Scaime GM 80 TG User manual

Operating instruction
DC Voltage Measuring Amplifier with Data Logger
GM 80 TG / PA
(V1.__)

Safety Notes
General References
The enclosed operating instruction is intended for technically qualified personnel who has corresponding knowledge in the
field of measurement and industrial process & control technology.
The precise information about all safety notes contained in this operation manual and warnings, as well as its perfect
technical implementation are precondition for the safe installation, the initiation, the secure operation and the maintenance
of technology devices. For this purpose it is absolutely necessary that all measures are carried out by qualified personnel.
All persons concerned with the project planning, installation and service of devices, must be familiar to the security concepts
in automatic control and should be qualified in this sense.
For clarity reasons, the enclosed operating instruction can not represent complete details in all conceivable cases of
applications for the handling of devices. Further, we cannot consider the entire types of installation, handling and
maintenance. If you wish further information or if special problems occur, which were not ,or not at length represented in this
operating instruction, contact us, please.
The oblivion of the safety notes can and will lead to material damages, body injuries and death.
The devices may only be operated in accordance with the applications described in this operation manual. Built-in
devices may only be operated in appropriate installations.
With the connection and the initiation of the device, the customer accepts the general sale and delivery conditions. Further,
he accepts eventually incomplete operation manuals. The information described is without guarantee. Errors and changes
are reserved.
Intended Purpose, Improper Usage
A device is used for displaying, processing and controlling or regulation of processes. It shall not be used as the only tool for
the prevention of dangerous states to machines and plants. Machines and plants must be constructed in such a way, that
erroneous states can not lead to a dangerous situation for the staff (e.g. by independent limit switches, mechanical locking
devices). It must be guaranteed in particular that device-operating errors, its malfunction or it’s breakdown do not lead to
great property damages or danger for the staff. Consequently, the device then can be used to prevent the machine or the
technical installations from error conditions.
It is also important that the use of devices does not endanger precautions for the safety of technical installations.
Emergency-off settings must remain effective in all operation modes.
Installation Notes
The devices must be installed and connected by compliance with the relevant DIN- and VDE-norms. They must be installed
in such manner that an unintentional use is sufficingly excluded. The corresponding hardware and software safety
precautions are to be observed in such manner that an interruption of the supply and signal cables cannot lead to an
undefined or dangerous state. Supply and signal cables must be installed in such way, that disturbing signals (e.g. inductive
or capacitive intersperses) will not cause derogations to the function of devices.
Disturbance, Maintenance and Repair Notes
The devices do not contain parts which can be maintained on the customer side. Repairs shall be carried out by exclusively.
If assuming that a safe operation of the device is not possible anymore, it must be closed down and protected against
unintentional handling immediately. This, in particular, applies:
If the device shows visible damages
If the device is no longer operative
If parts of the device are loose or slack
If the connection cables show visible damages
Furthermore, we point out that all obligations of exclusively result from the respective sales contract in which the
guarantee has been conclusively settled.

