Hycontrol REFLEX User manual

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 1
REFLEX/SCANFLEX
PROGRAMMABLE LEVEL
CONTROLLER
INSTRUCTION MANUAL
Hycontrol Limited
Larchwood House, Orchard Street
Redditch, Worcestershire. B98 7DP
Tel: (01527) 406800 Fax: (01527) 406810
Elect. Iss. 01

Ref: INDEX - REFLEX/SCANFLEX MANUAL
EDITION 1: JYLY ’97
REFLEX/SCANFLEX
PROGRAMMABLE LEVEL CONTROL SYSTEM
INDEX
I n t r o d u c t i o n 1
Installation & Wiring - Single point 2 - 3
- Multipoint 4 - 11
Pre-Start Guide 12 - 13
Programming - Principles & Definitions 14 - 19
- Parameter Index 20
- Parameter Definitions 21 - 33
Programme Examples 34 - 36
Fault Finding & Commissioning 37 - 47
APPENDIX 1 - Transducer Specification 48 - 54
- Temperature Sensor 55
APPENDIX 2 - Reflex Description & Specification 56 - 57
- Scanflex Multiplexor SM-10 58 - 61
- Scanflex Relay Module SR-10 62 - 64
- Scanflex Analogue Module SA-10 65 - 67
APPENDIX 3 - Linearisation of Vessels 68 - 70
APPENDIX 4 - Parameter Settings 71 - 72

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 1
REFLEX/SCANFLEX
PROGRAMMABLE LEVEL CTROL SYSTEM
INTRODUCTION
The REFLEX/SCANFLEX Programmable Level Controller is capable of monitoring the level
of liquids, powders and solids in vessels up to 50 metres deep, depending on the type of
material they contain.
The instrument is programmed by the user, who can select either;
Single point monitoring (REFLEX mode) for one transducer or
Multipoint monitoring (SCANFLEX mode) for up to 10 transducers.
The REFLEX/SCANFLEX will operate with either short range transducer of the RXV15
family or long range transducer of the RXM19 family.
The principle of operation of the REFLEX/SCANFLEX system is to use ultrasonic pulses
which are transmitted directly, or via a Multiplexor, to the transducer mounted at each
measurement point. Echoes are reflected off the surface of the material being monitored, back
to the transducer.
The time period between transmission and reception of the echo is directly proportional to the
distance between the transducer and the surface being monitored. A microcontroller computes
this time period for all echoes received and analyses them to determine which is the correct
reflection from the material surface. It uses this data as the basis for giving control outputs and
displays in usable engineering units.
REFLEX/SCANFLEX is capable of the following functions:
Level Measurement
Volume Measurement
Distance Measurement
When used as a REFLEX single point instrument the controller is connected directly to the
transducer.
When used as a SCANFLEX in its multipoint mode the controller is connected to the
transducers via a Multiplexor. Additionally, relay and analogue output modules can be added
to the system and individually programmed for each point.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 2
INSTALLATION
REFLEX - AS A SINGLE POINT INSTRUMENT
Transceiver Mounting
Undo the 6 quarter turn screws on the front panel and open the hinged door to expose the
mounting holes.
Mount the unit on a flat surface and secure it via the 4 mounting holes moulded in the
enclosure. DO NOT use excessive force when tightening the fixings and avoid any distortion
of the enclosure.
Ensure that the mounting surface is not subject to vibration and is not in close proximity to
high voltage cables, contactors or drive controls. The unit should not be mounted in a confined
space where temperatures may exceed the normal working temperature. If the unit is mounted
outside it must be protected from direct sunlight or severe weather conditions.
Remove the required number of hexagon blanking plugs from the bottom of the enclosure and
replace them with appropriate conduit hubs or cable glands to maintain the I.P. rating.
Figure 1:
HYCONTROL
RELAY 1 RELAY 3
RELAY 4
RELAY 5
RELAY 2
REFLEX
2 3 4
6 78
0
ENT
MODE TEST#
5
9
1
CE
DSP
PROGRAMMABLE LEVEL CONTROLLER
40
40
90
40
10 160
130 CTRS
228 CTRS
240
4 MOUNTING HOLES
4.3 DIA (UNDER LID)
3 HOLES
20 DIA PLUGGED
HYCONTROL
.-

