Weinzierl KNX IO 511 Specification sheet

©2019 WEINZIERL ENGINEERING GmbH Page 1/15
Operation and installation manual
KNX IO 511 (1O2I)
(Art. # 5232)
Switching actuator with 1 output and 2 binary inputs
KNX IO 511 (1O2I)
Application
The KNX IO 511 (1O2I) is a compact switching actuator with 1
bi-stable output and 2 binary inputs. The actuator provides the
function for universal outputs including scene control, timer,
staircase lighting and heating valves (PWM for thermoelectric
valve drives).
The inputs can be connected to conventional switches with an
external voltage of 12 to 230 V. In ex-factory settings the inputs
are connected internally to the actuator. The actuator combined
with input B1 serves as a latching relay. Input B2 is used for zero
crossing detection.
Two push buttons and three LEDs allow a local operation and a
visualization of the device state.
In addition to the output and input channels the device includes
16 independent functions for logic or timer control.
1. Installation and Connection
The KNX IO 511 (1O2I) is designed for installation on a DIN rail
(35 mm) with a width of 1 unit (18 mm). An installation-friendly
design with pluggable screw terminals helps to reduce the cost
of commissioning. It features the following controls and displays:
This device is powered by the KNX bus. An external power
supply is not necessary.
The device is not working without bus power.
A. KNX Programming mode
The KNX programming mode is activated/deactivated either by
pressing the flushed KNX programming button ❸ or by simulta-
neously pressing the buttons ❼ and ❽.Accessing the pro-
gramming mode via the device front buttons can be enabled /
disabled via the ETS® by changing the value of Prog. mode on
device front.
When the programming mode is active, the programming LED
❷ and LED Ch/M ❺light red.
B. Manual operation and status display
The LED Ch/M ❺lights up or flashes if the device is successful-
ly powered by the KNX bus.
By pressing button A ❼long, the manual operation mode will
be entered for channel (A). This is indicated by cyclic single
flashing of LED Ch/M ❺in orange.
The actuator (channel A) can be switched on with button On ❼
and switched off with button Off ❽. The manual operation mode
can be exit by pressing the buttons (Esc) ❼und ❽simultane-
ously.
The LED A ❹is used to display the status of the channel (A). It
lights when the channel is on and is switched off when the chan-
nel is off.
By pressing button B ❽long, the manual operation mode will
be entered for channel pair B (Ch B In1/In2).This is indicated by
cyclic double flashing of LED Ch/M ❺in orange.
If manual operation of channel pair B is activated, the bus tele-
grams of In1 and In2 can be triggered by button 1 ❼and 2 ❽,
if input channel is configured by ETS.
LED 1 ❹and LED 2 ❻are used to indicate state of selected
channel pair while manual operation. They light green when the
button 1 ❼ or 2 ❽ is pressed.
The manual operation mode can be exit by pressing the buttons
(Esc) ❼und ❽simultaneously.
Summary of the states of LED Ch/M ❺:
LED Status
Meaning
LED lights green
Device is working in standard operation mode.
LED lights red
Programming mode is active.
LED flashes 1x orange
Programming mode is not active.
Manual operation is active.
Switching first channel (A)
LED flashes 2x orange
Programming mode is not active.
Manual operation is active.
Switching channel pair (B In1/In2)
LED blinks red
Programming mode is not active.
Manual operation is not active.
The device is not properly loaded e.g.
after an interrupted download.
LED blinks green
The device is currently loaded by the ETS.
EN
❶KNX bus connector
❷Programming LED
❸Button f. programming mode
❹LED On/1 (multicolor)
❺LED Ch/M (multicolor)
❻LED --/2 (multicolor)
❼Button A (On/1)
❽Button B (Off/2)
❾Pluggable screw terminals

©2019 WEINZIERL ENGINEERING GmbH Page 2/15
2. Ex-factory behavior
In ex-factory state, the binary inputs are internally connected to
the actuator channel.
By applying a voltage pulse to binary input B1, the actuator
switches over (toggle function). The device thus behaves like a
latching relay. This presetting enables the replacement of a
conventional impulse switch by the KNX IO 511 without pro-
gramming. For this function, the device must be connected to the
KNX bus voltage. The KNX IO 511 can then be programmed and
integrated into the KNX system.
Binary input B2 is configured as zero crossing detection. If the
input is connected to phase (L), the actuator switches at zero
crossing of the mains voltage. This protects the relay contacts,
especially with capacitive loads (switching power supplies / LED
lights) and increases the life time of the device. If input B2 is not
connected, the actuator switches without taking into account the
zero crossing.
Conventional latching relay KNX IO 511 (1O2I)
3. Reset to factory device settings
It is possible to reset the device to its factory settings:
Disconnect the KNX Bus connector ❶ from device
Press the KNX programming button ❸ and keep it
pressed down
Reconnect the KNX Bus connector ❶ of device
Keep the KNX programming button ❸pressed for at
least another 6 seconds
A short flashing of all LEDs (❷❹❺❻) visualizes the
successful reset of the device to factory default settings.
4. Wiring scheme
C. Pluggable screw terminals
Top connector
The top pluggable screw terminal ❾on the left terminal pin Ch
A Out are used as closer. The central terminal pin Ch A !Out
serve as opener. On the right terminal pin Ch A Cm the common
pin is contacted e.g. the voltage to be switched.
Bottom connector
The middle pin of the bottom connector ❾shall be connected to
the common wire (neutral for 230V AC and GND for DC). The
left and right pin shall be connected to the corresponding switch-
es / push buttons.
5. ETS database
The ETS database (for ETS 4.2 ETS and 5) can be downloaded
from the product website of the KNX IO 511 (1O2I)
(www.weinzierl.de) or via the KNX online catalogue.
ETS parameter dialog
The following pages and parameters are visible in the ETS.
D. Description:
The first page shows general information about the device.