Brief Description:
The GM 80 TG / PA is a DC measuring amplifier for passive, active sensors or sensors with current interface.
GM80 TG Table device with 24 V DC wall power supply
GM80 PA Panel device 72 x 144 norm, cut-out in cabinet: 138 x 68 mm
Inputs: Passive (SG) 0,35-3,3mV/V; active: 0-1V...0-5V / 0/4 – 20mA
Data logger : can store up to 3000 measured values. For short-term to long-term measurements
with many operation modes.
RS 232: Data transfer or queries of the measured or logged values to a pc or a printer.
10 parameter sets: Here, the calibration data, the sensor designation and the physical unit are stored.
Control inputs: 3 opto coupler inputs with functions such as data logging, RS232-issue, clear memory,
tare or second limit value set.
Limit values: 2 very fast photoMos relays as closing contacts are freely configurable
Measuring functions: Tare, min./max. value and delete min./max., are callable during the measurement.
If the GM 80 is being delivered with one or more sensors, these sensors will be in-calibrated to the
GM 80 and are immediately ready for operation.
The assignment of these sensors to the corresponding parameter set is documented on the rear of the device.
Operation Example:
- GM 80 PA after current supply is immediately in the measuring mode of the previous selected parameter set.
- GM 80 TG is switched on by pressing ENTER.
Key Assignment:
Key Menu:
Scroll up
Scroll down
ENTER Confirmation, one step up in the menu
ESC Discard, one step back in the menu
- Control time and date in SYSTEM menu or adjust if necessary
-Adjust language
Call menu 2 SYSTEM – 2.1 LANG. When ENTER button was pressed, the GM 80 is in the selection mode. With
keys PLUS and/or MINUS the language can be selected. With ENTER the selected language will be stored. With
ESC the selected language will be discarded.
-Adjust time
Call menu 2 SYSTEM – 2.8 DATE. When ENTER button was pressed TIME will appear on the LCD. Press ENTER
again and the time can be adjusted. With PLUS and MINUS the hours can be adjusted. After ENTER the minutes
can be adjusted with PLUS and MINUS. With ENTER the selected time will be stored. With ESC the selected time
will be discarded.
- Change to the measuring mode
From menu 1 MEASUR by pressing ENTER the list of all sensors is called. With PLUS and/or. MINUS a sensor
parameter set is being chosen. With ENTER the GM 80 is being adjusted to this sensor parameter set. With ESC it
is possible to switch back to menu 1 MEASUR from any mode.

- Change measuring rate by measuring mode
The measuring mode can be left by pressing ESC. After pressing ESC again, the GM 80 will be in menu 1
MEASUR. From there the menu 2 SYSTEM – 2.4 Rate can be called.Select RATE by key PLUS and/or MINUS. By
pressing key ENTER the set measuring rate is being displayed first.By key PLUS and/or MINUS a new measuring
rate can be adjusted. By ENTER the new measuring rate will be taken over, by ESC the new measuring rate will be
discarded.
- Switch off GM 80 TG
If the GM80 TG is operating in menu 1 MEASURE it can be switched off, when ESC is pressed for >3 seconds.
- Switch off GM 80 PA
This device can only be switched off by disconnecting from current supply.
Measuring with the GM 80:
Selected Sensor: Force sensor with measuring range: 200KN
Sensitivity 2mV/V
Designation e.g.: Press
Parameter set: Sensor no.: 3
Option: 100% Calibration control
In order to be able to now measure with this sensor, the sensor " Press" is selected in the measuring mode. During a
measurement, a minimum and maximum value buffer can be called with the MINUS key. The respective displayed minimum
or maximum value can be deleted by ENTER.
If the measured value shall be sent through an interface to a pc or printer, the baud rate must be adjusted to the receiver
and at SCI-MODE the operating mode must be chosen. For example: HAND, a measured value with time is displayed
during every keystroke on ENTER while measuring.
For data logging, adjust operating mode in the logger mode, e.g. choose AUTO and interval time e.g. 10 sec and change to
measuring mode. A measured value with time is now stored every 10 sec. In mode LOGGSEND, these data can then be
sent through the interface.
Key Assignment:
Key Measuring Mode:
Press = TARE
MEASURING---MIN---MAX--- MEASURING...
ENTER At MEASURING: send data
At LOGG: store measured value, if adjusted
At MIN: delete MIN At MAX: delete MAX
ESC Back to menu / Press for 3 sec. = Off
Parameters of a Sensor:
After entering the password (9373) in menu 2SYSTEM-2.5PASS, the sensor can be installed in the calibration menu.
Following parameters are possible:
Sensor__l Sensor no. 3 Sensor 0 – 9 possible
POINTDIS 200,0 Match meas. range and decimal point (max. 9999)
UNIT _kN 1 – 3 digit unit possible
DESIGN Press Up to 8 digit name (or numbers) arbitrary
CALIB PAS_wCON Select Passive with cal. control. See data sheet of
sensor
0% LOAD Unload sensor 0% value of sensor is assigned to display 0
100% CON Autom. calibration 100% value of sensor is assigned to display
200,0 kN
SAVE ENTER or ESC Confirm or discard

