hex
nuts are specified, it is essential that the threads of
the associated cap screws be lubricated with a gen-
eral-purpose grease, to facilitate tightening. All pins
used in the field assembly should also be lubricated
to facilitate insertion.
Step 1
Cut the steel straps that bind the mounting pedestals to
the cross base, the straps that bind the container of mis-
cellaneous operating-mechanism components and hard-
ware, and the straps that bind the pole-units. Also remove
the wood bracing between the pole-unit terminal pads.
See Figure 2. For Circuit-Switchers rated 161 kV and
230 kV: Remove the lifting angles attached to the pole-unit
channel bases; retain these lifting angles and associated
hardware for re-use in Step 13.
ÇCAUTION
Do not remove the containers from the interrupters,
or the plastic bubble-wrap from the insulating sup-
port columns, until the installation has been
completed.

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 11 of 26
August 12, 2002
INSTALLATION — Continued
Protective cover at pole-unit mounting
position. See Step 13
Eyebolts (not furnished)
Figure 3. Pedestal mounting detail.
Figure 4. Hoisting the cross base.
Step 3
Attach four suitable lifting slings to the cross base. See
Figure 4. Unbolt the base from the shipping skid and lift
the base atop the mounting pedestals, as shown on the
catalog drawing. Avoid sudden starts and stops. Verify
that the switch-position indicator on the base is visible on
the desired side (this is also the side on which the opera-
tor door will open).
Step 4
Loosely bolt the cross base to the mounting pedestals
using the ⁵⁄₈—112¹⁄₄hex-head galvanized steel cap
screws, flat washers, and self-locking hex nuts furnished.
Then— using a level—verify that the cross base is hori-
zontal, both lengthwise and side-to-side; adjust the lower
set of anchor-bolt nuts at the pedestals to achieve this
condition
Step 5
Securely bolt the cross base to the mounting pedestals.
Shims are furnished and should be installed as necessary
between the cross base and the mounting pedestals, to
compensate for any irregularities greater than ¹⁄₈ inch
between the mating surfaces.
Step 6
Check the lower set of anchor-bolt nuts at each mounting
pedestal to verify that all nuts are in contact with the
bottom of the pedestal. Hand-tighten these anchor-bolt
nuts as necessary. Then securely tighten the upper set of
anchor-bolt nuts at each mounting pedestal.
Concrete pad
Pedestal
Anchor bolts
Two nuts and two flat washers
provide leveling means
Step 2
Install the mounting pedestals. See Figure 3. Make cer-
tain that the grounding pad on each mounting pedestal is
properly positioned for this particular installation.
Adjust the lower set of anchor-bolt nuts at each pedes-
tal to generally plumb and level the pedestal. The upper
set of anchor-bolt nuts should be only loosely attached at
this time.

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 12 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
INSTALLATION — Continued
Figure 5. Raising operator upon base skid.
Step 7
Loosen the ¹⁄₂—131¹⁄₄galvanized steel cap screws, flat
washers, and nuts which are used to attach the bottom
plates to the underside of the cross base. Remove the
plates and place them and their hardware aside on a clean
surface.
Also remove the ³⁄₄-inch stainless-steel pin and cotter
pin from the interphase drive lever enclosed in the cross
base. See Figure 10. Retain these pins for re-use in
Step 17.
Step 8
Wrap a lifting sling around the stored-energy housing of
the operator, as shown in Figure 5 (left). Now carefully
raise the operator to the upright position so that it rests
on its base skid, as shown in Figure 5 (right). Do not
remove the lifting sling around the stored-energy hous-
ing, as the operator is top-heavy and must be adequately
supported until it is attached to the Circuit-Switcher.
Remove the skid and bracing which runs the length of the
operator, stored-energy housing, and operator support
tube. Also remove the protective cover atop the operator
support tube, as well as the protective covers on the oper-
ator enclosure louvers.
Step 9
Reposition the lifting sling around the front of the stored-
energy housing and wrap another lifting sling around the
back of the stored-energy housing, as shown in Figure 6.
Make certain that the operator door faces the same way
as the switch-position indicator on the cross base. Then
carefully hoist the operator into place. Be careful not to
damage the uni-ball coupling on the operator connecting
link during hoisting and attachment of the operator.
Attach the operator support tube mounting plate to the
underside of the cross base using four ¹⁄₂—131¹⁄₄ hex-
head galvanized steel cap screws, flat washers, and self-
locking hex nuts. Tighten all four screws securely.
Stored-energy housing

