S&S Northern ATWM Maintenance and service guide

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
ATWM—Installaon & Maintenance
A. GENERAL INFORMATION
The AT-WM is a pulse water meter, leak monitoring system that has been specically designed to help achieve the
requirements of BREEAM 2011 (BRE Environmental Assessment Method).The AT-WM system will allow designers,
M&E contractors and developers to achieve the “Credit” available to reduce the impact of water leaks that may
otherwise go undetected. The system is designed to monitor water owing through a pulse water meter. If the
volume of water reaches the pre-set limit (customer adjustable) the system can isolate the mains water pipe,
therefore liming the amount of water and leak damage.
INSTALLATION ITEMS (NOT SUPPLIED)
Wall fasteners for surface mounng (four screws)
Rubber or elastomeric washers to seal at mounng points
Semi-ush recess ange (oponal)
TOOLS REQUIRED
Drill or hole punch for electrical conduit entries
Phillips (cross-head) screwdriver
Small at-head screwdriver
STORAGE
Keep the module in a dry place prior to installaon to avoid possible damage to internal components.
B. PRODUCT INFORMATION
AT-WM—12Vdc Regulated Supply 250mA (Polarity NonSpecic) PSU supplied.
Temperature— 85oC Max
Pressure— 0.35—10Bar
Flowrates— ATWM will detect any ow rate greater than 0.5 litres per minute

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
C. WIRING & PULLING
Current IEE Regulaons: AT-WM should be installed by a competent installer, in accordance with the recommendaons
laid down by the HVCA and sound engineering pracce.
D. PLUMBING INSTALLATION
The diagrams will serve as a visual aid, but it is recommended that a competent plumber carries out the assembly and
installaon. Connect the pipe to the water meter / valve according to markings on the valve body. Apply pipe compound
sparingly to male threads only. Ensure compound does not enter valve. Avoid pipe strain by proper support and align-
ment. Type PN16 mang anges will be required on some models over 50mm.
E. HELPFUL HINTS
We recommend that AT-WM is installed with a maintenance by-pass. The water meter can be ed vercally or horizon-
tally. Note the direcon of the ow arrows marked on the water meter and valve to ensure they are ed correctly.
F. MAINTENANCE
Clean periodically depending on condions. Keep the medium owing through the water meter / valve as free from dirt
as possible. While in service, the Solenoid Valve should be operated at least once a month to ensure proper cleaning and
closing. We strongly recommend a strainer is ed prior to any meters or valves to prevent debris fouling the mecha-
nism.
G. WIRING INSTRUCTIONS

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
Plumb in the Water Meter and Solenoid Valve (if applicable) in line with the manufacturer’s instrucons. Using wiring
instrucons above, connect each Meter and Valve assembly to the controller using a shielded 2 core 1.00mm2 copper
cable. For longer runs, use a larger core size.
Power the controller using the supplied transformer and open/close the valves to check they operate correctly. Run
some water and check meter reading on Modes page has increased.The Input connecon can be made to an intruder
alarm for automac guard level switching when alarm is acvated. The Output connecons can be used to acvate an
external alarm, auto dialler or connecon to a BMS.
The AT-WM controller monitors the water owing ONE or TWO water meters or ow switches. There are two guard lev-
els, Low Guard for when the property is occupied and High Guard for unoccupied. If the maximum allowable volume of
water, or ow me is exceeded the solenoid valve can be set to automacally shut o the water supply. The controller
will emit an audible and visual alarm.
H. WATER METER & CONTROL UNIT (NO SOLENOID VALVE)
IMPORTANT NOTE: The Pulse sensor which is pre-ed to the top of the water meter is pre wired with a 1.5m cable. This
can be extended using a screened 2 core cable using 1.0mm2 up to 100m and 1.5mm2 up to 150m. The screen is im-
portant to eliminate any interference and should be connected to the “Alarm In –“
I. WATER METER & CONTROL UNIT (WITH SOLENOID VALVE UP TO 50MM)