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 3
Electrical Connections - Single Point Applications
The instrument has two-part screw terminals. It can be powered from either an AC or DC
supply.
Figure 2:
AC power supply - connected:- Earth to terminal 1
Neutral to terminal 2
Live to terminal 3
The instrument will automatically accept either 110V or 230V AC ±10%, 50Hz or 60Hz,
12VA. A time lag fuse T160mA is fitted.
DC power supply - connected :- Positive +ve to terminal 27
Negative -ve to terminal 28
The instrument will accept 24V DC + 25%, - 10%. 9W.
A time lag fuse T315mA is fitted.
5 SPDT Relays - rated 8A/250V AC/30V DC resistive, with gold plated contacts for lower
power switching, are connected to terminals 4 to 18, for controlling external alarms, contactors,
pumps etc..
Transducer RXV15 Series - is connected:- Black to terminal 19
See Page 50 Blue to terminal 20
Screen to terminal 21
Transducer RXT15 Series - is connected:- Screen to terminal 19
See Page 50 Blue to terminal 20
Black to terminal 22
Transducer RXM19 - is connected:- Core to terminal 20
See Page 51 Screen to terminal 19
Transducer RXM19ER - is connected:- Core to terminal 20
See Page 52 Screen to terminal 19
Analogue Output - is connected :- Screen to terminal 24
(Isolated on AC units only) Positive +ve to terminal 25
Negative -ve to terminal 26.
Separate Temperature Sensor - connected with a shielded twisted pair and connected:-
( Screen to terminal 21
Must enable Pr.37 ( Core* to terminal 22* Polarity of cores is
( Core* to terminal 23 unimportant
Communications RS485 & RS232 - Contact Hycontrol for separate document.
1 2 3
E N L
L2 L1
AC POWER
110/230 VAC
+10%/-10%
50/60 HZ 12VA
19 20 21 22 23 24 25 26
27 28
+ -
DC POWER
21.6-30VDC
9W
ISOLATED
ANALOG
OUTPUT
SHIELD
HOT.BLUE
BLACK
+-
TEMP
SENSOR
TRANS-
DUCER
SHIELD
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
RELAY 1 RELAY 3 RELAY 4 RELAY 5
RELAY 2