GM 80 TG/PA Brief Handling Overview

Mains Operation:
GM80 TG: Wall power supply with 24V DC / 250mA is part of the delivery scope.
GM80 PA: The supply voltage of 16-30V DC is connected via a BMS-plug.
Battery for Date and Time:
A commercial CR2032 lithium battery with 3V is used. If time and date continuously begins at 0.00 hrs and date of
01.01.70, the battery must be exchanged. Switch the GM80 off-circuit first!!! At the GM80-TG both screws are
unfixed at the bottom and the housing top has to be removed.
At the GM80-PA the front framework is removed and the front foil has to be slightly lifted at all 4 corners, then the
underlying screws need to be unfixed. Then the circuit board can be pulled out carefully. The battery is located on
a clamp on the circuit board and can easily be exchanged. “Plus” on top!
Control inputs: Trigger, Enable, Tare/GWS2
This input can be controlled e.g. with a PLC, remote switch, foot switch... or similar.
It is an optocoupler input and therefore it is separated galvanically.
As a control signal, 0V - 2V is recognized as low level, 3,5V -27V as high level.
Trigger:
Thus depending on the adjustment, data can be stored or interface data can be issued.
This input has a high sampling rate, therefore very short impulses are recognized as well.
Enable:
By this the min. and max. value is deleted externally.
In the display mode Max or Min, e.g. after each measurement the min. or max value can be deleted in order to acquire the
next min. or max. value.
Tare / GWS2 (limit value set 2):
Select in the menu which function should be carried out while applying a signal.
Tare: tare externally.
GWS2: by this the second limit value set is being activated, parameters are being adjusted in the menu.
Operation Mode Low level High level
GWS1 + TARE GWS1 TARE
GWS1 + GWS2 GWS1 GWS2
Serial Interface Adjustment:
Parity: none
Data bits: 8
Stop bits: 1
Limit Values:
2 switching points (SP), independent from each other, can be configured in value and the switching direction. The second
limit value set has to be activated by the control input.

Menu Description:
1 MEASURE: Measuring mode
SENSOR__: Sensor selection for measuring mode, sensor 0 - 9
Here the sensor parameter set for the measurement is being selected.
The sensor parameter set must match the connected sensor.
2 SYSTEM: All system parameters are being stored in this menu column.
2.1 LANG Language adjustment
The menu language can be chosen in German, English, French or Spanish.
2.2 INFO Information query was configured factory-sided and is not variable.
VERS NO. Software version
2.3 SCI Interface configuration
BAUD: Baud rate adjustment must be conform with the receiver (pc or printer).
SCI MODE Interface configuration only refers to the measuring mode, not the logg mode!
OFF Interface off
HAND At key stroke "ENTER“ the measured value is issued
AUTO Interval time, adjustable from 10ms to 1h (at high measuring rate only possible with highest baud
rate)
TRIGGER At a trigger pulse a measured value is issued
TRIGGER2 At a trigger pulse a measured value is issued and the MIN-MAX-value is deleted.
deleted.
ADDRESSAddress selection
2.4 RATE Measuring rate and average value
RATE Measuring rate adjustment can be chosen between 1/s and 1000/s. At fast courses (screw joint,
insert press...) always choose a fast measuring rate, e.g. 1000/s, at very slow courses a small rate,
e.g. 1/s.
AVERAGE Forming an average value, the numbers indicate by how many measurements an average value is
accumulated. Applicable at e.g. vibrations, control oscillations.....
2.5 PASS Password query
After entering the password 9373 it is possible to enter menu 3 CALIB .
There the sensor parameters can be modified.
2.6 LCD LCD-contrast adjustment
If the LCD becomes unreadable by external influences e.g. solar radiation, heat or cold, the LCD-
contrast can be corrected here.
2.7 LOGG Data logger adjustments
LOGGMODE Data logger configuration.
OFF Off-switch for logger operation, by this the measuring mode is possible only.
HAND At each key stroke on Enter a logg value is being taken over.
AUTO Adjustment of the measuring intervals.
DIAGRAM With each increasing flank of the trigger signal a logg value is being taken over.
WINDOW The window operation is being started by an increasing trigger flank and can only be finished by a
decreasing flank. During this time, measured values will be deposited in the data logger in 1ms
raster.
TRIGGER2 With each increasing flank of the trigger signal a logg-value is taken over and the MIN-
MAX-value is deleted.
LOGGSEND Logger values are issued through the interface, press ENTER twice
LOGGDEL Logger values are deleted, beforehand there will be a safety query whether the buffer should be
deleted. Before deleting please assure that you have received the desired data.