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
J. WIRING FOR AT-RU1 RELAY UNIT DIN RAIL MOUNTABLE
AT-RU1 CONNECTIONS
Power Connecons to Relay (Mains), 230Vac supply L = Live, N = Neutral, E = Earth
Power Connecons to Relay (Relay Valve), 230Vac supply L1= Live Close, L2= Live Open, N = Neutral, E = Earth
Control Connecons from AT-WM Controller 1= V (Valve) 2=C (Common)
NOTE: Wiring should only be done by a qualied electrician
NOTE: These diagrams are shown for one water meter and one solenoid valve. If two are required, the second set should
be wired to the “Valve 2” terminals.
Diagrams shown are for one water meter/solenoid valve. When two are required, use Valve 2 terminals for the second
set.
K. OPERATING THE AT-WM FOR DAY TO DAY USE.
Push any key to wake the display which will show the Home Page, see below. The home page shows the me, date, the
level of guard and the state of the valves.
Use the keys (Up, Down, Le & Right) to navigate. Use OK buon to switch between High & Low Guard Levels. Use OK to
open and close valves. To return to Home, press (Le) at any me.
To change a numerical value press OK to select the line; (Up, Down) to change the value and OK to conrm changes. Use
the (Up, Down, Le & Right) to navigate the menu.

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
Page le and right to access other operang pages
Override will show either Start Manual Override or Cancel Manual Override.
Home This is the default screen, this screen displays date, me and system status.
Modes Use OK to switch between Normal 2 guard and single Permanent High Mode. Also displays power source and me-
ter readings.
Audit The audit page records the maximum and minimum litres of water used in a period. The period can be half hour,
one hour, guard period or 24 hours depending on system sengs.
Data will display the history of Minimum and Maximum Litres used in any 60 seconds.
Events Log displays a record of events with mes and dates.
TO TEMPORARILY OVERRIDE THE GUARD LIMITS –
From Home go le to Override. Press OK to Start Manual Override Countdown. To Cancel Override, go le again from
Home page and press OK.
The default override me is 30 minutes. This can be changed between 10 and 45 minutes. The override allows unlimited
water to ow during this period.
THE GUARD MENU
To access the guard menu push both the Up and Down keys together for 2 seconds.
HI GUARD VAL: Push OK to change and conrm the maximum value in litres/hour (default: 2)
LO GUARD VAL: As above, but for when the property is occupied (default: 50)
OVERRIDE TIME: Push OK to increase from 10 minutes to 45 minutes maximum (default: 30)
METER READINGS: Push OK, navigate to match the actual water meter reading.
DATE: Push OK to select and conrm the date. Use the Up and Down keys to adjust the date.
TIME: Push OK to select and conrm the me. Use the Up and Down keys to adjust the me.
MODE: Select mode: • DAILY - every day is the same • SEVEN DAY - day by day • WEEKEND/WEEKDAY - two sengs for
the whole week • ALARM – Automac (for systems connected to an intruder alarm)
SET HI/LO Times: Push OK to access the 7 day mer. To set the LOW GUARD start to nish periods use the navigaon
keys. If only one period is required set both 1 and 2 the same
To Excit Guard Menu, push (le) at any me
THE ENGINEERING MENU
To access the engineering menu push the le, right and down keys together for 3 seconds.
FLOW PER: Push OK to select between hourly , half hourly, guard and day metering (default: hour)
PULSE: Push OK to select between one pulse per 1 litre, or one pulse per 10 Litres and one pulse per 100 Litres (default: 1
litre)
VALVES: Push OK to select valves, None; Both; Valve 1 only; or Valve 2 only (default: Both)
METERS: Push OK to select meters, None; Both; Meter 1 only; or Meter 2 only (default: Both)
LEAK: Push OK to select
LEAK Sengs. Close all; Close Single.
CLOSE VALVE: Push OK to close the valve when a High Guard period is selected (default: No)