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 4
INSTALLATION
REFLEX - AS A MULTIPOINT INSTRUMENT
System Configuration
The REFLEX controller can be used as the heart of a SCANFLEX System which will monitor
and control the level in 2 to 10 separate vessels. The transducer for each vessel is connected to
the controller via a 10 point Multiplexor SM-10. A full description of the Multiplexor and
PCB layout is shown on Page 58 to 61.
The Controller will output an analogue signal proportional to level or distance for each point as
it is scanned, but if a continuous mA signal is required for each point then an Analogue Output
Module SA-10, must be connected. A full description of the Analogue Output Card and PCB
layout is shown on Page 65 to 67
When used in the multipoint Scanflex mode the 5 relays in the Controller are pre-assigned as
Group Alarms and show the following:-
Relay 1 Indicates that Relay 1, on one of the points being monitored, has operated.
Relay 2 Indicates that Relay 2, on one of the points being monitored, has operated.
Relay 3 Indicates a loss of echo on one of the transducers.
Relay 4 Indicates that there is a fault in the communications with a module.
Relay 5 Indicates that the instrument is in Programme Mode.
To provide two separate alarm or control relays for each point a Relay Module SR-10 must be
connected.
A second Relay Module can be added, to provide 2 more alarms or relays for each point. A full
description of the Relay Module and PCB layout is shown on Pages 62 to 64.
Scanflex Configuration General
The modular approach to the design of the SCANFLEX system allows a choice of different
system configurations to be built. The individual modules required to build each system can be
mounted remote from each other. The controller is linked to the Multiplexor with RG62AU
cable and communication between the Controller and all modules is via a single RS485 cable.
Suitable cables include Belden 8451, Alpha 2461 or equivalents.
A little care in the selection of the location for the individual modules can considerably reduce
the cost of cabling.
i.e. The Multiplexor Module should be close to the transducer.
The Analogue Module should be close to where the outputs are required.
The Relay Module should be close to the alarms or controls it operates.
The maximum distance between the Controller, through the Multiplexor, to each individual
transducer, should not exceed 300m.
The Relay and Analogue Modules can be up to 2000m from the Controller, or greater if
repeater modules are used on the RS485 communications.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 5
Below are detailed a number of typical configurations:-
Configuration 1 - Minimum System
RS485
Reflex
Controller
Scanflex
SM-10
Multiplexor
Group and
status alarms
RS232
10 Transducers
Transducer link RG62A/U co-axial cable
(and t/comp if specified)
Minimum system to provide:-
A display of measurement for up to 10 points and 5 group alarms which are designated as
shown on Page 4.
An analogue output is available from the controller but it varies as the instrument scans each
point.
The RS232 output enables a local computer or PLC to obtain data from all measurement
points.
Configuration 2 - With Analogue Output - Module SA-10
RS485
Reflex
Controller
Scanflex
SM-10
Multiplexor
Group and
status alarms
RS232
10 Transducers
Transducer link RG62A/U co-axial cable
(and t/comp if specified)
10 Analogue
outputs
Scanflex
SA-10
Analogue
Module
In addition to the functions provided by Configuration 1, the analogue module provides a
continuous analogue output for each measurement point.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 6
Configuration 3 - With 2 or 4 Relays Per Point - Module SR-10
RS485
Reflex
Controller
Scanflex
SM-10
Multiplexor
Group and
status alarms
RS232
10 Transducers
Transducer link RG62A/U co-axial cable
(and t/comp if specified)
Scanflex
SR-10
Relay
Module (1)
10 x 2
Relays
Scanflex
SR-10
Relay
Module (2)
10 x 2
Relays
In addition to the functionality of Configuration 1 the Relay Module provides two alarm relays
for each measurement point. A second Relay Module can be added to either increase the
number of relays per point to 4 or duplicate the relay settings of the first (SR-10) module.
Dependent on how LK4 or LK5 are set. (See Pages 62 and 63 for details).
Configuration 4 - With both Analogue and Relay Outputs
Scanflex
SR-10
Relay
Module (2)
10 x 2 Relays
RS485
Transducer link RG62A/U co-axial cable
(and t/comp if specified)
Scanflex