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 13 of 26
August 12, 2002
INSTALLATION — Continued
Figure 6. Hoisting operator into position.
Step 10
Attach the operator support angle to the appropriate
mounting pedestal using two ⁵⁄₈—1114hex-head galva-
nized steel cap screws, four flat washers, and two self-
locking hex nuts furnished. Refer to the catalog drawing
and Figure 6. Then attach the operator support plate to
the angle on the side of the operator enclosure and to the
operator support angle on the mounting pedestal using
four ¹⁄₂—131¹⁄₂hex-head galvanized steel cap screws,
flat washers, and self-locking hex nuts furnished. Securely
tighten the screws. See Figures 1 and 6. On Circuit-
Switchers utilizing two or three mounting pedestals,
insert the hole plugs furnished into all unused holes in the
pedestals.
Step 11
Attach the support armsto the mounting pedestals as
shown on the catalog drawing, using ⁵⁄₈—111¹⁄₂ hex-
head galvanized steel cap screws and flat washers fur-
nished. The screws should only be loosely attached at this
time.
Step 12
For Circuit-Switchers rated 69 kV through 138 kV: Refer
to the catalog drawing and attach the interrupter-end and
disconnect-end support arm channel assembliesto the
support arms, using clip angles, ¹⁄₂—131³⁄₄ hex-head
galvanized steel cap screws, flat washers, and self-locking
hex nuts furnished.
For Circuit-Switchers rated 161 kV and 230 kV: Refer to
the catalog drawing and attach the interrupter-end and
disconnect-end support arm channel assemblies to the
support arms, using clip angles, ¹⁄₂—131³⁄₄ hex-head
galvanized steel cap screws (at the outboard pole-units),
¹⁄₂—132 hex-head galvanized steel cap screws (at the
center pole-unit), flat washers, and self-locking hex nuts
furnished.
Level the support arm channel assemblies to the same
elevation as the cross base, then tighten the associated
cap screws securely. Now securely tighten the
⁵⁄₈—111¹⁄₂ hex-head galvanized steel cap screws which
attach the support arms to the mounting pedestals.
Torque the cap screws to 160 foot-pounds.
A single support arm and support arm channel assembly are used on
69-kV Circuit-Switchers with 48-inch phase spacing, for attachment at the
interrupter end. Further, a disconnect-end support arm angle is furnished
in lieu of a disconnect-end support arm channel assembly.
Operator support tube
mounting plate
Uni-ball coupling
Operator support tube
Stored-energy housing
Holes for ¹⁄₂—131³⁄₄
hex-head galvanized steel
cap screws, flat washers,
and self-locking nuts
⁵⁄₈—1114hex-head
galvanized steel cap
screws, flat washers, and
self-locking nuts
Operator support angles

