Schweitzer Engineering SEL-751 User manual

qSELECT Power Supply With I/O (Slot A)
wSELECT Processor and Communications Card (Slot B)
eSELECT I/O Expansion Card (Slot C: see table)
rSELECT I/O Expansion Card (Slot D: see table)
tSELECT I/O Expansion Card (Slot E: see table).
ySELECT 4ACI/3AVIor4ACICard(SlotZ)
uDevice Case
iRear-Panel Mounting Screws
oRear Panel
Refer to the Model Option Table on the SEL website for ordering details Rear-Panel Slot
Card Type A B C D E Z
SELECT PSIO/2 DI/3 DOa
aRefer to the SEL-751 two-line and touchscreen display Model Option Tables (MOT) for power supply and CPU board variants.
●n/a n/a n/a n/a n/a
SELECT CPU/COMan/a ●n/a n/a n/a n/a
SELECT EIA-232/EIA-485 n/a n/a ●n/a n/a n/a
SELECT DeviceNet n/a n/a ●n/a n/a n/a
SELECT 3 DI/4 DO/1 AO (one card per relay) n/a n/a ●●●n/a
SELECT 4 DI/4 DO n/a n/a ●●●n/a
SELECT 4 DI/3 DO (1 Form B, 2 Form C) n/a n/a ●●●n/a
SELECT 8 DI n/a n/a ●●●n/a
SELECT 14 DI n/a n/a ●●●n/a
SELECT 8 DO n/a n/a ●●●n/a
SELECT 8 AI n/a n/a ● ● ● n/a
SELECT 4 AI/4 AO (one card per relay) n/a n/a ● ● ●n/a
SELECT 10 RTD n/a n/a n/a ● n/a n/a
SELECT 2 AVI/4 AFDI (MOT…x70x…) n/a n/a n/a n/a ●n/a
SELECT 2 AVI/4 AFDI (MOT…xL0x…) n/a n/a n/a n/a ●n/a
SELECT 8 AFDI (MOT…x77x…) n/a n/a n/a n/a ●n/a
SELECT 4 ACI/3 AVI (MOT…x81/82/83/85/86/87x…) n/a n/a n/a n/a n/a ●
SELECT 4 ACI/3 AVI (MOT…xL1/L2/L3/L5/L6/L7x…) n/a n/a n/a n/a n/a ●
SELECT 4 ACI (MOT…xA1/A2/A3/A5/A6/A7x…) n/a n/a n/a n/a n/a ●
6
7
8
9
1
2
3
4
5
SEL-751 Card Options

2
The SEL-751 offers flexibility in tailoring I/O to your specific application. The SEL-751 has six rear-panel slots, labeled
as Slots A, B, C, D, E, and Z. Slots A, B, and Zare base unit slots, each associated with a specific function. Optional
digital/analog I/O cards are available for the SEL-751 in Slots C, D, and E. Optional communications cards are available
only for Slot C; an RTD card is available only for Slot D; the 1 A/5 A/200 mA CT combinations for voltage/current or
current only cards are available only on Slot Z; and a voltage/arc-flash card is available for Slot E. The previous figure
and table show the slot allocations for the cards.
Because installations differ substantially, the SEL-751 offers a variety of card configurations that provide options for the
many diverse applications. Choose the combination of option cards most suited for your application from the selection.
Warnings
Card Installation for Slots C, D, E, and Z
Use the following procedure to install or replace any one of the cards into Slots C, D, E, or Zof the base unit:
1. Save the settings and event report data before installing the new card in the relay.
2. Remove the power supply voltage qfrom terminals A01 (+/H) and A02(–/N), and then remove the ground
wire from the green ground screw (GND).
3. Disconnect all the connection plugs.
4. Remove the eight (8) screws on the rear iand remove the rear cover.
5. Remove the plastic filler plate covering the slot associated with the card being installed.
6. Insert or replace the card in the correct slot.
For proper electromagnetic interference protection, make sure the contact fingers on the printed circuit
board are bent at approximately a 130° angle relative to the board.
7. Before reattaching the rear cover, check for and remove any foreign material that may remain inside the
SEL-751 case.
8. Carefully reattach the rear cover.
9. Reinstall the eight (8) screws that secure the rear cover to the case i.
10. Apply power supply voltage qto terminals A01 (+/H) and A02 (–/N), and reconnect the ground wire to the
green ground screw (GND).
11. If the card is in the proper slot, the front panel displays the following:
STATUS FAIL
X Card Failure
If you do not see this message and the ENABLED light is turned on, the card was inserted in the wrong slot.
Begin again at Step 2.
If you do see this message, then proceed to Step 12.
12. Press the ESC pushbutton.
13. Press the Down Arrow pushbutton until STATUS is highlighted.
DANGER
Disconnect or de-energize all
external connections before
opening this device. Contact
with hazardous voltages and
currents inside this device
can cause electrical shock
resulting in injury or death.
WARNING
Equipment components are sensitive to
electrostatic discharge (ESD).
Undetectable permanent damage can
result if you do not use proper ESD
procedures. Ground yourself, your work
surface, and this equipment before
removing any cover from this equipment.
WARNING
To install an option card the relay must
be de-energized and then reenergized.
When reenergized, the relay will
reboot. Therefore, de-energize the
protected equipment before installing
the option card to prevent damage to
the equipment.
WARNING
Have only qualified
personnel service this
equipment. If you are not
qualified to service this
equipment, you can injure
yourself or others, or cause
equipment damage.