SR-10
Relay
Module (1)
10 Analogue
outputs
Reflex
Controller
Group and
status alarms
RS232
10 Transducers
Scanflex
SM-10
Multiplexor
Scanflex
SA-10
Analogue
Module
10 x 2 Relays
All Modules can be connected
to the RS485 in any order
Configuration 4 shows maximum outputs available per point i.e. 1 analogue and 4 relays.
This configuration provides all the discrete outputs that can be programmed for each
measurement point. Two Relay Modules provide 4 independently programmable relay switch
points for each transducer.
If required additional Analogue and/or Relay Modules can be added to duplicate the same
signals in different locations or control rooms. Up to 14 Modules can be connected, although
the total system configuration must not exceed 15 modules including the one Multiplexor.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 7
INSTRUMENT MOUNTING
To install the REFLEX/SCANFLEX Controller and the associated Scanflex SM-10
Multiplexor, SA-10 Analogue Module, and SR-10 Relay Module, if required, follow the
guidelines below.
Reflex/Scanflex Controller See Fig. 1
To install this follow the instructions for mounting the Reflex transceiver as shown on Page 2.
Modules SM-10, SA-10 and SR-10
These are all supplied in identical enclosures as shown on Page 59. Before mounting them
drill the enclosure and fit appropriate conduit hubs or cable glands.
Undo the 6 quarter turn screws on the front panel and remove it to expose the mounting holes.
Mount the unit on a flat surface and secure it via the 4 mounting holes moulded in the
enclosure. DO NOT use excessive force when tightening the fixings and avoid any distortion
of the enclosure.
Ensure that the mounting surface is not subject to vibration and is not in close proximity to
high voltage cables, contactors or drive controls. The unit should not be mounted in a confined
space where temperatures may exceed the normal working temperature. If the unit is mounted
outside it must be protected from direct sunlight or severe weather conditions.
Scanflex Multiplexor SM-10
One of these modules must be fitted in all multipoint systems.
For economy of cabling put the Multiplexor as near the transducers as possible.
See Page 9 for ELECTRICAL CONNECTIONS.
Scanflex Analogue Module SA-10
This is an optional requirement.
The Analogue Module should be located close to where the analogue outputs are to be used or
displayed in order to reduce the wiring to a minimum.
See Page 10 for ELECTRICAL CONNECTIONS.
Scanflex Relay Module SR-10
This is an optional requirement.
The Relay Module should be located close to where the controls or alarms are located. If
relays are required to activate both controls and alarms, but they are located in different areas,
then a Relay Module should be mounted separately in each location as this will significantly
simplify and reduce cabling costs.
See Page 10 for ELECTRICAL CONNECTIONS.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 8
Electrical Connections - MultiPoint System
Controller - Electrical Connections
The Reflex Controller is common to all systems. It has two-part screw terminals. It can be
powered from either an AC or DC supply, but the Multiplexor, Analogue and Relay Modules
must be powered from 110/230V AC.
Fig 3.Terminal Layout - Bottom PCB
Fig 4.Communications terminals on top PCB.
AC power supply - connected:- Earth to terminal 1
Neutral to terminal 2
Live to terminal 3
The instrument will automatically accept either 110V or 230V AC ±10%, 50Hz or 60Hz,
12VA. A time lag fuse T160mA is fitted.
DC power supply - connected :- Positive +ve to terminal 27
Negative -ve to terminal 28
The instrument will accept 24V DC + 25%, - 10%. 9W.
A time lag fuse T315mA is fitted.
5 SPDT Relays - rated 8A/250V AC/30V DC resistive, with gold plated contacts for lower
power switching, are connected to terminals 4 to 18, for controlling external group alarms for
pre-determined conditions as detailed on Page 4.
Co-axial Cable Connection to Multiplexor SM-10 - is connected:-
Core to terminal 20
Screen to terminal 19
This cable should be separated from power cables and preferably installed in its own earthed
steel conduit.
1 2 3
E N L
L2 L1
AC POWER
110/230 VAC
+10%/-10%
50/60 HZ 12VA
19 20 21 22 23 24 25 26
27 28
+ -
DC POWER
21.6-30VDC
9W
ISOLATED
ANALOG
OUTPUT
SHIELD
HOT.BLUE
BLACK
+-
TEMP
SENSOR
TRANS-
DUCER
SHIELD
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
RELAY 1 RELAY 3 RELAY 4 RELAY 5
RELAY 2
RS232 RS485
Tx GND SCR SCR - +
TB5
Rx
31 32 33 34 35 36 37

