schildknecht DATAEAGLE COMPACT 4 Series Guide

Installation and commissioning manual
Wireless Data System
DATAEAGLE® 4XXX Compact
Schildknecht AG
D -71711 Murr –Haugweg 26
Tel +49 (0)7144 89718-0 - Fax +49 (0) 7144 8971829
Email: office@schildknecht.ag - Internet: www.schildknecht.ag
DATAEAGLE 4XXX Compact
Version: 14.04.2020

Montage und Inbetriebnahme DATAEAGLE 4XXX Compact
© Copyright
Schildknecht AG
All rights reserved.
No part of this publication
may be reproduced or
translated in full or in part
without prior written per-
mission.
Right to make changes
Changes may be made
at any time to the form,
equipment and technol-
ogy of items covered in
this documentation. For
this reason, no claims re-
lating to the aforemen-
tioned may be derived
from the information,
illustration and descrip-
tions provided in these
operating instructions for
appliances or systems
manufactured after the
date of issue of these op-
erating instructions.
Warranty
Schildknecht AG can ac-
cept no liability for indi-
rect damage or direct
damage, incidental dam-
age, consequential dam-
age or compensation for
expenses incurred by
performance of contract
which arise from deliv-
ery, provision and use of
this material.
Introduction

Montage und Inbetriebnahme DATAEAGLE 4XXX Compact
To start with, we have a few important things to say about
safety. Please observe these instructions without fail, in order
to avoid property damage and personal injury.
We show you step by step how to install the system, put it
into operation and how to operate it.
Any questions? First, have a look in the table of contents.
You will quickly find what you are looking for.
If you do need us in person: just call us or send a fax:
Schildknecht AG
Haugweg 26
D -71711 Murr
Phone
+49 / (0) 7144 89718-0
Fax
+49 / (0) 7144 8971829
Internet
www.schildknecht.ag
e-mail
WWW
e-mail
FAX

Montage und Inbetriebnahme DATAEAGLE 4XXX Compact
List of contents
Subject Page no.
Introduction 1-1
1. General information 1-1
1.1. Guide to symbols 1-1
1.2. Copyright and brand names 1-1
1.3. Declaration of conformity and EC directives 1-1
2. Safety instructions 2-1
2.1. Intended use 2-1
2.2. General information 2-1
2.3. Installations instructions 2-2
2.4. Safety instructions for operation 2-2
2.5. Personnel qualification 2-3
3. Structure 3-1
3.1. System description 3-1
3.2. Radio module 3-2
4. Installation of new devices 4-1
4.1. Overview Installation 4-1
4.2. Install unit on top-hat rail 4-2
4.3. Install antenna cable 4-3
4.4. Connect Ethernet plug 4-4
4.5. Connect power supply 4-4
5. Extension and exchange 5-1
5.1. Preparation 5-1
5.1.1. System requirements 5-1
5.1.2. Create a new folder 5-1
5.1.3. Microsoft Internet Explorer 5-2
5.1.4. Install USB drivers 5-3
5.1.5. Install Dataeagle Wizard 5-7
5.2. Extension 5-9
5.2.1. Additional Profinet device / Safety Node (SN) to existing or new
Radio Slave 5-9
5.2.2. Additional Radio Slave 5-9
5.2.3. Start Dataeagle Wizard 5-10
5.2.4. Configure Radio Master 5-11
5.2.5. Configure Radio Slave 5-16
5.3. Exchange 5-19
5.3.1. Remove wiring 5-20

Montage und Inbetriebnahme DATAEAGLE 4XXX Compact
5.3.2. Remove old module 5-20
5.3.3. Install new module 5-20
5.3.4. Start Dataeagle Wizard 5-21
5.3.5. Procedure for exchanging radio modules 5-22
5.3.6. Example 1: Exchange of a Radio Slave 5-23
5.3.7. Example 2: Exchange of a radio master 5-30
6. Increasing the system availability (Profinet only) 6-1
6.1. Function 6-1
6.2. Setting of the filter time at Radio Master and Radio Slave 6-1
6.3. Typical values for the filter time 6-5
6.3.1. Default 6-5
6.3.2. Recommendation for operation 6-5
6.3.3. Recommendation for commissioning 6-5
6.3.4. Recommendation for applications with Profisafe 6-5
7. Dismantling and disposal 7-1
8. Tips and Tricks 8-1
8.1. Improving the EMC safety 8-1
8.1.1. Introduction 8-1
8.1.2. Basic guidelines 8-1
8.2. Guidelines for optimized installation of antennas 8-5
8.3. Advices for troubleshooting 8-7
9. Technical specifications 9-1