©2019 WEINZIERL ENGINEERING GmbH Page 3/15
General settings:
Device name (30 Characters)
An arbitrary name can be assigned for the KNX IO 511 (1O2I).
The device name should be meaningful, e.g. „Living Room“. This
helps the clarity of the ETS project.
Send delay after bus power return
A send delay of telegrams after the return of the bus voltage can
be set via this parameter. In this case, telegrams from the device
are sent to the KNX bus in a delayed manner by the set time.
This results in a reduction of the bus load at a bus power return.
Other functions such as receiving telegrams of switching opera-
tions of the actuator are not affected by this parameter.
Prog. mode on device front
In addition to the normal programming button ❸the device
allows activating the programming mode on the device front
without opening the switchboard cover. The programming mode
can be activated and deactivated via pressing simultaneously
both buttons ❼and ❽.
This feature can be enabled and disabled via the parameter
“Prog. mode on device front”. The recessed programming button
❸(next to the Programming LED ❷) is always enabled and
not influenced by this parameter.
Manual operation on device
This parameter is used to configure the manual operation on the
device. The manual operation mode can be disabled or activated
(with or without time limitation). The time limit defines the dura-
tion until the automatic return from the manual operation mode
back into the normal operating mode.
The device is in normal operating mode when the manual control
is not active. In the manual operating mode, received switching
telegrams are ignored. When the manual operation mode is
terminated (after expiry of the time limit or manually), the last
state of the outputs remains, until a new switching telegram is
received again.
The following options are selectable:
- Disabled
- Enabled with time limit 1 min
- Enabled with time limit 10 min
- Enabled with time limit 30 min
- Enabled without time limit
Heartbeat
Cyclic sending of values to the KNX-Bus, to indicate that the
device is operational. For the Cycle time values between 1 min
and 24h are selectable.
Group Object
Type KNX
Size
Direction
GO 1 Heartbeat - Trigger
1.001
1 Bit
To KNX
Long button press after
The time for detection of a long button press can be set here,
this time is valid for all input channels.
E. Actuator 1: General:
Name (30 Characters)
An arbitrary name can be assigned for the channel. However,
this should be clear and meaningful, this makes it easier to work
with the associated group objects, because the given name is
displayed there as a label. If no name is assigned, the group
objects are named “Actuator A: …”.
Function
This parameter defines the functionality of the actuator.
The following options are selectable:
- Disabled
- Universal output
- On/Off delay
- Staircase function
- Valve actuator (PWM for thermal servo)
A more detailed description of the functions can be found in the
individual function descriptions under Function (…).
If the actuator is not “Disabled”, the following parameters are
displayed:
Behavior on bus power failure
The behavior which is held at the output during the bus power
failure can be configured here.
The following options are selectable:
- No reaction
- Switch on
- Switch off
Behavior after bus power return
Here the behavior of the output after bus power return can be
configured. This behavior will be set after every device restart
(e.g. also on restart after ETS download).
The following options are selectable:
- No reaction
- Switch on
- Switch off
- State like before bus power failure