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 9
Analogue Output - is connected :- Screen to terminal 24*
Positive +ve to terminal 25*
Negative -ve to terminal 26*
* Gives an indication of only one point at time. For continuous analogue output an Analogue
Output Module SA-10 is required.
Separate Temperature Compensation - when compensation is provided by a separate
temperature sensor on each point then the controller should be connected to the Multiplexor
SM-10 with a shielded twisted pair and connected:-
Screen to terminal 21) terminal Shld ) On
Core* to terminal 22) On Controller terminal + ) Multiplexor
Core* to terminal 23) terminal - )
* The polarity of the cores is unimportant.
Communications between Scanflex Modules Via RS485
The Controller is connected to the Multiplexor Module, Analogue Module and Relay Module
using 2 core screened cable. TB5 terminals 35 to 37, on the Controller top PCB are connected
to the matching SHLD, -ve and +ve terminals on TB1 on the Multiplexor and then looped on to
TB1 on the Analogue and/or Relay Modules used in the system. For location of terminals see
Pages 8, 60, 63 and 66.
Communications to external PC or PLC via RS232
Communications from the Controller via RS232 to Hycontrol's vision system or to the user's
external devices, is via 3 core screened cable connected to terminals 31 to 34 on TB5.
MULTIPLEXOR MODULE SM-10 - ELECTRICAL CONNECTIONS See Page 60
Communication - From the Controller terminals 35-37 to the Multiplexor is via a 2 core
screened cable connected to TB1. Use Belden 8451 or equivalent cable.
Power Supply - Selectable 110V or 230V AC +10/-15%, 50Hz or 60Hz, 12VA
is connected to TB4. Voltage selector SW4 must be set to the
correct voltage.
Transducer link to Co-axial cable RG62AU must be used. Connect to TB3 TRANS
Controller Core to HOT
Screen to SCR
Transducer connection
to Multiplexor - Up to 10 transducers can be connected to one Multiplexor. If
fewer than 10 transducers are connected and called up in the
programme they must be connected to Points 1 to 'n' in sequence.
NO GAPS MUST BE LEFT IN THE RANGE PROGRAMMED.
(e.g. 6 transducers must be connected to
Points 1 to Point 6).
RXV15 Transducer Blue to HOT
Black & Screen to SCR
RXM19 Transducer Core to HOT
Screen to SCR
RXM19ER Transducer Core to HOT
Screen to SCR
HOT

