2 K-1 K-2 K-3 SATEL
the magnetic contact elements, use a ø9 mm drill. Press the K-2 magnetic contact elements or screw
the K-3 magnetic contact elements into the holes made.
Notes:
Do not use a hammer to drive the contact into the hole (it may damage the reed switch).
When screwing the K-3 contact into the hole, the wires become twisted. To prevent them from
damage, twist the wires against the direction of screwing before installation.
magnet.
contact.
A – make distance.
B – permissible offset between contact and magnet axes: K-2 = 10 mm, K-3 = 12 mm.
C – minimum thickness of the wall in which magnetic contact elements can be mounted: 10 mm.
3. Specifications
Magnetic contact type......................................................................................................................... NC
Maximum switching voltage.............................................................................................................. 20 V
Maximum switching current ........................................................................................................... 20 mA
Contact resistance.......................................................................................................................150 mΩ
Minimum life expectancy (20 V, 20 mA) ......................................................................................360 000
Contact material ...............................................................................................................Ru (ruthenium)
Make distance K-1 ................................................................18 mm
K-2 ................................................................28 mm
K-3 ................................................................15 mm
Break distance K-1 ................................................................28 mm
K-2 ................................................................40 mm
K-3 ................................................................24 mm
Environmental class according to EN50130-5........................................................................................II
Operating temperature range ............................................................................................ -10°C...+55°C
Maximum humidity........................................................................................................................ 93±3%
Weight K-1 ....................................................................10 g
K-2 ....................................................................10 g
K-3 ....................................................................24 g
The declaration of conformity may be consulted at www.satel.eu/ce
SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND
tel. +48 58 320 94 00
www.satel.eu