©2019 WEINZIERL ENGINEERING GmbH Page 4/15
Send state
This parameter defines the behavior of the state objects:
- Disabled
State objects are deactivated and not displayed
- Only on read
State objects send only on request
- On change
State objects send on value change
- Cyclic and on change
State objects send cyclically and on value change
Group Object
Type KNX
Size
Direction
GO 18 Actuator 1: Output - State
1.001
1 Bit
To KNX
GO 19 Actuator 1: Valve actuator (PWM)
–State*
5.001
1 Byte
To KNX
* if valve actuator was selected
Time for cyclic state
Is selected state object “Cyclic and on change“, in this parameter
the cycle time can be set.
Lock function
With this parameter the lock function can be enabled. If this
functionality is activated, the associated group objects as well as
the parameter page “Actuator 1: Lock function” are displayed for
further configuration. If the lock has been activated via the group
object "Lock", the received switching telegrams are not execut-
ed.
In addition to the lock object, there is also a priority object, which
can be switched independently of the lock. Thus, it is possible to
set an output state without affecting other functions.
Group Object
Type KNX
Size
Direction
GO 15 Actuator 1: Lock - Activate
1.001
1 Bit
From KNX
GO 16 Actuator 1: Prior. output - Switch
1.001
1 Bit
From KNX
Example of the priority object:
In the case of events in public buildings or in restaurants, the
normal operation can be set into an inoperative state by the lock
group object. Thus it is possible to lock during the lecture or
concert, switches that are accessible to unauthorized persons, in
order to prevent unmeant switching. Nevertheless, the individual
lamps can controlled by use of the priority object without cancel-
ing the lock.
F. Lock function:
Polarity of object
This parameter defines, if the lock should be activated by receiv-
ing a 1 or by receiving a 0.
The following options are selectable:
- Lock active on 1
- Lock active on 0
Behavior on start
This parameter configures, which state the output should set, if
the lock activates.
The following options are selectable:
- No reaction
- Switch on
- Switch of
This output state can still be changed by the priority object.
Behavior at end
This parameter defines, which state the output should set, if the
lock deactivates.
The following options are selectable:
- No reaction
- Switch on
- Switch off
- State before lock
- State without lock
State before lock:
This restores the original state before the lock was activated.
Switching telegrams received during the lock are ignored.
State without lock:
Here the state of the last received switching telegram is restored.
This takes into account the received switching telegrams during
the lock. Thus, when the lock is deactivated, the last received
switching telegram is set.
Function (Universal output)
If the universal output is selected on the parameter page "Actua-
tor 1: General", the actuator can be used as a switching output.
A parameter for the scene function is also displayed.
Group Object
Type KNX
Size
Direction
GO 11 Actuator 1: Output - Switch
1.001
1 Bit
From KNX
Scene function
With this parameter the scene function can be enabled or disa-
bled. If this functionality is enabled, the respective group object
as well as the parameter page "Actuator 1: Scene function" are
displayed for further configuration of scenes 1-16.
Group Object
Type KNX
Size
Direction
GO 12 Actuator 1: Scene –Activ./Lrn.
18.001
1 Bit
From KNX

©2019 WEINZIERL ENGINEERING GmbH Page 5/15
G. Scene function:
Scene 1-16
These parameters can be used to configure the state, which is
set at the output when the respective scene is executed.
The following options are selectable:
- No reaction
- Switch on
- Switch off
- Learnable
Learnable:
By using a scene control telegram, the current state at the output
can be saved for the respective scene. This allows the user to
customize the scene without ETS download.
Number
This parameter sets any scene number between 1 and 64 to the
scene. There must not configured any scene numbers twice.
Function (On/Off delay)
If the ON/OFF delay is selected on the parameter page "Actuator
1: General", delayed switching times can be configured. The
"Actuator 1: On/Off Delay" parameter page is displayed for this
purpose.
Group Object
Type KNX
Size
Direction
GO 11 Actuator 1: Output - Switch
1.001
1 Bit
From KNX
H. On/Off delay:
On delay time
The duration of the switch-on delay is configured in this parame-
ter.
Input -------1------------------0----------
Output -------|-T-1--------------0----------
Off delay time
The duration of the switch-off delay is configured in this parame-
ter.
Input -------1------------------0----------
Output -------1------------------|-T-0------
Retriggerable
If these parameters are activated, the respective delay time is
restarted upon receipt of the corresponding switching signal.
Function (Staircase function)
If the staircase function is selected on the parameter page "Ac-
tuator 1: General", a group object for the staircase function
appears in addition to the normal switching object. Via the addi-
tional parameter page "Actuator 1: Staircase function" this func-
tion can be configured.
Group Object
Type KNX
Size
Direction
GO 11 Actuator 1: Output - Switch
1.001
1 Bit
From KNX
GO 13 Actuator 1: Staircase function -
Trigger
1.010
1 Bit
From KNX
I. Staircase function:
Switch of time
The time for which the output is activated after an ON telegram
(object of the staircase function) has been received, can set in
this parameter.
Input -------1------------------0----------
Output -------1-T-0-------------------------
Retriggerable
This parameter can be used to set whether the follow-up time is
to be restarted when an ON telegram is received on the object of
the staircase function.
Reaction on ‘OFF’ telegram
This parameter can be used to set whether an OFF telegram on
the object of the staircase function should be processed or ig-
nored.