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 10
ANALOGUE MODULE SA-10 - ELECTRICAL CONNECTIONS See Page 66
Communication - From Controller or other module via a 2 core screened
cable connected to TB1. Refer to Page 9.
Power Supply - Selectable 110V or 230V AC +10%/-15%, 50Hz or 60Hz,
12VA is connected to TB4. Voltage selector SW4 must be set
to the correct voltage.
Analogue Outputs - Are connected to the +ve -ve and shield terminals of TB2 for
each point starting at Point 1 and leaving no gaps in the
programmed range.
RELAY MODULE SR-10 - ELECTRICAL CONNECTIONSSee Page 63
Communication - From Controller or other module via a 2 core screened
cable connected to TB1. Refer to Page 9.
Power Supply - Selectable 110V or 230V AC +10/-15%, 50Hz or 60Hz, 12VA
is connected to TB4. Voltage selector SW4 must be set to the
correct voltage.
Relay Outputs - One Relay Module provides two relays for each point. If 4
relays are required for a point then two Relay Modules must be
used.
Relays are connected at TB2 for each point starting at Point 1
and leaving no gaps in the programmed ranged
MODULE IDENTIFICATION INSTRUCTIONS
Each Module (other than the Controller) must have an individual address number. This is set
on Switch (SW1) which is located on the upper left hand side of each Module.
The switch (SW1) on the Multiplexor must always be set to 1, with other Modules numbered
sequentially with no gaps in the sequence.
The total number of Modules connected to the Controller must be entered in Pr.51
NB - No two Module switches should be set to the same position.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 11
Transducer Installation
The positioning of the transducer and the mounting method used is important and varies with
the type of transducer, the application and the material, being monitored.
On liquid measurement applications it is important to ensure that the transducer is
perpendicular to the liquid surface and the circumstances shown on Page 49 should be avoided.
The transducer beam angle is 10 to 120included.
Transducers should be mounted in the isolation kits provided and for solids applications where
levels may not be flat due to the effects of fill or draw off points, then an aiming kit as shown
on Pages 53 or 54 should be used.
Transducers wired to the Multiplexor (SM-10) must to be connected to Point 1 first then
sequentially and without gaps. See Page 60 for terminal connections.
Each transducer is supplied with a length of integral cable, which can be extended up to 300
metres using a suitable junction box, and RG62A/U co-axial cable. The 300m is the maximum
distance from the Controller to the transducer via the Multiplexor. Transducer cable should
be separated from power cables and preferably installed in its own earthed steel conduit.
Transducer cables and temperature compensation cables can be run together.
For installation of the RXV15 series transducer in hazardous locations refer to the appropriate
National Standard.
SEE APPENDIX (1) FOR TRANSDUCER PERFORMANCE, POSITIONING AND
PHYSICAL RECOMMENDATIONS FOR STANDPIPE INSTALLATIONS.
Temperature Sensor See Page 55
If temperature compensation is required the sensor should be mounted where it will monitor
temperature changes of the air between the transducer and the material. This is usually
adjacent to the transducer, but should not be in direct sunlight.
The sensor is connected to the Multiplexor at TB2 using a 2 core screened cable connected to -
ve, +ve and SHLD for each point. The Multiplexor terminal TB3 connections SHLD, + and -,
are connected to Controller terminals 21 to 23 using the same type of cable. The total cable run
from sensor to Controller via the Multiplexor should not exceed 300m. The cable can be run
together with the transducer cable in the same conduit.
For installation of sensor type RTS-2B in hazardous locations refer to the appropriate
National Standard.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 12
PRE-START GUIDE
Pre-Start Check List
1. Check that each module enclosure is mounted securely in accordance with
Pages 2 or 7.
2. Check that the wiring is in accordance with Page 3 for a single point instrument or
Pages 8-10 for a multipoint instrument.
3. Provide a power supply for the Controller and each Module in a multipoint system.
Remember that the Controller can have 110/230V AC or 24V DC supply but
the Scanflex Modules must have 110 or 230V AC and this must be selected, on
the module.
4. Check that each module has its individual system address number by setting the
selector switch (SW1) on each module to its correct position. See Page 10.
5. Check that the data link to each module is as shown in Configuration wiring diagrams,
Pages 5 & 6 and the RS485 connections are as indicated on Pages 9 and 10
6. Check the RG62AU cable link from terminals 19 and 20 on the Controller to TB 3
on the Multiplexor.
7. Check the temperature sensor link (if required) from terminals 21 to 23 on the
Controller to TB 3 on the Multiplexor.
8. Check that any Relay or Analogue Modules are correctly wired. See Page 10.
YOU ARE NOW READY TO SWITCH ON
9. Check that the neon light in the Reflex Controller is flashing. The instrument will
be in the normal RUN mode.
At switch-on the instrument will show either:-
REFLEX
HYCONTROL
HYCONTROL
SCANFLEX
HYCONTROL
HYCONTROL
In single point mode Pr.1 = 1
(Under factory default programme)
In multipoint mode Pr.1 = 2 to 10
(If pre-programmed)
or
The above display will remain for 1 minute maximum and then go into its normal RUN
mode.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 13
10. In the 'run' mode three different display layouts are available.
10a. Normal 'RUN' Mode
Point number will be 1 in single point, Reflex mode
and will change continuously between 01 and the max.
number of points in multi point Scanflex mode
4 Boxes show external relay status
in Multipoint mode only. (Dark if
energised)
4 digit display
of level
Bar graph - length proportional to level display
or "Loss of Echo" if this condition exists.
POINT
01 21.39
10b. Display of Secondary Functions
When "TEST" is pressed the display shows gain, distance and loss of echo status for that
point. When "DSP" is pressed it shows mA Output and Temperature for that point.
Press "DSP"Press "TEST"Press CE to return to RUN
Shown only when condition
exists for the point.
POINT : 01
ANALOGUE = 15MA
TEMPERATURE = 20 DEGC
POINT : 01
DISTANCE = 1.7
GAIN = 0.2%
LOSS OF ECHO
Secondary display is of the next scanned
point, not the point in the normal run displa
y
10c. Status check for Scanflex Modules
This is available only if the instrument is configured as a multipoint system and a Multiplexor
and other modules are being used.
When "#" is pressed in RUN mode the display of a Scanflex will show the status and the
number of modules connected to the Controller as defined by Pr.51.
If a box is filled in it indicates a fault in communication. Consult Page 44
If the above displays do not appear then re-set to factory defaults as instructed on Page 16 and
check the entry at Pr.51
11. On Scanflex application also check that the green comms light on the Multiplexor is
flashing and the red status light is scanning from point 1 to point 10 or however many
points are selected.
THE SYSTEM IS NOW READY TO BE PROGRAMMED
UNIT STATUS
Box filled in
shows a fault