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 14 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
INSTALLATION — Continued
Step 13
For Circuit-Switchers rated 69 kV through 138 kV: Attach
four suitable lifting slings to the channel base of the pole-
unit that will be mounted at the center of the cross
base—marked “Pole 2”—as shown in Figure 7 (left).
(“Pole 2” is positioned outboard on the shipping skid for
ease in handling.)
For Circuit-Switchers rated 161 kV and 230 kV: Attach
the lifting angles retained from Step 1 to the channel base
of the pole-unit that will be mounted at the center of the
cross base—marked “Pole 2,” using ¹⁄₂—131³⁄₄hex-
head galvanized steel cap screws, flat washers, and hex
nuts furnished. See Figure 7 (right). Securely tighten the
cap screws. (“Pole 2” is positioned outboard on the ship-
ping skid for ease in handling.) Then attach four suitable
lifting slings (10 to 12 feet long for Circuit-Switchers rated
161 kV, 12 to 14 feet long for Circuit-Switchers rated 230
kV) to the lifting angles.
Make certain that the rigging does not stress the inter-
rupter, transition box, or disconnect. Unbolt the base
from the skid. Raise the pole-unit a few feet, then remove
the two ¹⁄₂—131³⁄₄hex-head galvanized steel cap
screws, flat washers, and hex nuts which attach the ship-
ping bracket to the bottom of the pole-unit channel base.
Note: The insulated operating rod is under pressure;
removal of the two screws may result in the operating rod
quickly moving down approximately ³⁄₈ inch. Remove the
¹⁄₂-inch silicon-bronze pin and cotter pin from the insu-
lated operating rod and retain these for re-use in Step
16(d). Discard the shipping bracket and associated hard-
ware.
Remove the protective cover on the cross base at the
pole-unit mounting position. See Figure 4. Now continue
to raise the pole-unit to its mounting position at the center
of the cross base, as shown on the catalog drawing. Care-
fully guide the pole-unit to avoid damaging the insulated
operating rod. Do not attempt to lift the pole-unit by the
interrupter or disconnect.
Attach the pole-unit channel base to the cross base,
using ¹⁄₂—131³⁄₄hex-head galvanized steel cap screws,
flat washers, and self-locking hex nuts furnished. Securely
tighten the cap screws.
Figure 7. Hoisting the pole-unit.
Insulated operat-
ing rod
(shipping bracket
removed in photo)
Circuit-Switchers rated 69 kV through 138 kV
Eyebolts
(not furnished)

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 15 of 26
August 12, 2002
INSTALLATION — Continued
Next, attach the pole-unit channel base to the inter-
rupter-end support arm channel assembly. For Circuit-
Switchers rated 69 kV through 138 kV: Use ¹⁄₂—131¹⁄₂
hex-head galvanized steel cap screws, flat washers, and
self-locking hex nuts furnished. For Circuit-Switchers
rated 161 kV and 230 kV: Use ¹⁄₂—132hex-head galva-
nized steel cap screws, flat washers, and self-locking hex
nuts furnished. Securely tighten the cap screws.
Finally, attach the pole-unit channel base to the discon-
nect-end support arm channel assembly.For Circuit-
Switchers rated 69 kV through 138 kV: Use ¹⁄₂—131¹⁄₂
hex-head galvanized steel cap screws, flat washers, and
self-locking hex nuts furnished. For Circuit-Switchers
rated 161 kV and 230 kV: Use ¹⁄₂—132hex-head galva-
nized steel cap screws, flat washers, and self-locking hex
nuts furnished. Securely tighten the cap screws. Shims are
furnished and should be installed as necessary between
the pole-unit channel base and the disconnect-end sup-
port arm channel assembly, to compensatae for any irreg-
ularities between the mating surfaces.
Step 14
Repeat Step 13 for the two outboard pole-units—marked
“Pole 1” and “Pole 3.”
Step 15
For 69-kV Circuit-Switchers with 48-inch phase spacing:
Relevel the interrupter-end support arm channel assembly
and disconnect-end support arm angle to the same eleva-
tion as the cross base. If necessary, loosen the cap screws
used to attach the outboard pole-unit channel bases to the
cross base, interrupter-end support arm channel assem-
bly, and disconnect-end support arm angle, and shift the
pole-units in order to level the channel assembly and sup-
port arm angle. Then securely tighten the cap screws.
Disconnect-end support arm angle on 69-kV Circuit-Switchers with
48-inch phase spacing.
Circuit-Switchers rated 161 kV and 230 kV
Insulated operating rod
(shipping bracket removed
in photo)
Lifting
angles