©2019 WEINZIERL ENGINEERING GmbH Page 6/15
Time for warning before switch off
The time between pre-warning and deactivation is configured, or
the pre-warning is deactivated with this parameter. If the pre-
warning time is longer than the actual follow-up time, no pre-
warning is carried out.
Time of interrupt
The pre-warning is indicated by a brief interruption (switch off ->
switch on). The duration of this interrupt is configured in this
parameter.
Note: LED lamps often have a long follow-up time, in which the
lamp still lights even though it is already switched off. With such
lamps longer interrupt times must be set to generate a "visible"
interruption.
Function (Valve actuator)
The function valve actuator is foreseen to control thermoelectric
valve drives which are used for floor heating but also for radia-
tors. It maps the continuous position (0% - 100%) to an ongoing
On/Off sequence called PWM (pulse width modulation) signal.
If the valve actuator is selected on the parameter page "Actuator
1: General", a group object for the valve actuator appears in-
stead of the normal switching object. This allows the current
PWM at the output to be set via KNX (0% - 100%). An additional
parameter page "Actuator 1: Valve actuator" appears for the
configuration of the valve actuator.
The received control value is saved automatically by the device,
to continue faultless after a possible bus power loss.
Group Object
Type KNX
Size
Direction
GO 14 Actuator 1: Valve actuator (PWM)
–Control value
5.001
1 Byte
From KNX
J. Valve actuator:
Cyclic time (PWM)
The cyclic time of the PWM, which is used to control a servo
drive, is configured with this parameter. One cycle involves a
time range in which the output is switched on and one in which
the output is switched off. The cyclic time corresponds to the
period between two rising edges (state change at the output
from OFF to ON). The longer the flow of the heating circuit (tube
/ pipe length), the higher the cyclic time should be set.
Note: Typical thermal servo require several minutes for a 100%
valve change.
Maximum control value (PWM)
This parameter can be used to limit the maximum control value.
The control value is expressed in percent and defines the period
during which the output is switched on in one cycle.
Example:
Cyclic time = 10 Min.
Maximum control value (PWM) = 80 %
Maximal output state = ON - 8 min / OFF - 2 min
Stuck protection
With the stuck protection, it is intended to prevent the valve from
being damaged by corrosion or calcification, that it can no longer
be moved. In case stuck protection is enabled, this is only trig-
gered if the value is permanently 0 % or 100 %. On every other
control value the servo already moves, so there is no need for a
stuck protection.
Control value 0% Open servo for the set time
Control value 100%Close servo for the set time
In case the valve is not allowed to open, the stuck protection
must be disabled.
Execution time
If the stuck protection is activated, this parameter is used to set
the duration of the state change.
Monitoring interval
If the stuck protection is activated, this parameter sets the moni-
toring interval. If the state of the output remains unchanged for
this time, the lock protection is triggered.
Protection on missing control value
This parameter enables the protection function on missing con-
trol value telegrams. This is necessary in order to prevent un-
wanted and uncontrolled overheating or cooling down of the
room, when the control value is missing.
Protection takes effect, as soon as no telegrams are received
from the controller over a longer period of time. As soon as this
extended telegram pause has occurred, it can be assumed that
the corresponding controller has failed or the connection be-
tween the controller and the valve actuator has been interrupted.
Protection control value (PWM)
If the protection on missing control value is enabled, this pa-
rameter sets a protection control value. This configured PWM
value will set the output, if the protection is active.
As soon as telegrams from the controller are received again, the
protection control value (PWM) is overwritten by the received
value. The protection does not react again, until the waiting time
in the set monitoring interval is exceeded between individual
telegrams.
Monitoring interval
If the protection on missing control value is enabled, this pa-
rameter sets the monitoring interval. If no further telegram is
received by the device during this time, the protection function
takes effect.

©2019 WEINZIERL ENGINEERING GmbH Page 7/15
Lock function (with valve actuator)
With this parameter the lock function can be disabled or enabled.
If this functionality is activated, the associated group objects as
well as the parameter page “Actuator 1: Lock function” are dis-
played for further configuration. If the lock has been activated via
the group object "Lock", the received switching telegrams are not
executed.
In addition to the lock object, there is also a priority object, which
can be used to set a control value independently of the lock.
Thus, it is possible to set an output PWM without affecting other
functions.
When the lock is ended, the last received value (not priority
object) is represented as PWM at the output.
Group Object
Type KNX
Size
Direction
GO 15 Actuator 1: Lock - Activate
1.001
1 Bit
From KNX
GO 17 Actuator 1: Prior. valve actuator
(PWM) –Control value
5.001
1 Byte
From KNX
K. Lock function:
Polarity of object
This parameter defines, if the lock should be activated by receiv-
ing a 1 or by receiving a 0.
The following options are selectable:
- Lock active on 1
- Lock active on 0
Behavior on start
This parameter defines, which behavior the output should repre-
sent, if the lock activates.
The following options are selectable:
- No reaction
- Value
No reaction:
The PWM value remains as to begin of the lock function.
Value:
When the lock is activated, a defined PWM value is represented
on the output.
Control value (PWM)
If a defined PWM value should be set to the output when the
lock is activated, this value can be set with this parameter.
L. Input B1: General
Name (30 Characters)
An arbitrary name can be assigned for the channel. However,
this should be clear and meaningful, this makes it easier to work
with the associated group objects, because the given name is
displayed there as a label. If no name is assigned, the group
objects are named “Input …”.with the channel number, which is
also used in this manual. The 1st binary input will be described
below, the functioning of the other channel is according to the
1st.
Function
This parameter defines the functionality of the connected con-
tact. The following options are selectable:
- Disabled
- Switching
- Dimming
- Shutter
- Send value
- Scene
- Impulse counter
- Latching relay, toggle INTERNAL*
- Latching relay, on INTERNAL*
- Latching relay, off INTERNAL*
- Zero crossing detection INTERNAL**
*An internal connection from the binary input to the actuator. In
this case there will be no telegram on the bus, instead directly
the actuator is switched on, off or toggled. With this toggle func-
tion it´s possible, to replace a latching relay with the KNX IO 511
(1O2I) and used all existing wiring, without configuring any new
KNX group addresses at the device.
**An internal connection from the binary input to the actuator to
switch the relay in the zero crossing at 100V –230V / 50Hz –
60Hz. This treats the conducts of the relay wit care and thus
increases the lifetime of the relay. In case that the zero crossing
cannot detected identically e.g. the phases is not connected to
the pin, the relay is switched immediately, like the function is not
selected.
ATTENTION: The zero crossing detection must not be used from
several cannels at the same time!