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 14
PROGRAMMING
REFLEX/SCANFLEX system needs to be programmed by the operator to produce the
required measurements and control. To do this the keypad on the Controller is used to access
parameters and enter values in each one to determine the controls required.
Principle of Programming
The REFLEX/SCANFLEX has two modes:-
a) RUN (Normal operating)
b) PROG (Programming)
In the 'RUN' mode, the instrument monitors the target, displaying values, and setting outputs
as programmed by the operator. If Scanflex multipoint operation (Pr.1 = 2 to 10) has been
selected then in "RUN" mode the instrument will automatically scan each point and update
the display in numerical sequence.
In the 'PROG' mode the operator uses the keypad in conjunction with the display to adjust the
settings for each point and to test that the unit is programmed correctly.
Security Code
The REFLEX/SCANFLEX program includes security code protection. Any operator who
knows the entry sequence can display the value of a parameter, but any attempt to enter a new
value or perform a test will result in the security code being requested.
The security code is requested by the prompt 'CODE'. If the code is not entered correctly,
then this prompt is re-displayed.
Once the code has been input correctly, it will not be required again whilst the system remains
in the 'PROG' mode.
The factory set value is 9753, but a new "customers" security code comprising 4 numerical
digits, can be entered via Pr.96 providing the operator is in program mode. The range of
acceptable values is 1000 to 9999. If an invalid code is entered the instrument will default to
a code number 1000.
The code number is scrambled immediately on entry and therefore cannot be read by an
unauthorised person.
If you forget your own new code number contact Hycontrol advising the scrambled code
number displayed at Pr.96