Installation and commissioning DATAEAGLE 4XXX Compact 1-1
Chapter 1 –General information
1. General information
1.1. Guide to symbols
This section contains an explanation of the symbols used in
this manual.
Indicates an imminently hazardous situation which, if not
avoided, may result in death or serious injury.
Indicates a potentially hazardous situation which, if not
avoided, may result in property damage.
Indicates sections which contain important information.
Indicates work operations which need to be carried out.
This symbol is followed by a description about how the status
of the system changes after an operation has been carried
out.
1.2. Copyright and brand names
Brand names and product names mentioned in this manual
are trademarks or registered trademarks of their respective
owners.
Microsoft Windows 7, Windows Vista, Windows 2000, Win-
dows XP and Microsoft Internet Explorer are registered
trademarks of Microsoft Corp.
Adobe Reader is a registered trademark of Adobe Systems
Corp.
DATAEAGLE® is a registered trademark of Schildknecht AG.
1.3. Declaration of conformity and EC
directives
Information about the declaration of conformity and about EC
directives can be found under:
http://www.schildknecht.ag/download/dataeagle-konformitaetserklaerung
CAUTION

Installation and commissioning DATAEAGLE 4XXX Compact 2-1
Chapter 2 - Safety instructions
2. Safety instructions
2.1. Intended use
Information about the intended use can be found in the oper-
ating instructions wireless data systems DATAEAGLE.
2.2. General information
In order to guarantee safe use and fault-free operation, the
according safety instructions have to be observed under all
circumstances.
Safety instructions which apply to all product families are de-
scribed in the operating instructions for wireless data sys-
tems DATAEAGLE. This manual is part of the system docu-
mentation. Read these instructions before installation and
commissioning of the wireless data system.
Safety instructions which apply only to an individual wireless
data system are described below and in the according sec-
tion of this installation and commissioning manual.

Installation and commissioning DATAEAGLE 4XXX Compact 2-2
Chapter 2 - Safety instructions
2.3. Installations instructions
Country licenses can be found in the attached declara-
tion of conformity.
Risk of electrical shock.
Always disconnect the modules from the power source
when working on the modules (installation, etc.)!
Risk of injury.
Comply with the local regulations and safety instruc-
tions during installation!
Static charges can damage electronic devices.
Remove electrostatic discharge from your body before
touching the device!
The modules must not be opened or modified (except
the steps described in this manual). Do not repair the
module yourself, replace it with an equivalent module.
Repairs may only be carried out by the Schildknecht AG.
The Schildknecht AG is not liable for damage resulting
from a failure to comply.
2.4. Safety instructions for operation
Electromagnetic radiation.
Keep at least a distance of 20 cm to the antennas when
the devices are in operation.
CAUTION
CAUTION

Installation and commissioning DATAEAGLE 4XXX Compact 2-3
Chapter 2 - Safety instructions
2.5. Personnel qualification
Only qualified personnel may carry out the following tasks:
Installation
Commissioning
Operation
Maintenance
Within the context of safety regulations, qualified personnel
are individuals authorized to commission, to ground, and to
identify equipment and systems in accordance with the
safety-engineering standards.
All operating personnel must be trained accordingly.
Personnel involved with operating the unit in conjunction with
controllers must possess sound programming skills for the in-
dividual controller and programming language in question.

Installation and commissioning DATAEAGLE 4XXX Compact 3-1
Chapter 3 –Structure
3. Structure
3.1. System description
The system DATAEAGLE 4xxx is used for a transparent
Ethernet data transmission. It consists of a radio master and
up to 4 radio slaves (depending on the device type).
The series DATAEAGLE 4xx2, 4xx3 and 4xx5 is optimized
for Profinet and openSAFETY via UDP.
Up to 6 Profinet devices or 16 Safety Nodes (SN) can be
connected to one or more radio slaves (depending on the de-
vice type).
The radio links work like an Ethernet cable.
Each radio module is identified by its address.
Subsequently the terms Ethernet and Profinet are used
equivalently. Differences are described where appropriate.

Installation and commissioning DATAEAGLE 4XXX Compact 3-2
Chapter 3 –Structure
3.2. Radio module
The radio module transmits the signals via radio and is avail-
able in two radio technologies.
Radio modules are configured with the software Dataeagle
Wizard (see chapter 5.1)
New devices are pre-configured in the factory.
Further settings are not necessary.
Type
Radio Technology
Ethernet
Profinet-Devices
Safety Nodes
Radio-Slaves
4710
2,4 GHz BT / 100mW
10/ 100MBit
--
--
max. 4
4712
2,4 GHz BT / 100mW
10/ 100MBit
max. 6
max. 16
max. 4 (PN)
max. 1 (openSAEFTY)
4713
2,4 GHz BT / 100mW
10/ 100MBit
max. 6
--
max. 4
4715
2,4 GHz BT / 100mW
10/ 100MBit
max. 4
--
max. 1
4333
869 MHz / 500mW
10/ 100MBit
max. 4
--
max. 4

Installation and commissioning DATAEAGLE 4XXX Compact 3-3
Chapter 3 –Structure
The illustration shows all connections of the radio module.
The table shows the significance of the LEDs at the
radio module:
Name
Col-
our
Function
ON
Green
Power ok
BF
Red
Status display at Dataeagle Master
On: no reception of Ethernet telegrams
Flashing (Profinet):
Error (one of the connected PN partici-
pants is not exchanging data)
Off (Profinet): everything ok (all con-
nected PN participants are exchanging
data)
RX
Yel-
low
Receiving radio data
LINK
Blue
DE47XX:
Bluetooth connection established
DE43XX:
On or flashing when connected
Antenna con-
nection
Power supply
+24V,GND,PE
USB
connection
(configuration)
Status LEDs
Ethernet
connection
(Switch)
Relay output
(radio control)