©2019 WEINZIERL ENGINEERING GmbH Page 8/15
A more detailed description of the functions can be found in the
individual function descriptions.
M. Function „Switching, Dimming, Shutter, Send value,
Scene“
If an input function of a channel is selected, the following param-
eters are displayed:
Type
The mode of operation of the contact connected to the input
channel can be configured here:
- Normally open contact
- Normally closed contact
Lock function
With this parameter the lock function can be enabled. If this
functionality is activated, the associated group objects as well as
the parameter page “Input B1: Lock function” are displayed for
further configuration. If the lock has been activated via the group
object, no telegrams are triggered by state changes of the con-
nected contact.
Group Object
Type KNX
Size
Direction
GO 26 Input B1: Lock - Activate
1.001
1 Bit
From KNX
N. Input B1: Lock function
Polarity of object
This parameter defines, if the lock should be activated by receiv-
ing a 1 or by receiving a 0.
The following options are selectable:
- Lock active on 1
- Lock active on 0
Behavior of (…) on start
The telegram can be configured here, which is sent when the
lock is activated.
Behavior of (…) at end
The telegram can be configured here, which is sent when the
lock is deactivated.
O. Function „Impulse counter“
If the impulse counter function is selected, further parameters
are displayed in the general settings of the input channel. Here,
the general settings of the impulse counter are made, a scaled
counter and/or counter of the rate of change must also be se-
lected.
Input signal
Here it can be selected whether DC or alternating voltage is
applied to the binary input.
Count on
This parameter can be used to determine whether the value of
the counter is increased at the rising or falling edge at the input
Scaled counter (e.g. [kWh])
Here, the scaled counter can be activated, the parameter page
"Scaled counter" is displayed when activated.
Rate of change (e.g. [kW], [m/s], [km/h])
The counter for a rate of change can be activated here. If acti-
vated, the "Rate of change" parameter page is displayed.
P. Input B1: Switching
If the switching function is selected, up to 2 binary switching
telegrams can be sent via the following objects:
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Output a –Switch
1.001
1 Bit
To KNX
GO 22 Input B1: Output b –Switch
1.001
1 Bit
To KNX
Output b is only visible when activated by parameter.
User control
The parameter “User control” determines whether telegrams are
sent when the input is changed (e.g. key switches) or when the
input is operated short/long (e.g. switching/dimming switches).

©2019 WEINZIERL ENGINEERING GmbH Page 9/15
Function of (…) on press / short press
Function of (…) on release / long press
It is selectable for each object, which telegram is sent on open-
ing/closing the contact or on short/long button press.
- No reaction
- Switch on
- Switch off
- Toggle
Output b
Here you can show/hide the parameters and the object for out-
put b.
Q. Input B1: Dimming
On selection of function Dimming following objects are visible:
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Dimming on/off –Switch
1.001
1 Bit
To KNX
GO 22 Input B1: Dimming relative –
Brighter/Darker
3.007
4 Bit
To KNX
Dimming function
The dimming function parameter determines whether only one
switching / dimming direction or 1-button control is to be used:
- On / Dim brighter
- Off / Dim darker
- Toggle direction
If the input detects a short button press, a switching telegram is
sent via object 21. On long button press, a relative dimming is
sent over the entire dimming range to object 22. When releasing
after long button press, a dimming-stop telegram is sent via
object 22.
The time for detection of a long button press can be set in the
general parameters and is valid for all channels.
R. Input B1: Shutter
On selection of Shutter function following objects are visible:
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Drive start –Up/Down
1.008
1 Bit
To KNX
GO 22 Input B1: Drive stop –Step/Stop
1.007
1 Bit
To KNX
Shutter function
The “Shutter function” parameter determines whether only one
shutter direction or 1-button control is to be used:
- Up / Step-Stop
- Down / Step-Stop
- Toggle direction
User control
The parameter “User control” determines the sending of tele-
grams on short and long button press:
- Long = Drive / Short = Step/Stop
Long button press: Drive command via object 21.
Short button press: Stop/step command via object 22
- Short = Drive / Short = Step/Stop
Alternately drive command via object 21 und stop/step
command via object 22 on short button press, long
button press is not evaluated
- Pressed = Drive / Release = Stop
On button press drive command via object 21, on re-
leasing the button stop/step command via object 22
The time for detection of a long button press can be set in the
general parameters and is valid for all channels.
S. Input B1: Send value
If function Send value is selected, the following telegrams can be
sent at button press:
- 1 byte - Percent value
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send percent value (1
byte) –Set value
5.001
1 Byte
To KNX
- 1 byte - Integer value
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send integer value (1
byte) –Set value
5.010
1 Byte
To KNX
- 2 byte - Integer value
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send integer value (2
byte) –Set value
7.001
2 Byte
To KNX
- 2 byte - Float value
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send float value (2
byte) –Set value
9.001
2 Byte
To KNX
- 3 byte - RGB value
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send RGB color value
(3 byte) –Set value
232.600
3 Byte
To KNX