2.8 TIME Date and time adjustment
DATE Date
TIME Time
2.9 INPUT Mode of operation and limit value adjustments
DISPLAY Cont continuous measurement
Min min. measured value is displayed and restored by a trigger pulse.
Max max measured value is displayed and restored by a trigger pulse.
LIMIT Limit values are active only when mode of operation is selected.
VALUE SETS SP1_1 switch point 1 of (GWS1) switch point and switching direction adjustable.
SP1_2 switch point 1 of (GWS2) switch point and switching direction adjustable.
SP2_1 switch point 2 of (GWS1) switch point and switching direction adjustable.
SP2_2 switch point 2 of (GWS2) switch point and switching direction adjustable.
OPERATION GWS off all limit values and external tare are switched-off.
MODE GWS/TARE GWS 1 and external tare is active.
GWS 1+2 GWS 1 and 2 are active, GWS2 is activated via control input.
3 CALIB Calibration menu – this is active only, if the password has been entered correctly
in 2.5PASS. For the calibration the sensor needs to be connected to the sensor
socket.
Sensor__ Sensor number or name of the sensor which is to be calibrated.
POINTDIS Measuring range with decimal indication of the sensor, e.g. 100,0; 200,0; 63,00;...
Call menu "POINTDIS", after pressing ENTER the final value of the sensor can be entered, by
PLUS or MINUS the numeric character can be edited, by ENTER the next figure can be edited, if all
figures are edited, by PLUS and/or MINUS the comma will be shifted. For the completion of the
input press ENTER, thereafter the final value is being logged in the GM 80.
UNIT Input of the physical unit, e.g. Kg, Ncm, t, gr, kN, N·m, bar...
DESIG Name of the sensor e.g. sensor 1,2,3, silo, tank, mixer, balance1, motor, test1..
CALIB Selection of the sensor type (active, passive, 4-20mA, with or without calib. control..)

Calibration Procedure:
ACT_wCON Active sensor with calibration control
0% LOAD unload sensor
100%Con after pressing ENTER the calibration takes place automatically.
SAVE query for takeover of calibration data
ACT_nCON Active sensor without calibration control
0% LOAD unload sensor
100%Con calibration by 100 % load (apply the nominal load/nominal torque) or switch to nominal
value
NOMVALUE enter the nominal value in mV/V or switch to 100 % load
SAVE query for takeover of calibration data
PAS_wCON Passive sensor with calibration control
0%LOAD unload sensor
100%Con after pressing ENTER the calibration takes place automatically.
SAVE query for takeover of calibration data
PAS_nCON Passive sensor without calibration control
0% LOAD unload sensor
100% LOAD calibration by 100 % load (apply the nominal load/nominal torque) or switch to nominal
value
NOMVALUE enter the nominal value in mV/V or switch to 100 % load
SAVE query for takeover of calibration data
CURRENT Sensor with 4 - 20mA
0% LOAD unload sensor
100% LOAD calibration by 100 % load (apply the nominal load/nominal torque) or switch to nominal
value
or NOMVALUE fixed value 4-20 mA
SAVE query for takeover of calibration data
Edit and Adjust Limit Values
In menu 2 SYSTEM - 2,9 INPUT - Setpoint the limit value parameters can be adjusted. If menu LIMIT VALUE SETS is
selected and confirmed by ENTER, the limit values are listed. Switch to the next limit value with the PLUS key. With the
MINUS key the switching level HI or LO can be selected.
Definition of the switching levels:
HI... if the measured value exceeds the SP, the output will be switched on.
if the measured value falls below the point of hysteresis, the output will be switched off.
LO.. if the measured value exceeds the SP, the output will be switched off.
if the measured value falls below the point of hysteresis, the output will be switched on.
The adjusted level is taken over by pressing ENTER. If ENTER was pressed, the SP can still be edited. With the keys PLUS
and/or MINUS the leading sign and the digits can be adjusted. Jump to the next digit with ENTER. By confirming with
ENTER the new adjusted SP is accepted; with ESC the new adjusted SP gets discarded.