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
ALARM IN: Push OK to select between O, Normally open and closed. When selected this will switch between guard lev-
els In line with the intruder alarm (default: Norm Open)
ALARM OUT: On/O For connecon to BMS or other alarm (default: OFF)
RESET DEFAULTS: Push OK to reset factory default sengs.
To EXIT Engineering Menu, push (le) at any me.
SETTING THE HIGH AND LOW GUARD VALUES USING THE AUDIT PAGE
The Data page stores the Maximum value recorded in the High & Low Guard periods.
START AUTO AUDIT: (If factory set) will disable the Guard funcon, WARNING your property is not protected at all during
AUTO AUDIT.
USE DATA: At any me you can select USE DATA to transfer the Auto Audit maximum values plus 10% into the High and
Low Guard Values in the Guard Menu.
To EXIT the menu, push at any me. one low period per day with period 1 start & nish mes the same. To EXIT Guard
Menu, push (le) at any me.
L. AT-WM-C – SETTINGS GUIDE
This document should be used as an addional guide to how to set up your AquiTron ATWM Major leak detecon con-
troller. Please fully read the AT-WM installaon instrucons for informaon on installing, connecng, and navigang
around the menu system.
All values used in this guide are examples only and NOT denive sengs, your values will be dierent as required by the
property the unit is located within.
When seng up this controller please consider the protecon required. This system is primarily designed to comply with
the criteria set out in BREEAM WAT 03 to detect MAJOR LEAKS in commercial buildings.
[Any text below in brackets and italics may not strictly be necessary but are hints and/or methods used to ensure pro-
gramming is progressing correctly]
TOOLS REQUIRED
AT-WM-C
Fingers
Sengs relevant to the applicaon
There are two hidden menus used to program the unit:
Guard menu – accessed by pressing and holding for 5 seconds the up and down arrows together.
Engineering menu – accessed by pressing and holding for 5 seconds the le, right and down arrows together.
Navigate through menus – use up and down arrows to move the cursor (ashing on le hand side of the screen) through
the opons available. Once the cursor is at the opon required press OK to enter that opon. Pressing OK will either cycle
through the available opons or allow you to use the arrows to enter the seng required and press ok to go back to
menu. Pressing the L/H arrow will exit the menu back to the home screen.

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
Any seng not menoned in this guide is generally not required to setup the system and should be le as default.
Allow 30-45 minutes to program and check each unit.
If no buon is pressed the system will me out and you will have to re-enter the menu. •
If the unit has been previously setup or ‘ddled with’ we would advise starng with a factory reset. This can be
found at the boom of the engineering menu
The rst 7 steps are all to be found in the Guard menu and are mostly in logical order as you go down through the menu.
STEP 1 Set me and date – Locate and set the unit to the correct me and date. [exit menu to home screen by pressing
R/H arrow, check me and date is displaying correctly. It is important to do this rst as it aects further sengs opons]
STEP 2 HI GRD LTR – Press ok and set hi grd value. Min is 1ltr, Max is 2000ltr. This is the lower value of the two for when
the building is not expected to use as much water . [Use le and right arrows to enter higher values faster. We selected
50] Press ok to exit back to menu. [if you skipped step 1 and the building is in use, expect the unit to go into alarm now].
STEP 3 LO GRD LTR – Press ok and set lo grd value. Min is 1ltr, Max 5000000ltr. This is the higher value of the two for
when the building is expected to use the most water. [Use le and right arrows to enter higher values faster. We select-
ed 100] Press ok to exit back to menu.
STEP 4 Override me – press ok to cycle to 45. The override funcon allows you to use unlimited water for the period
entered without the unit going into alarm. Once started a countdown will begin once the period ends the system will
automacally revert to its normal sengs.
STEP 5 Meter 1 (2) –- Press ok and set to match the reading from the top of water meter 1. [Use le and right arrows to
enter higher values faster.] Press ok to exit back to menu and repeat for meter 2 if two meters are ed.
Skip me and date as we have already done these.
STEP 6 Mode – Press ok to cycle through opons available [the dierent modes are described on page 6 of this manual.
For this example we will assume daily has been selected]
STEP 7 Set HI/LO Times – Press ok to enter the set Low Guard me period screen. This is the me the building is occu-
pied. Set lines 1 and 2 the same [if you do not the system will go into alarm]. All mes out of this period are high guard.
[A value MUST be entered in this screen. If you require a value higher than 2000ltr per half hour, in eect a permanent
low guard, then we would advise seng this low period to 1 minute at midnight ie. 00.01 – 00.00. For our example we
have entered 06.00 – 18.00]. Press ok and le arrow once to exit to menu.
This is the end of the guard menu the next steps are in the engineering menu, again in order.