©2019 WEINZIERL ENGINEERING GmbH Page 10/15
- 14 byte - ASCII string
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send ASCII string (14
byte) –Set value
16.000
14
Byte
To KNX
- Shutter
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send blind position –Set
position
5.001
1 Byte
To KNX
GO 22 Input B1: Send slat position –Set
position
5.001
1 Byte
To KNX
A field for entering the values to be sent is displayed, as well as
the objects appropriate to the selected type.
If the shutter is selected as the value to be sent, height is sent on
button press, lamella is sent on releasing the button, if the re-
spective value is used.
T. Input B1: Scene
On selection of Scene function the following object is visible:
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Scene –Activ./Lrn.
18.001
1 Byte
To KNX
Scene position 1 - 8
For each position, scene 1 –64 can be activated.
If only one scene position is activated, it is sent on short button
press.
If several scene positions are used, the activated positions are
switched through with each short button press.
Reset scene position
The behavior for selection and transmission of the scene posi-
tions can be determined via the parameter "Reset scene posi-
tion":
- Never
Starting with the first scene position, the next scene
position of the list is sent with each short button press,
after the last scene position has been sent, the list
starts again from the beginning.
- After execution
Beginning with the first scene position, each short but-
ton press switches the scene position by one position
within the execution delay, at the end of the execution
delay, the current scene position is sent
- 5 Sec. - 10 Min.
On each button press the configured delay time is
started.
Starting with the first scene position, the next scene
position of the list is sent with each short button press,
after the last scene position has been sent, the list
starts again from the beginning.
After the delay time has expired, the list starts again at
the first scene position on the next short button press.
When the lock function is used, the scene position is always
reset when unlocking.
Condition on long/very long button press
It is also possible to select how a long and very long button
press is to be treated:
- No reaction
- Save last scene
A telegram for "save scene" with the last sent scene is
triggered.
- Send scene
The scene configured in the appearing parameter is
sent.
- Reset position
This function is used to override the behavior as set in
the "Reset scene position" parameter.
The duration of time for detecting a very long button press is
twice the time for detecting a long button press, as it is parame-
terized in the general settings.
U. Input B1: Scaled counter
This counter can be used to count values on input impulses,
where an integer value or a floating-point value can be selected
as a counter variable. With this function, e.g. Electrical energy
can be counted directly and sent to the bus via an object.
Scaling factor (Value per pulse)
Here, a floating-point value is to be entered. It determines the
value by which the counter value is increased per pulse.
Datapoint type
The datapoint type of output object of the counter variable can
be selected here:
- Integer (32 Bit) –DPT 13
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Counter –Value
13.013
4 Byte
To KNX
- Float (16 Bit) –DPT 9
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Counter –Value
9.024
2 Byte
To KNX
- Float (32 Bit) –DPT 14
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Counter –Value
14.056
4 Byte
To KNX

©2019 WEINZIERL ENGINEERING GmbH Page 11/15
Send condition
This parameter can be used to determine how the current coun-
ter value is to be sent:
- On read
No independent sending of the counter value by the
device. To read the counter value, the read-flag of the
group object has to be set.
- On change
An additional parameter is displayed to select the min-
imal delta from the last sent value for sending a new
counter value
- Cyclically
An additional parameter is displayed to configure the
sending frequency of the counter variable.
- On change and cyclically
Both sending conditions are active.
If the counter is locked by the object, also cyclic sending is
stopped.
Monitoring limit value
When limit monitoring is activated, the following object is dis-
played:
Group Object
Type KNX
Size
Direction
GO 22 Input B1: Counter threshold –State
1.002
1 Bit
To KNX
When limit monitoring is activated, the following parameters are
displayed:
Limit value
Here you can edit the checked limit value. The data-
point type is the same as the counter value.
Behavior on reaching limit value (object)
Here it is possible to determine whether a 0 or a 1 is
sent via the object “Counter threshold –State” when
the limit value is reached.
Behavior on reaching limit value (counter)
In addition to the limit value itself, it is possible to de-
termine the behavior of the counter when the limit val-
ue is reached:
- Counter continue
Counter value continues increasing on ever
pulse
- Counter reset and continue
Counter value is reset to 0 and continues in-
creasing on ever pulse
- Counter stop
Counter value stays on limit value and must
be reset by object
Send on device restart
It can be determined with this parameter whether the counter
value should be sent when the device is restarted.
Reset via object
If this function is activated, the following object appears:
Group Object
Type KNX
Size
Direction
GO 25 Input B1: Reset –Trigger
1.017
1 Bit
From KNX
When a telegram is received via this object, the current count
values are reset to 0.
Reset after ETS download
If this parameter is activated, the counter values are reset to 0
after device reset (e.g. after ETS download), otherwise they are
retained.
Lock function
The lock function can be activated or deactivated here. If this
functionality is activated, the following group object appears, as
well as the parameter page "Lock function" for detailed configu-
ration.
Group Object
Type KNX
Size
Direction
GO 26 Input B1: Lock –Activate
1.001
1 Bit
From KNX
If the lock has been activated via the group object, state changes
at the input do not cause an increase of the counter variable.
V. Input B1: Lock function
Polarity of object
This parameter can be used to determine how the lock is to be
activated, either by receiving a 1 or a 0. The corresponding
telegram disables the lock again.
Behavior on start of lock
With this parameter the behavior of the counter can be config-
ured when the lock is activated:
- Counter stop
- Counter stop and reset
Behavior on end of lock
With this parameter the behavior of the counter can be config-
ured when the lock is deactivated:
- Counter continue
- Counter reset and continue