Operation via the Serial Interface (SCI):
Through the serial interface, measurement values can be issued singly or automatically by the GM 80.
The commands can be sent to the GM 80 via a terminal program or PLC.
If several devices are connected to the RS232-BUS, none of the devices should be operated in the SCI-mode “AUTO”.
Protocol set-up
0x02 0xXX "x"
(STX) Address Command
At the device with address 0x00 all parameters (company header, sensor designation...) are issued when changing into the
measuring mode. If these parameters are not indicated, an address unequal 0x00 has to be
adjusted.
If the GM 80 is in the measuring mode, following commands are available:
ASCII HEX Description
0 0x30 Query continuous measured value (signed integer)
1 0x31 Query maximal value (signed integer)
2 0x32 Query minimal value (signed integer)
3 0x33 Tare display
4 0x34 Reset maximal value
5 0x35 Reset minimal value
6 0x36 Actuate calibration control for sensors with 100 % control resistance
7 0x37 Switch off calibration control for sensors with 100 % control resistance
A 0x41 Read-Out datalogger
B 0x42 Delete datalogger
C 0x43 Read-Out current sensor parameter
D 0x44 Read-Out status
E 0x45 Read-Out complete status
g 0x67 Change protocol setup
k 0x6B ENTER
l 0x6C PLUS
m 0x6D MINUS
n 0x6E ESC
Outside of the measuring mode following commands are available:
ASCII HEX Description
A 0x41 Read-Out datalogger
C 0x43 Read-Out current sensor parameter
D 0x44 Read-Out status
E 0x45 Read-Out complete status
a 0x61 Write time
b 0x62 Read-Out time
c 0x63 Write company header
d 0x64 Read-Out company header
e 0x65 Write all sensor parameters
f 0x66 Read-Out all sensor parameters
g 0x67 Change protocol setup
k 0x6B ENTER
l 0x6C PLUS
m 0x6D MINUS
n 0x6E ESC
Read-out of present sensor parameter:
Sensor designation 8Byte ASCII
Display final value 2Byte packed BCD-figure
Unit 3Byte
ASCII