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 16 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
INSTALLATION — Continued
Step 16
Prepare the insulated operating rod of each pole-unit for
attachment to the interphase drive in the cross base as fol-
lows:
(a) Remove the six ⁵⁄₁₆—18³⁄₄hex-head stainless-steel
cap screws used to attach the access cover to the side
of the transition box. See Figure 8 (left). Remove the
cover and place it and the hardware on a clean sur-
face.
(b) Check that the transition lever is in the open position.
The lever should be turned fully counterclockwise.
See Figure 8 (right). If the lever is not in the open posi-
tion, complete the following steps:
Carefully turn the transition lever to this position. If
the transition lever cannot be freely rotated to its fully
counterclockwise position, misalignment of the inter-
phase drive is occurring in the cross base. Temporarily
swing the insulated operating rod end links up, away
from the interphase drive linkage lever, and again try
ÇCAUTION
Keep fingers clear of the transition lever’s
travel. The transition lever is under pressure and
could quickly rotate counterclockwise. Injury to the
fingers could result.
rotating the transition lever to its fully counterclock-
wise position; see Figure 9.
(c) Remove the ³⁄₈-inch stainless-steel connecting pin used
to attach the transition lever to the operating rod link.
See Figure 8 (right). The pin is locked in place by a
retainer; lift and turn the retainer to remove the pin.
Keep the pin for re-use in Step 16(e).
(d) Attach the insulated operating rod end links to the
interphase drive linkage lever in the cross base, using
the ¹⁄₂-inch silicon-bronze pin and cotter pin retained
from Step 13; see Figure 9. The insulated operating rod
may be moved up or down, as required, to make the
connection.
(e) Replace the ³⁄₈-inch stainless-steel connecting pin
retained from Step 16(c). See Figure 8 (right). It will
be necessary to loosen the ⁵⁄₁₆—182¹⁄₄hex-head
stainless-steel screw indicated in Figure 8 (right)
and withdraw it approximately ¹⁄₈ inch, so that the
connecting pin can be inserted. Do not remove the
screw at this time.
(f) After the connecting pin has been inserted and locked
in place by its retainer, remove and discard the
⁵⁄₁₆—182¹⁄₄hex-head stainless-steel screw and stop
bracket (marked with a black/yellow striped label)
illustrated in Figure 8 (right).
⁵⁄₁₆—182¹⁄₄hex-head
stainless-steel screw
Transition lever in shipping position Transition lever in open position
Spacer
(marked
with a
black/
yellow
striped
label)
Operating rod link
Transition
lever
⁵⁄₁₆—18³⁄₄hex-head
stainless-steel cap screws for
access cover (removed)
Transition
box
Connecting pin
retainer
³⁄₈stainless-
steel connect-
ing pin
Stop bracket (marked
with a black/yellow
striped label)
Figure 8. Preparing insulated operating rod for attachment.

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 17 of 26
August 12, 2002
INSTALLATION — Continued
Adjustable locking rod
(marked with a black/yellow
striped label)
Interphase drive lever
¹⁄₄—20 locknut
Operator connecting link ³⁄₄stainless-steelpin
and cotter pin
Uni-ball
coupling
Step 17
Attach the uni-ball coupling on the operator connecting
link to the interphase drive lever in the cross base, using
the ³⁄₄-inch stainless-steel pin and cotter pin retained from
Step 7. See Figure 10. An adjustable locking rod (marked
with a black/yellow striped label) is furnished, factory-con-
nected to the interphase drive lever; turn the associated
¹⁄₄—20 locknuts as required to raise or lower the inter-
phase drive lever and thus facilitate insertion of the stain-
less-steel pin.
Step 18
Remove the lower ¹⁄₄—20 locknut which retains the
adjustable locking rod. Then remove and discard the
adjustable locking rod and locknuts.
Figure 9. Attaching insulated operating rod to interphase
drive.
Insulated operating rod end links
Interphase drive
linkage lever ¹⁄₂silicon-bronze
pin and cotter pin
Figure 10. Attaching connecting link to interphase drive
lever.