©2019 WEINZIERL ENGINEERING GmbH Page 12/15
W. Input B1: Rate of change
This counter is used to connect devices to the bus where the
rate of change is critical within a time interval, e.g. an anemome-
ter.
Scaling factor (Value per delta in base time span)
A floating-point value is to be entered here. It determines the
value by which the counter value is increased on every pulse
Time base
Here the time base of the rate of change can be specified:
- Pulses per second (e.g. [m/s], [km/h])
Value from parameter Scaling factor is multiplied by 1
- Pulses per hour (e.g. [kW])
Value from parameter Scaling factor is multiplied by
3600
Measurement time span
The measurement time span determines how quickly the counter
can react to changes. Therefore, a short sample rate should be
selected for fast processes (e.g. anemometer).
The rate of change is calculated using the 3 parameters men-
tioned above:
The device saves several meter readings per measurement
interval, scales it with the scaling factor * time base and divides it
by the measuring interval.
Datapoint type
The datapoint type of output object of the counter variable can
be selected here:
- Floating point (16 Bit) - DPT 9
Group Object
Type KNX
Size
Direction
GO 23 Input B1: Rate of change –Value
9.024
2 Byte
To KNX
- Floating point (32 Bit) - DPT 14
Group Object
Type KNX
Size
Direction
GO 23 Input B1: Rate of change –Value
14.056
4 Byte
To KNX
Send condition
This parameter can be used to determine how the current coun-
ter value is to be sent:
- On read
No independent sending of the counter value by the
device. To read the counter value, the read-flag of the
group object has to be set.
- On change
An additional parameter is displayed to select the min-
imal delta from the last sent value for sending a new
counter value
- Cyclically
An additional parameter is displayed to configure the
sending frequency of the counter variable.
- On change and cyclically
Both sending conditions are active.
Monitoring limit value
When limit monitoring is activated, the following object is dis-
played:
Group Object
Type KNX
Size
Direction
GO 24 Input B1: Rate threshold –State
1.002
1 Bit
To KNX
When limit monitoring is activated, the following parameters are
displayed:
Limit value
Here you can edit the checked limit value. The data-
point type is the same as rate of change value.
Behavior on exceeding limit value
In addition to the limit value itself, it is possible to de-
termine whether the counter should transmit 0 or 1 via
the object if the limit value is exceeded.
Behavior on going below limit value
Here it is possible to determine whether the counter
should transmit 0 or 1 via the object if the counter vari-
able goes under limit value.
Example: Electricity meter with S0 interface
From the data sheet of the electricity meter it can be seen that
the device delivers 500 pulses per kWh. A device with constant
power of 1kW is connected to this current meter for one hour.
The scaled counter measures the energy consumed:
Scaling factor: 1 / 500 = 0.002 -> Output in
kWh
The counter for the rate of change measures the current power:
Scaling factor:
- Output in kW: 1/500 = 0.002
- Output in W: 1/500 * 1000 = 2
Time base: Pulses per hour
Measurement time span: 300 s
Example: Anemometer
From the data sheet of the electricity meter it can be seen that
the device delivers 4 pulses/s at a wind speed of 1 m/s.
The counter for the rate of change measures the wind speed:
Scaling factor:
- Output in m/s: 1/4 = 0.25
- Output in km/h: 1/4 * 3.6 = 0.9
Time base: Pulses per second
Measurement time span: 10 s