Sensor type and digits 1Byte 0xAB: A ... Sensor type, B ... digit of the dec. point (binary coded)
Sensor type:
0xXXXX XXXX
||||
0000 ... active withcalibration control
0%load and 100% load calibration
0001 ... active without calibration
control 0%load and 100% load calibration
0010 ... active without calibration
control 0%load calibration and edit 100%load
V
0011 ... active without calibration
control edit 0%load V and 100%load V
0100 ... passive with calibration control
0%load and 100% load calibration
0101 ... passive without calibration
control 0%load and 100% load calibration
0110 ... passive without calibration
control 0%load calibration and edit 100%
load
in mV/V
0111 ... passive without calibration
control edit 0%load and 100% load in mV/V
1000 ... current 0%load
and 100% load calibration
1001 ... current 0%load
calibration and edit 100%load in mA
1010 ... current edit
0%load mA and 100%load mA
Dec. point:
0xXXXX XXXX
||||
|000 ... _5000___
|001 ... _5,000__
|010 ... _50,00__
|011 ... _500,0__
|100 ... 5,000___
0%load 2Byte
HEX-value (MSB/LSB)
100% load 2Byte HEX- value (MSB/LSB)
Read-out of status:
Status 2Byte general error condition of the GM80
Read-out of complete status:
Status 2Byte general error condition of the GM80
Meas. rate 1Byte 0x01 … 1000/sec
0x02 … 100/sec
0x03 ... 10/sec
0x04 ... 1/sec
Average value 1Byte 0x01 ... x/1
0x02 ... x/2
0x04 ... x/4
0x08 ... x/8
0x10 ... x/16
0x20 ... x/32
SCI_MODE 1Byte
0x00 ... interface off
0x04 … hand mode
0x08 … automatic mode
0x0C … trigger mode
SCI_MODE_DELAY 1Byte
0x02 …10ms
0x03 … 100ms
0x04 … 1s
0x05 … 10s
0x06 ... 1min
0x07 ... 10min
0x08 ... 1h
LOGGMODE 1Byte
0x00 ... logger off
0x04 ... hand mode
0x08 ... automatic mode
0x0C ... graph mode
0x10 ... screen mode
LOGGMODE_DELAY 1Byte 0x01 … 1ms
0x02 …10ms
0x03 … 100ms
0x04 … 1s
0x05 … 10s
0x06 ... 1min
0x07 ... 10min
0x08 ... 1h
Language 1Byte
0x00 ... GERMAN
0x02 ... ENGLISH
0x04 ... FRENCH
0x06 ... SPANISH
Protocol status 1Byte 0xXXXX XXXX (binary coded)
|||| ||||
|||| |||1 ... do not send conclusion character
|||| ||1 ... send CR/LF
|||| |1 ... send CR
|||| 1 ... send LF

Read Time:
Output: DAY.MONTH.YEAR
2xspace
HOURS:MINUTES:SECONDS
Write Time:
The writing is identically with the data block for receipt of time, however, the data block for writing is protected with a
checksum and the corresponding weighted checksum.
Read Company Header:
With this command the company header, which is stored in the GM 80, can be read.
Write Company Header:
The input is ended either if 256 characters are received or if the character ETX (0x03) Strg-C is contained in the character
string.
Change of Protocol Setup:
Protocol status 1Byte 0xXXXX XXXX (binary coded)
|||| ||||
|||| |||1 ... no closing character is sent
|||| ||1 ... send CR/LF
|||| |1 ... send CR
|||| 1 ... send LF
Calculation of the Checksum (CS) and the Weighted Checksum (gewCS)
The calculation takes place via all parameter bytes (without the command byte). At the CS all bytes are added (overflows
are not considered here). For the calculation of the gewCS the CS is added to the gewCS. At overflow the gewCS is
incremented by 1.

Formatting of the Serial Interface Output
Output format in SCI mode:
HAND: Algebraic sign, measured value, unit, time and CRLF
AUTO: 10ms Signed integer and CRLF
100ms Signed integer and CRLF
1s Algebraic sign, measured value, unit, time and CRLF
10s Algebraic sign, measured value, unit, time and CRLF
1min Algebraic sign, measured value, unit, time and CRLF
10min Algebraic sign, measured value, unit, time and CRLF
1h Algebraic sign, measured value, unit, time and CRLF
TRIGGER: Signed integer and CRLF
TRIGGER2: Signed integer and CRLF
Output format in LOGG mode:
HAND: Algebraic sign, measured value, unit, time and CRLF
AUTO: Algebraic sign, measured value,unit and CRLF
DIAGRAM: Algebraic sign, measured value,unit and CRLF
WINDOW: Algebraic sign, measured value,unit and CRLF
TRIGGER2: Algebraic sign, measured value,unit and CRLF
Adjustments in the SCI Mode
SCI OFF: At this adjustment a transfer of measured values from the GM 80 is disabled.
The GM 80 can be controlled however with the GM 80-commands.
HAND: In this mode a measured value is issued via the serial interface when the Enter key is pressed at the GM 80.
AUTO: In this mode a measured value is issued via the serial interface in the adjusted delay
TRIGGER: At a trigger event In this mode, a measured value is written in the logger. Since the trigger pulses may occur in
10ms raster and additional time-logg is not possible. The flank of the trigger pulse must be on HIGH for at least 4ms. Then it
must be on LOW for at least 6ms.
TRIGGER2: This mode functions like the trigger mode, however here the MIN value and the MAX value
are set back at a recognized trigger pulse. The display is set back to the display mode which was adjusted in
menu 2.9 INPUT-DISPLAY.
Connection to the Serial Interface
As a single device, the GM 80 can directly be connected to a PC by a serial 1:1 connecting cable.
By internal circuitry, up to 6 devices can be connected to the RS232 interface parallel.
The connection with the GM 80 takes place parallel via a 1:1 connection (Rx on Rx, Tx on Tx and GND on GND). The
connection to the pc then takes place with a zero-modem cable. In the BUS operation mode all GM 80 units operate as
SLAVE; a connected control as MASTER.