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 18 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
INSTALLATION — Continued
Figure 11. Connecting interphase pipe assembly and vertical operating-pipe assembly. Attachment of interphase drive
link to interphase pipe assembly is different on Circuit-Switchers rated 69 kV (with 48-inch phase spacing), 161 kV, and
230 kV; refer to the catalog drawing.
Interphase pipe
assembly
¹⁄₂stainless-steel pin
and and cotter pin
Locknut
Take-off shaft
⁵⁄₈stainless-steel
pin and “X” washer
Locknut
Interphase
drive link
Clevis
Bell crank
Adjustable
coupling
¹⁄₂stainless-steel pin,
galvanized steel spacers, and
stainless-steel “X” washers
Insulating support
column drive lever
Vertical
operating-
pipe
assembly
⁵⁄₈stainless-
steel pin and
cotter pin
Locknut
(not visible
in photo)

S&C ELECTRIC COMPANY
s
INSTRUCTION SHEET 716-501
Page 19 of 26
August 12, 2002
INSTALLATION — Continued
Step 19
Make certain that the insulating support column drive
lever at each pole-unit is turned completely in the blade-
closing direction. Connect the factory-adjusted inter-
phase pipe assembly to the center pole-unit insulating
support column drive lever using a ¹⁄₂-inch stainless-steel
pin, two galvanized steel spacers, and two stainless-steel
“X” washers furnished. See Figure 11. Then attach the
interphase pipe assembly to the two outboard pole-unit
insulating support column drive levers.
In the event that the interphase pipe assembly cannot
be connected to an outboard pole-unit insulating support
column drive lever, loosen the appropriate locknut at the
adjustable coupling and rotate the affected interphase
pipe section so that the connection can be made; then
tighten the locknut. See Figure 11.
Verify, at each outboard pole-unit insulating support
column, that the clearance between the rotating-spindle
closed-stop bolt and the bumper is ¹⁄₁₆ inch or less. See
Figure 12 (left). (At the center pole-unit insulating support
column, the closed-stop bolt must touch the bumper.) In
the event that the clearance between the closed-stop bolt
and the bumper exceeds ¹⁄₁₆ inch at either outboard pole-
unit insulating support column, remove the pin at the
appropriate insulating support column drive lever, loosen
the appropriate locknut at the adjustable coupling, and
rotate the affected interphase pipe section so that the
aforementioned clearance is attained. Then replaced the
pin and tighten the locknut. See Figure 11. Do not adjust
the closed-stop bolts.
Step 20
Attach the clevis end of the interphase drive link to the
longer of the bell-crank arms on the cross base, using a ¹⁄₂-
inch stainless-steel pin and cotter pin furnished. See
Figure 11.
Step 21
Attach the “C”-shaped clevis at the lower end of the verti-
cal operating-pipe assembly to the take-off shaft on the
rear of the operator, using a ⁵⁄₈-inch stainless-steel pin and
stainless-steel “X” washer furnished. See Figure 11 (inset).
Then attach the straight clevis at the upper end of the ver-
tical operating-pipe assembly to the shorter of the bell-
crank arms on the cross base, using a ⁵⁄₈-inch stainless-
steel pin and cotter pin furnished. See Figure 11. If neces-
sary, loosen the locknuts at the top and bottom of the ver-
tical operating pipe and rotate the pipe so that the
connection can be made; then tighten the locknuts.
Figure 12. Clearances at closed and open stops.
0at center pole-unit
¹⁄₁₆max. at outboard
pole-units
Disconnect in closed position Disconnect in open position
Bumper Open-stop
bolt
Closed-stop
bolt
Rotating
spindle
Insulating support
column
Must not touch
Do not adjust
closed-stop bolt Do not adjust
open-stop bolt