©2019 WEINZIERL ENGINEERING GmbH Page 13/15
X. Logic / Timer
Function 1 - 16
These channels contain additional functions such as timing and
logic. All these 16 additional functions are identical.
The following options are selectable:
- Disabled
- Timer
- Logic
Function type (Disabled)
If the function type is set to "Disabled", no timer or logic specific
parameters and group objects are available.
Function type (Timer)
The timer-specific parameters and group objects are available.
Function type (Logic)
The logic-specific parameters and group objects are available.
Note: These additional logic and timer functions can be linked to
one another by means of the associated group objects. This also
allows to create complex structures. For this purpose, the output
of a function is set to the same group address as the input of the
next function.
Y. Function 1 –16 (Timer)
Function name (10 Characters)
The function name can be chosen freely.
The name is visible in the group object entry in the ETS soft-
ware. This makes it easier to work with the associated group
objects, because the given name is displayed there as a label.
Timer type (Switch-on delay)
A timer that switches ON after duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’ (Not inverted / Inverted).
Input -------1------------------0----------
Output -------|-T-1--------------0----------
Timer type (Switch-off delay)
A timer that switches OFF after duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’. (Not inverted / Inverted)
Input -------1------------------0----------
Output -------1------------------|-T-0------
Group Object
Type KNX
Size
Direction
Timer –Switch-on delayed - Input
1.002
1 Bit
From KNX
Timer –Switch-on delayed - Output
1.002
1 Bit
To KNX
Group Object
Type KNX
Size
Direction
Timer –Switch-off delayed - Input
1.002
1 Bit
From KNX
Timer –Switch-off delayed - Output
1.002
1 Bit
To KNX

©2019 WEINZIERL ENGINEERING GmbH Page 14/15
Timer type (Switch-on and -off delay)
A timer that switches ON and OFF after duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’. (Not inverted / Inverted)
Input -------1------------------0----------
Output -------|-T-1--------------|-T-0------
Timer type (Impulse (Staircase))
Timer with impulse that –after being switched ON –automati-
cally switches OFF after a defined duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’. (Not inverted / Inverted)
Input -------1------------------0----------
Output -------1-T-0-------------------------
Each timer can be stopped by sending the opposite val-
ue to its input group object.
For example:
An already started switch on timer can be stopped by
sending OFF (0) to its input group object.
Z. Function 1 –16 (Logic)
Function name (10 Characters)
The function name can be chosen freely.
The name is visible in the group object entry in the ETS soft-
ware. This makes it easier to work with the associated group
objects, because the given name is displayed there as a label.
Gate type (AND gate)
The output is triggered on (1), if both inputs are switched on (1).
Gate type (OR gate)
The output is triggered on (1), if one or both inputs are switched
on (1).
Gate type (XOR gate)
The output is triggered on (1), if the two inputs are not equal.
Gate type (NAND gate)
The output is triggered on (1), if one or both inputs are switched
off (0).
Gate type (NOR gate)
The output is triggered on (1), if both inputs are switched off (0).
Gate type (XNOR gate)
The output is triggered on (1), if both inputs are equal.
Gate type (INVERTER)
Input on (1) is converted into output off (0). Input off (0) is con-
verted into output on (1).
Group Object
Type KNX
Size
Direction
Timer –Switch-on/off delayed - Input
1.002
1 Bit
From KNX
Timer –Switch-on/off delayed - Output
1.002
1 Bit
To KNX
Group Object
Type
KNX
Size
Direction
Timer –Switch-impulse (staircase) - Input
1.002
1 Bit
From KNX
Timer –Switch-impulse (staircase) - Output
1.002
1 Bit
To KNX
Group Object
Type KNX
Size
Direction
Logic –Gate input A - Input
1.002
1 Bit
From KNX
Logic –Gate input B - Input
1.002
1 Bit
From KNX
Logic –Gate output –Output
1.002
1 Bit
To KNX
Group Object
Type KNX
Size
Direction
Logic –Gate input - Input
1.002
1 Bit
From KNX
Logic –Gate output –Output
1.002
1 Bit
To KNX

©2019 WEINZIERL ENGINEERING GmbH Page 15/15
WARNING
The device must be mounted and commissioned by
an authorized electrician.
The prevailing safety rules must be heeded.
The device must not be opened.
For planning and construction of electric installa-
tions, the relevant guidelines, regulations and
standards of the respective country are to be con-
sidered.
The device is a permanently connected equipment:
A readily accessible disconnect device shall be in-
corporated external to the equipment.
The installation requires a 16 A fuse for external
overcurrent protection.
The power rating is indicated on the side of the
product.
ETS4/5 Database
www.weinzierl.de/en/products/511/ets4
Datasheet
www.weinzierl.de/en/products/511/datasheet
CE Declaration
www.weinzierl.de/en/products/511/ce-declaration
Weinzierl Engineering GmbH
D-84508 Burgkirchen / Alz
Germany
www.weinzierl.de
2019/03/05
Table of contents
Other Weinzierl Controllers manuals

Weinzierl
Weinzierl 5374 Specification sheet

Weinzierl
Weinzierl KNX IO 532 Specification sheet

Weinzierl
Weinzierl KNX IO 534 (4D) Specification sheet

Weinzierl
Weinzierl KNX IO 510.1 secure Specification sheet

Weinzierl
Weinzierl KNX IP LineMaster 760 Specification sheet

Weinzierl
Weinzierl KNX TP Push Button 420 secure Specification sheet
Popular Controllers manuals by other brands

Altronic
Altronic EPC-250 Installation and operating instructions

West Penn Wire
West Penn Wire AV-IP-NC811 Operation manual

Advantech
Advantech AMAX-1220 Series user manual

QuietCool
QuietCool IT-AC-KIT installation guide

ActronAir
ActronAir QUE QZW-100 Installation and user manual

Vemer
Vemer AHT user manual