Table 2: Error messages / flash codes red diagnostic LED
Flash codes (red) Designation Autonomous switch-off after Error cause
1 flash pulse Error (warning) at output Y1 30 min Fault in output test or voltage
at output Y1, although the
output is disabled.
2 flash pulses Error (warning) at output Y2 30 min Fault in output test or voltage
at output Y2, although the
output is disabled.
3 flash pulses Error (warning) cross-wire short 30 min Cross-wire short between the
output cables or fault at both
outputs
4 flash pulses Error (warning) temperature too
high
30 min The temperature measurement
reveals an internal temperature
that is too high
5 flash pulses Actuator fault 0 min Incorrect or defective actuator
6 flash pulses Error actuator combination 0 min An invalid combination of
actuators was detected (blocking
bolt detection or tamper
attempt).
Continuous red signal Internal fault / overvoltage or
undervoltage fault
0 min Device defective /
supply voltage not within
specifications
6.5 直列診断機能SD付き電磁ロック付きインターロック
シリアル診断ケーブル付き電磁ロック付きインターロックには、従来型の診断出力の代わりに、シリアル入出力ケーブルを有しています。直列接続する場合は、これらの入力・出力ケーブルは直列接続により診断データを伝送します。
最大31個の電磁ロック付きインターロックが直列に接続出来ます。シリアル診断ラインの評価には PROFIBUSゲートウェイ SD-I-
DP-V0-2 又はユニバーサルゲートウェイ SD-I-U-...
を使用します。このシリアル診断用インターフェースはスレーブとして既存のフィールドバスシステムに組み込めます。この様にして、診断信号はPLCで評価出来ます。
SDゲートウェイの接続に関する必要なソフトウェアは、products.schmersal.comからダウンロード出来ます。
応答データと診断データは、直列に接続された個々の電磁ロック付きインターロック用に自動的・継続的にPLCの入力バイトに書き込まれます。電磁ロック付きインターロック用の要求データは、PLCの出力バイトを通じてコンポーネントに伝送されます。SDゲートウェイと電磁ロック付きインターロック間の通信エラーが発生した場合、電磁ロック付きインターロックのスイッチング状態が維持されます。
Error
Errors which no longer guarantee the function of the safety switchgear (internal errors) cause the safety outputs to
be disabled within the duration of risk. The fault is reset, when the cause is eliminated and bit 7 of the request
byte changes from 1 to 0 or the safety guard is opened. Faults at the safety outputs are only deleted upon the next
release, as the fault rectification cannot be detected sooner.
FAutomatic, electronic locking takes place if more than one fault is detected at the safety outputs or a cross circuit is
detected between Y1 and Y2. This means that normal fault acknowledgement is no longer possible. To reset this type of
interlock, the solenoid interlock must be isolated from the supply voltage after elimination of the error causes.
Error warning
A fault that does not immediately endanger the safety function of the safety switchgear (e.g. too high ambient
temperature, safety output at external potential, cross-circuit) leads to delayed shutdown. This signal combination,
diagnostic output disabled and safety channels still enabled, can be used to stop the production process in a
controlled manner.
An error warning is deleted when the cause of error is eliminated.
If the fault warning remains on for 30 minutes, the safety outputs are also switched off (red LED flashes).
診断エラー(警告)
応答バイトにおいてエラー(警告)が発せられた場合、詳細な情報を読み出す事が出来ます。
18-20