3
14. Press the ENT pushbutton.
The front panel displays the following:
STATUS
Relay Status
15. Press the ENT pushbutton.
The front panel displays the following:
Serial Num
000000000000000000000000
16. Press the ENT pushbutton.
The front panel displays the following:
Confirm Hardware
Config (Enter)
17. Press the ENT pushbutton.
The front panel displays the following:
Accept New Config?
No Yes
18. Select Yes and press the ENT pushbutton.
The front panel displays the following:
Config Accepted.
Enter to Reboot
19. Press ENT.
The relay restarts and the ENABLED light is turned on to indicate the card was installed correctly.
After reconfiguration, the relay updates the part number, except for the digits shown below. These digits
remain unchanged, i.e., these digits retain the same character as before the reconfiguration. A
communications card (DeviceNet or EIA-232/EIA-485) installed in Slot C will be reflected as an empty
slot in the part number. A regular 4 DI/4 DO card and a hybrid 4 DI/4 DO card have the same device ID.
When interchanging these two cards, the part number for the respective slots should be updated manually.
Use the STATUS command to view the part number.
Use the PARTNO command from the Access Level 2 to enter the exact part number of the relay.
20. Update the side-panel drawing with the drawing sticker provided in the option card kit. If necessary,
replace the rear panel with the one applicable for the card and attach the terminal marking label provided
with the card to the rear-panel cover.
21. Reconnect all connection plugs, and add any additional wiring/connectors required by the new card.
PART NUM = 751001B5X1X7086020X

4
2011–2017 Schweitzer Engineering Laboratories, Inc. All rights reserved. All trademarks are the property of their respective holders. SEL products appearing in this document may
be covered by U.S. and foreign patents. The information in this document is provided for informational use only and is subject to change without notice.
*PLS751-01* Date Code 20170315
Slot B CPU Board Replacement
When replacing the Slot Bcard, please perform the following:
1. Ensure that the card has the latest firmware from the factory.
2. Review the firmware revision history for the changes that were made; note that new settings added, if any,
might affect existing settings in the relay or its application.
3. Save all the settings and event reports before replacing the card.
4. If the IEC 61850 protocol option was used previously, verify that the IEC 61850 protocol is still
operational after the replacement. If not, reenable it. Refer to Protocol Verification for Relays With
IEC 61850 Option in Appendix B: Firmware Upgrade Instructions of the instruction manual.
Perform the following steps to replace the existing CPU board with a new board:
1. Turn off the power to the relay.
2. Use a ground strap between yourself and relay.
3. Disconnect the terminal blocks and CT/PT wires.
4. Remove the rear panel.
5. Remove the main board from its slot and insert the new board.
6. Install the new rear panel and reconnect the terminal blocks and CT/PT wires.
7. Apply new side stickers to the relay.
8. Turn on the relay and log in via terminal emulation software.
9. Issue the STA command and accept the new configuration.
10. From Access Level 2, type CAL to enter the CAL level.
Do not modify any calibration settings other than those listed in this procedure.
The CAL level default password is CLARKE.
11. From the CAL level issue the SET C command.
12. Enter the relay serial number and part number to the appropriate values, type END, and then save the
settings.
13. Issue the STAC command to reboot the relay.
14. Issue the STA command to verify that the serial and part numbers of your relay are correct.
Slot A Power Supply Card
If replacing a power supply card, change the part number accordingly, using the PARTNO command from
Access Level 2. Install new side stickers on the relay.
Table of contents
Popular Relay manuals by other brands

Modine Manufacturing
Modine Manufacturing 6-582 instructions

FANOX
FANOX C 9 Installation and Adjustment guide

IFM Electronic
IFM Electronic efector 100 G1502S Original operating instructions

HANYOUNG NUX
HANYOUNG NUX HSR-3SL instruction manual

i-MO
i-MO iSmart v4 Series instruction manual

Functional Devices
Functional Devices RIBW24B-EN3 manual