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 15
To Enter Programme Mode and View Data
Press Mode Display shows -
PROG
Press 1
Value of Parameter
CONTROL = 01
Pr.01 = 15
NUMBER OF TRANS Parameter description
Shows Parameter
being viewed
Displays point or control parameter
currently programming
Parameters which effect all Points are called CONTROL. Parameters which may have a
different value for each individual Point are called POINT.
Press DSP
Pressing DSP toggles the cursor between Pr. No. and Value. Position the cursor under
whichever you want to change.
To Select and View any other Parameter
Either press the '▲' key or '▼' key until you come to the parameter required or put the cursor
under the Pr. No. (Press DSP to move cursor) and key in the new number required.
To Change the Value in a Parameter
Select the parameter which you wish to change. Put the cursor under the value presently in
that parameter and key in the new value required.
Press ENT Display shows - CODE
Key in 9753
CODE9753
Press ENT Display will show the new value.
If you remain in PROG mode other parameters can now be changed without the need to re-
enter the code.
i.e. Select the next Pr. No. to be changed.
Press DSP - to move cursor to the value.
Key in the new value required.
Press Ent. - Display will show new value
CONTROL = 01
Pr.01 = 1
NUMBER OF TRANS Cursor

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 16
To Change Point No. in Multipoint Mode (i.e. Pr.1 is 2 or greater)
Select any parameter, which is a POINT parameter (not CONTROL) and press # key. POINT
No. will increase progressively until the maximum selected by Pr.01 and then return to
POINT 01.
Note that you will stay on the Point No. selected until you return to RUN mode, or press the #
key to change the Point No.
Return System to "RUN" Mode
When all parameters have been set to their required value press MODE and the instrument
will return to "RUN" i.e. normal running. (The unit will automatically return to RUN mode if
a key is not pressed within 6 mins).
USE THE KEYPAD AND WATCH THE DISPLAY UNTIL YOU FEEL COMFORTABLE
WITH ALL KEY PRESSES AND DISPLAYS.
We recommend that you now reset the system to its factory defaults as shown below, before
you begin programming the system for your application.
System Reset to Factory Defaults
1. Press MODE to display 'PROG'.
2. Press 1 to display programme sequence.
3. Change Pr. number to display Pr.99.
4. Press DSP to move cursor under '===='
5. Press 'CE' then 'ENT'.
6. Press 9753 when 'CODE' displayed. (Or your own new code number).
7. Press 'ENT'.
8. Display will show 'PRES' and 'TRES' and return to programme display.
9. Press DSP to move cursor under Pr.99
10. You can now begin programming by changing Pr.99 to the first parameter you wish to
change.
All parameters are now returned to their original factory default values as specified in this
manual.
i.e.RXM19 family and single point Reflex mode.
Before starting to programme your application we recommend that you list all parameter
numbers/values which you intend to change from their factory defaults.
For Reflex single point use Page 71.
For Scanflex multipoint use Page 72.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 17
Manual Scanning
When used as a multipoint scanner this facility has been included mainly for commissioning
and fault finding purposes. It allows the system in the "RUN" mode to continually stay on
one point whilst checks are carried out. The normal scanning process is stopped.
When manual scan is in operation the system fault relay (Relay 4 on the Controller) will be in
alarm mode and the corresponding LED will be on.
Manual scan is enabled by programming Pr.53 = 1 and then re-entering "RUN" mode.
To select a specific point to be monitored press the relevant key 1-9 or 0, these correspond to
measuring points 1-10. To de-select manual scan set Pr.53 to 0 or power down then up
again.
NOTE:
1. When in manual scan, press "TEST" to display the gain value.
To return to normal display press the "CE" (Clear entry) key.
2. Module system status check does not operate during manual scan.
3. The unit will not automatically return to normal run mode. Reset Pr.53 to 0.

Ref: REFLEX/SCANFLEX MANUAL
EDITION 1: JULY ’97 18
Keypad Definitions
The keypad consists of 20 keys which are used to programme the Controller. Some of these
keys also have secondary functions enabling the operator to view the results being obtained
by the instrument during its normal 'RUN' cycle.
Primary Key Functions
0 - 9 Numerical Values
w Decimal Point
— Negative value (also used to slow down simulation)
CE Clear Entry (also used to leave test functions Pr.75 to Pr.78.)
# In normal 'RUN' mode it displays unit status and in 'PROG'
mode it advances point number. (also speeds up simulation Pr.78)
MODEAlternates between 'RUN' and 'PROG' mode.
TEST In 'RUN' it displays gain and distance or shows LOE status.
'▲' Increase parameter number (also control of simulation direction).
'▼' Decrease parameter number (also control of simulation direction)
DSP Moves the cursor on the display between Pr. No. and its value.
(Changes can be made only to the data underlined by the cursor.)
ENT Enter a new value or initiate a system test under Pr.75 to Pr.78
Active Secondary Key Functions
During normal 'RUN' mode it is possible for an operator to obtain the data defined as
secondary function without interrupting normal operation, by pressing the appropriate
key, i.e.
Key 1 Relay 1. Hours energised and number of starts.
Key 2 Relay 2. Hours energised and number of starts.
Key 3 Relay 3. Hours energised and number of starts.
Key 4 Relay 4. Hours energised and number of starts.
Key 5 Relay 5. Hours energised and number of starts.
Test In 'PROG' it scrolls through parameter list and control
simulation.
DSP Displays point, mA output and temperature
To cancel secondary display press "CE"
This manual suits for next models
1
Table of contents
Other Hycontrol Controllers manuals
Popular Controllers manuals by other brands

AMS Controls
AMS Controls MP450S Operator's manual

Bosch
Bosch REXROTH IndraMotion MLD Getting started

Sony
Sony ICF-SC1PC operating instructions

Mitsubishi Electric
Mitsubishi Electric MELSEC Q Series user manual

LAUREL Electronics
LAUREL Electronics MAGNA RS485 Installation & operating manual

Fermax
Fermax 8053 manual