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com
STEP 8 Flow Per – Press ok to cycle through the opons. This is the seng the controller uses to measure the values en-
tered in steps 2 and 3. [We generally use hour or half hour as these are the most granular seng and give the most pro-
tecon. We have used half hour in this example] E.g. if you entered 100ltr the system will allow 100ltr per half hour to
pass through before going into alarm. [This is NOT at set intervals that start on the hour or half hour (12.00, 12.30, 13.00,
13.30 etc). It uses a clever algorithm to constantly monitor volume used in any period of 30 minutes].
STEP 9 Pulse – Press ok to cycle through the opons. This must match the pulse output from the connected meter(S).
[Generally smaller meters will be 1ltr per pulse and larger anged meters 10 ltrs per pulse. This informaon is normally
found on the water meter. You cannot use meters that do not have a volt free pulse of 1, 10 or 100 ltrs on this controller.
We have selected 1]
STEP 10 Valves – Press ok to cycle through opons. If a valve is ed to the system select the channel you have connect-
ed the valve to [ignore this seng if no valve ed. We selected none].
STEP 11 Meters – Press ok to cycle through opons. Select dependent on whether you have one or two meters connect-
ed. [1 meter ed use channel 1 and select 1 only, two meters ed select both. We selected both].
For 99.9% of installaons you have now nished seng up.
An overview of the system as programmed above:
Between 6am and 6pm every day up to 100ltr per half hour can be used unl an alarm
From 6pm through to 6am the next day 50ltr per half hour can be used before an alarm.
Home screen:
Are the date and me correct? [if not, your me periods will be out. Please be aware this unit does not self-adjust
between GMT and BST]
Guard: Low [assuming you are in the low guard me period, if not unit will display ‘Timer high’. It is possible to put
the unit into manual high guard by pressing ok. Press ok again to go back to programmed sengs]
Channel 1: OK [if display is ‘closed’ select channel using down buon and press ok, should display ‘changing’ then
display ‘ok’]
Channel 2: OK [as channel 1. If you selected 1 meter in step 11, no channel 2 will be displayed]
Modes Screen: Press R/H arrow once to enter
Mode: Normal [It is possible to select ‘Permanent High’ by pressing ok (this will change the guard display on the
home screen to ‘Permanent High’). If selected the unit will stay in hi guard unl reversed]
Power: should say mains [unless you are running on baery back up, in which case it will say baery]
Meter 1: Will display the amount you entered in step 5 (unless water has been used). [An easy way to check you
have the correct pulse seng is to run o some water in the building and check this reading connues to match
the reading on the top of the water meter].
Meter 2: As meter 1 above [If you selected 1 meter in step 11 no meter 2 will be displayed]
Table of contents
Other S&S Northern Controllers manuals
Popular Controllers manuals by other brands

Emerson
Emerson Dixell XW20LS Installing and operating instructions

Berker
Berker 7531 31 07 Operating and assembly instructions

Orion
Orion GPC Plus Controller General information & application guide

Siemens
Siemens SIMOCODE pro System manual

AFRISO
AFRISO RG 210 operating instructions

Di-soric
Di-soric IO-Link Device Tool V 4.0 instruction manual