S&C ELECTRIC COMPANY s
716-501 INSTRUCTION SHEET
Page 20 of 26
August 12, 2002
S&C Series 2000 Circuit-Switchers Model 2010 — With Horizontal Interrupters and
Outdoor Transmission (69 kV through 230 kV) Vertical-Break Power-Operated Disconnect
Step 22
Use the manual charging handle furnished with the opera-
tor to check functioning of the low-speed power train, as
follows. Refer to Figure 16.
(a) Open the access shutter and place the manual charg-
ing handle on the manual charging shaft.
(b) Rotate the shaft, clockwise only, just to the point at
which the disconnect-blade tongue contacts clear
their respective jaw-contact fingers. See Figure 13.
With the disconnect blades maintained in the posi-
tion shown in Figure 13, check each blade to verify that
its centerline has not shifted left or right by more than
¹⁄₄ inch—as measured to the centerline of its respective
jaw contact. If any blade centerline has shifted by more
than ¹⁄₄ inch, loosen the leveling-screw locknuts
located under the associated jaw-contact support insu-
lator. See Figure 14. Adjust the locknuts as necessary
to shift the jaw-contact centerline to correspond to
that of the blade centerline, ±¹⁄₄ inch. Then tighten the
locknuts. To avoid changing the effective height of the
support insulator, do not adjust more than three of
the four sets of locknuts.
(c) Continue to rotate the shaft, clockwise only, until a
firm resistance is felt. At this point, the disconnect
blades should be open past 90 degrees. If the discon-
nect blades are not open past 90 degrees, loosen the
locknuts at the top and bottom of the vertical operat-
ing pipe and rotate the pipe clockwise (as viewed from
the top) to increase blade travel; then tighten the lock-
nuts. Now verify, at each pole-unit insulating support
column, that the rotating-spindle open-stop bolt does
not touch the bumper. See Figure 12 (right). If any
open-stop bolt does touch the bumper, loosen the
locknuts at the top and bottom of the vertical operat-
ing pipe and rotate the pipe counterclockwise (as
viewed from the top) to decrease blade travel; then
tighten the locknuts. Do not adjust the open-stop
bolts.
(d) Remove the manual charging handle from the manual
charging shaft.
Step 23
Attach the high-voltage conductors to their respective Cir-
cuit-Switcher terminal pads using flexible-conductor con-
nections. Observe the terminal-pad loading limits
specified on the catalog drawing.
Use the following procedure for attachment:
(a) Thoroughly wire-brush the current-transfer surfaces
of each connector and immediately apply a liberal
coating of Penetrox®A (available from Burndy Corpo-
ration) or other suitable aluminum connector com-
pound to the brushed surfaces.
(b) Wire-brush each Circuit-Switcher terminal pad and
apply a coating of Penetrox A. Then bolt the connec-
tors to the terminal pads.
(c) Prepare the conductors using established procedures
and clamp them in their respective connectors.
Step 24
Remove the container from each interrupter as follows:
(a) Remove and discard the ³⁄₈—16 zinc-plated serrated
hex nuts which run the length of the container.
(b) Remove and discard the ³⁄₈—16⁷⁄₈and two
³⁄₈—161zinc-plated hex-head cap screws and flat
washers which attach the upper container-half to the
coupling end casting of the interrupter. Also remove
and discard the ³⁄₈—16⁷⁄₈and two ³⁄₈—161zinc-
plated hex-head cap screws and flat washers which
attach the upper container-half to the indicator end
casting of the interrupter.
Figure 13. Checking alignment of disconnect blade and jaw
contact.
ÇDANGER
Conductors must be de-energized and grounded in
accordance with standard system operating practice.
Failure to do so can result in serious injury or
death.
C
L
C
L
INSTALLATION — Continued
of disconect blade
of jaw-contact assembly
Disconnect-
blade tongue
contact
Jaw-contact
finger
Other manuals for 2000 series
4
This manual suits for next models
1
Table of contents
Other S&C Switch manuals

S&C
S&C Alduti-Rupter Programming manual

S&C
S&C Omni-Rupter User manual

S&C
S&C Alduti-Rupter Switches Outdoor Distribution Owner's manual

S&C
S&C Alduti-Rupter User manual

S&C
S&C Omni-Rupter Series Owner's manual

S&C
S&C Alduti-Rupter Operation and maintenance manual

S&C
S&C Alduti-Rupter User manual

S&C
S&C Alduti-Rupter Owner's manual

S&C
S&C Mark V User manual

S&C
S&C CS-1A User manual