Installation and commissioning DATAEAGLE 4XXX Compact 4-1
Chapter 4 –Installation of new devices
4. Installation of new devices
Please be certain to read the guidelines in chapter 7
„Tips and Tricks – improvement of the electromagnetic
compatibility (EMC)“. Observe these guidelines during
the complete installation procedure. Thereby you avoid
electromagnetic interferences and you improve the data
transmission quality.
New devices are pre-configured in the factory.
Further settings are not necessary.
4.1. Overview Installation
The installation is very easy and is carried out according to
the procedure shown below:
Install module on top-hat rail
Connect antenna cable
Connect Profibus plug
Connect power supply
In case of limited space in the control cabinet:
Connect the power supply before you install the unit on
the top-hat rail.

Installation and commissioning DATAEAGLE 4XXX Compact 4-2
Chapter 4 –Installation of new devices
4.2. Install unit on top-hat rail
Place the unit diagonally from above on the top-hat rail.
Press the unit strongly downwards.
Nose above the
top-hat rail
Foot catch
snaps in

Installation and commissioning DATAEAGLE 4XXX Compact 4-3
CAUTION
Chapter 4 –Installation of new devices
4.3. Install antenna cable
Connect the antenna cable to the antenna connection
of the radio module.
The radio module may be damaged if the antenna cable
is fastened too tight.
Connect the antenna cable only hand-tight.
Install the antenna at the designated place.
Observe the guidelines for an optimum antenna installa-
tion in chapter 7 „Tips and Tricks“.

Installation and commissioning DATAEAGLE 4XXX Compact 4-4
Chapter 4 –Installation of new devices
4.4. Connect Ethernet plug
Connect the Ethernet plug.
4.5. Connect power supply
Connect the power supply according to the diagram
shown below. Either the 9-33 V supply of the control
cabinet can be used.
Connect the PE cable to the radio module.

Installation and commissioning DATAEAGLE 4XXX Compact 4-5
CAUTION
Chapter 4 –Installation of new devices
PE has to be connected with control cabinet round! If the
PE is not connected the noise filter cannot filter interfer-
ences on 9-33V DC power supply line. These may cause
malfunctions, errors or the destruction of the device.
Supply source needs to be in compliance with SELV and
LPS output according UL/IEC 60950-1 or ES1 and PS2
output according UL/IEC 62368-1.
A self-healing 0,7A fuse is integrated into the input
circuit. This fuse cannot be exchanged. The device has
to be disconnected from the power supply for approx. 2
minutes after the fuse has been triggered. Ensure that
the power supply provides 9 to 33 V DC before you
switch on the supply voltage.
The output „REL“ switches on radio reception the
supply voltage which is applied to the 9-33 V input.
(I REL max. 500mA)
This output can be used for monitoring the radio link.
The relay drops after an adjustable time without radio re-
ception.
A detailed description of the radio monitoring function is
not part of this manual.
Do not connect the output „REL“ when you don’t use
this function.

Installation and commissioning DATAEAGLE 4XXX Compact 5-1
Chapter 5 –Extension and exchange
5. Extension and exchange
If the system is extended or if modules are exchanged the
modules must be newly configured after installation. There-
fore the USB drivers and the software Dataeagle Wizard
must be installed on your PC and the radio module has to be
connected to the PC.
Do not yet connect the USB cable to the PC!
5.1. Preparation
5.1.1. System requirements
You need a PC with:
Operating system Windows 7, Vista, XP oder 2000.
Microsoft Internet Explorer.
Acrobat Reader.
Decompression program (WinRAR, WinZIP or similar).
One free USB interface.
5.1.2. Create a new folder
Create a new folder (e.g. Dataeagle).
Store the data which you will download in the next steps
into this folder.

Installation and commissioning DATAEAGLE 4XXX Compact 5-2
Chapter 5 –Extension and exchange
5.1.3. Microsoft Internet Explorer
To ensure a safe function it is important that you define Mi-
crosoft Windows Explorer as standard browser before you in-
sert the CD ROM into the drive.
Only when Microsoft Internet Explorer is not the stand-
ard browser:
Call the internet options via control panel.
Define the Internet Explorer as standard browser.

Installation and commissioning DATAEAGLE 4XXX Compact 5-3
Chapter 5 –Extension and exchange
5.1.4. Install USB drivers
For data transmission between PC and radio module it is
necessary to install the USB drivers.
Insert the CD in your CD-ROM drive.
The browser shows the available documents and down-
loads for all Schildknecht products.
Scroll until you find your product, e.g. DE Compact
4712.
Click on
This manual suits for next models
8
Table of contents
Other schildknecht Microphone System manuals