Operation and Function Principle of the GM 80-Data Logger
The data logger can, if the GM 80 is not in the measuring mode, be read by the menu option 2,7 LOGG - SENDING or by
the command "A" via the interface. Outside of the measuring mode the data logger is deleted only by the menu option 2,7
LOGG - DELETION.
If the GM 80 is in the measuring mode, the data logger can be read with the command "A" and be deleted with the
command "B".
If the measuring mode is being switched on from the menu option 1MEASURING-sensor selection,
the starting time of the measurement, the current sensor designation, the final value of the measuring range, the adjusted
measuring rate and the logger mode (e.g.: AUTO 1ms) are saved in the logger.
NOTE: All previous measured values are deleted here!
With the read-out of the data logger via the serial interface different adjustments are sent from the GM 80.
a) Company header
b) Starting time of the measurement
c) Sensor designation
d) Final display value
e) Adjusted measuring rate
f) Adjusted logger mode
g) Thereafter the measured values
In the HAND MODE the measured values are always logged with the time. The measured value is logged at the data in the
AUTOMODE. A time can be assigned to each measured value by the indicated starting time.
Since in GRAPHS and in the WINDOW MODE trigger events smaller than 1sec can occur, an additional time log is not
possible.
Adjustments in the Logg Mode
LOGG OUT: Here the data logger is switched off. The logg mode in the measuring mode is switched to
"LOGG OUT" as soon as the entire data logger has been edited.
HAND: In this mode a measured value is written into the data logger when the enter key was pressed at the GM 80. By an
additional logg of time, there is a time assignment for each measured value.
AUTO : In this mode in the adjusted Delay a measured value is written into the data logger. By the stored starting time there
is a time assignment for each measured value.
GRAPH: In this mode at a trigger event a measured value is written into the logger. Since the trigger pulses occur in 10ms
raster, an additional logg of the time is not possible. The flank of the trigger pulse must stand on HIGH for 4ms at least.
Afterwards on LOW for at least 6ms.
WINDOW: This mode reacts to increasing and/or decreasing flanks. At an increasing flank the logging of the measured
values is started. From now on the measured values are written in the data logger with 1ms raster. A decreasing flank ends
the recording.
TRIGGER2: This mode functions like the graph mode, however, here the MIN value and the MAX value
are set back at a recognized trigger pulse. The display is set back to the display mode which was adjusted in
menu 2.9 INPUT-DISPLAY.

Pin Assignment:

Supplement
Device Disposal:
Please dispose the unserviceable device according to the legal rules.
By this you meet the legal obligations and contribute to the environmental protection!
Tendance:
The device may be cleaned with a slightly moistened cloth.
FAQ – Trouble Shooting
Device can not be turned on
Battery/accumulator inserted correctly?
Connect power supply at operation with accumulators.
The display begins to flash.
Charge the accumulators and/or exchange the batteries.
The calibrated adjustments do not match with the sensor anymore.
Was the sensor overloaded?
Is the correct sensor selected?
Possibly recalibrate the sensor.
Wrong values are indicated after the calibration
Was the sensor type selected correctly?
At calibration with calibration control check sensor for this option.
NU-GM80PA-TG-E-0115