
© 2009 SCAD Technologies LLC •www.scadtech.com Page 9
the value of parameter P26 in programming mode. For relative mode, P25 and P29
must be set to 0. Use programming mode, as explained above to change these
settings.
• Absolute mode: Alternatively you can set an absolute high temperature alarm. That
is, you can set a particular temperature at which the alarm is activated. First you
must change the alarm mode to absolute by changing P29 to 1. Next you must
change P25 to -50. Finally you can set P26 to the temperature at which you wish the
alarm to occur.
• High temperature alarm delay:By default, the high temperature must be maintained
for two minutes before the alarm sounds. You may change this value (in minutes) by
changing P28.
• To disable the beeper: Change the value of C53 to 1 in programming mode. To re-
enable the beeper, change the value of C53 back to 0.
To change default temperature sensor display:
Your SensiStat by default displays the temperature sensed by the icebox temperature
sensor (probe 2, also known as “b2”). Probe 1, also known as “b1”, is the probe on your
holding plate and the one that controls the behavior of the SensiStat. By pressing the T
(Down) key, and then using the T(Down) or S(Up) keys you can scroll between display
choices. This can be a bit confusing, so experiment a bit to get the feel of it. What you
will see is an alternating display, first what is going to be displayed, like “b1” and then the
value of that probe. The alternating will continue until you lock in your choice by holding
down the Set button for a few seconds. You will also see “din1” and “din2” as choices for
display. Please just ignore these choices.
To display or set the freezing temperature:
1. To enter the set point programming mode, press and hold the SET key for 5
seconds.
2. The display will show “St1”, the variable for the freezing temperature for normal
operation.
3. Release the SET key. The display will now show the current setting for St1.
(Factory default is 0oF).
4. If you wish to change this value, press either the S(Up) and T(Down) keys until
you reach the new desired value.
5. Press the SET key briefly to confirm the current or new value of St1.
6. The display will show “St2”. This is the variable for the freezing temperature for
override mode. This value should be set to the same value as St1.
7. The value of St2 will be displayed. (Factory default is 0oF).
8. If you wish to change this value, press either the S(Up) and T(Down) until you
reach the new desired value.
9. Press the SET key briefly to confirm the current or new value of St2.
10. The SensiStat will return to its normal display mode.
To display or set the differential settings:
Generally, there is no need to change the differential settings unless your refrigeration
manufacturer specifies a different differential. Remember, the override differential is
critical for the “Free Power” mode to operate correctly. Avoid changing the “P2” value
unless you are certain you know why you are changing it.
1. Enter programming mode following the instructions above.
2. Select parameter “P1” (differential for normal operation) or “P2” mode (differential
for override operation).
3. After changing these values, exit programming mode by holding the PRG key for
several seconds until the normal display (temperature display) appears.